INSTALLATION INSTRUCTIONS
AIR HANDLER : AHF
X40159 Rev. E
Specifications subject to change without notice.
9
Table 5 - ELECTRIC HEATHER STATIC PRESSURE DROP
Single-Phase
CFM
EHIA
05
EHIA
07
EHIA
10
EHIA
15
EHIA
20
EHIA
25
In wc
600
0.01
0.01
0.01
–
–
–
700
0.01
0.01
0.01
–
–
–
800
0.01
0.01
0.01
0.01
–
–
900
0.01
0.01
0.01
0.01
–
–
1000
0.01
0.01
0.01
0.01
0.02
–
1100
0.01
0.01
0.01
0.02
0.02
–
1200
0.01
0.01
0.01
0.02
0.02
–
1300
0.01
0.02
0.02
0.02
0.02
–
1400
0.01
0.02
0.02
0.02
0.03
0.03
1500
0.01
0.02
0.02
0.02
0.03
0.04
1600
0.01
0.02
0.02
0.03
0.03
0.04
1700
0.01
0.02
0.02
0.03
0.03
0.04
1800
0.01
0.02
0.02
0.03
0.04
0.04
1900
0.01
0.02
0.02
0.03
0.04
0.05
2000
0.01
0.02
0.02
0.03
0.04
0.05
ACCESSORIES
ELECTRIC AIR CLEANER
The Electronic Air Cleaner may be connected to AHF as shown in
Figure 14
. This method requires a field supplied transformer. See
Electronic Air Cleaner literature for kit requirements.
HUMIDIFIER
Connect humidifier and humidistat to air handler unit as shown in
Figures 15 and 16
.
Three-Phase
CFM
N/A
N/A
EHIA
10
EHIA
15
EHIA
20
EHIA
25
In wc
600
0.01
–
–
–
700
0.01
–
–
–
800
0.01
0.01
–
–
900
0.01
0.01
–
–
1000
0.01
0.01
0.02
–
1100
0.01
0.02
0.02
–
1200
0.01
0.02
0.02
–
1300
0.02
0.02
0.02
–
1400
0.02
0.02
0.03
0.03
1500
0.02
0.02
0.03
0.04
1600
0.02
0.03
0.03
0.04
1700
0.02
0.03
0.03
0.04
1800
0.02
0.03
0.04
0.04
1900
0.02
0.03
0.04
0.05
2000
0.02
0.03
0.04
0.05
AHF
AHF