SEQUENCE OF OPERATION 

A. CONTINUOUS FAN 

Thermostat closes R to G. G energizes fan relay on FAN CONTROL 
BOARD  which  completes  the  high  voltage  circuit  to  indoor  blower 
motor. When G is de-energized, there is a built in 90 second blower-
off 

time  delay  relay

  (TDR).  To  disable  the  TDR  feature,  snip  the 

jumper wire JW1. 

B. COOLING MODE 

Air Conditioner Only: 

Thermostat  energizes  R  to  G  and  Y.  G  energizes  fan  relay  on  fan 
control board  which completes high-voltage circuit to  indoor blower 
motor. Y energizes the 24 low-voltage contactor in condensing unit. 
When call is satisfied, Y drops out and there is a 90 second blower 
TDR before fan relay opens. 

Heat Pump: 

Same as above - except thermostat will also energize O for reversing 
valve operation in cooling mode. O will typically remain energized by 
the  thermostat  (after  cooling  call  is  satisfied),  or  until  the  mode  is 
changed to heating. 

C. HEAT PUMP 

Cooling Mode: 

Thermostat energizes R to G, Y and O. G energizes indoor an relay 
on fan control board  which completes  high-voltage circuit  to  indoor 

blower motor. Y energizes the outdoor 24V low-voltage circuit in heat 
pump to energize compressor. O energizes reversing valve in cooling 
mode and typically remains energized until the mode is changed to 
heating.  When  thermostat  cooling  call  is  satisfied.  Y  drops  out.  O 
remains energized, and there is a 90 second TDR before indoor fan 
relay opens.

 

Heating Mode: 

Thermostat energizes R to G and Y only (no O signal in heating). G 
energizes  indoor  fan  relay  on  fan  control  board  which  completes 
high-voltage circuit to indoor blower motor. Y energizes the outdoor 
24V  low-voltage  circuit  in  heat  pump  to  energize  compressor.  The 
reversing  valve  is  not  energized  in  heating  unless  a  defrost  cycle 
should  occur. When call is satisfied,  Y  drops  out  and  there is  a 90 
second TDR before indoor fan relay opens. 

D. HEAT PUMP HEATING WITH AUXILIARY 

ELECTRIC HEAT 

Cooling Mode: 

Same operation as above in Heat Pump Cooling Mode. 

Heating Mode: 

Same  operation  as  above  in  Heat  Pump  Heating  Mode  with  the 
addition of W. Thermostat energizes R to G, Y, and W. W energizes 
electric  heat  relay(s)  which  completes  circuit  to  heater  element(s). 
When  W  is  de-energized,  electric  heat  relay(s)  open,  turning  off 
heater elements. The White wire in pigtail connects W2, W3, and E 
together. This may be separated for heater staging when available, 
see electric heat kit for more information. 

E. ELECTRIC HEAT OR EMERGENCY HEAT MODE 

Thermostat closes R to W. W energizes electric heat relay(s) which 
completes circuit  to heater  elements(s). Blower motor is  energized 
through N.C. (normally closed) contacts on fan relay. When W is de-
energized, electric heat relay(s) opens. 

CARE AND MAINTENANCE 

The  system  should  be  regularly  inspected  by  a  qualified  service 
technician. Consult the servicing dealer for recommended frequency. 
Between visits, the only consumer service recommended or required 
is air filter maintenance and condensate drain operation. 

AIR FILTER 

Inspect air filters at least monthly and replace or clean as required. 
Disposable type filters should be replaced. Reusable type filters may 
be cleaned by soaking in mild detergent and rinsing with cold water. 
The frequency of cleaning depends upon the hours of operation and 
the local atmospheric conditions. Install filters with the arrows on the 
side  pointing  in  the  direction  of  air  flow.  Clean  filters  keep  unit 
efficiency high. 

LUBRICATION  

The bearings of the blower motor are permanently lubricated. 

CONDENSATE DRAINS 

During  the  cooling  season  check  the  condensate  drain  lines  to  be 
sure that condensate is flowing from the primary drain but not from 
the  secondary  drain.  If  condensate  ever  flows  from  the  secondary 
drain, the unit should be promptly shut off and the condensate pan 
and drains cleaned to insure a free flowing primary drain.

Содержание AHF080014

Страница 1: ...Electrical Code CSA C22 1 Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injur...

Страница 2: ...approved heaters electric heat accessory models EHIA only Heaters that are not factory approved could cause damage which would not be covered under the equipment warranty CAUTION CUT HAZARD Failure t...

Страница 3: ...recommendations NOTE Local codes may limit application of systems without a ducted return to single story dwellings HORIZONTAL LEFT AND RIGHT INSTALLATIONS The air handler cabinets can be installed in...

Страница 4: ...o Figure 6 All electrical work MUST conform with the requirements of local codes and ordinances and the National Electrical Code NFPA 70 current edition The low voltage transformer and the fan control...

Страница 5: ...ews 3 Connect the 9 pin plug from No Heat Kit wiring into the receptacle that attaches to fan control board 4 Connect ground wire to unit ground lug 5 Connect 208 230V power lead from field disconnect...

Страница 6: ...2 9 3 6 15 2 14 105 32 1 14 230 AHF16 208 1 60 Single 1 2 2 9 3 6 15 2 14 105 32 1 14 230 AHF20 208 1 60 Single 3 4 6 0 7 5 15 2 14 90 27 1 14 230 Figure 8 Wiring Layout Air Conditioning Unit Cooling...

Страница 7: ...r Single Phase EHIA05KB KN EHIA15KB EHIA25KB10 EHIA07KB KN EHIA20KB EHIA10KB KN EHIA25KB EHIA15KB EHIA20KB EHIA25KB Three Phase EHIA10HB EHIA10HB EHIA20HB EHIA15HB EHIA15HB EHIA25HB EHIA20HB EHIA20HB...

Страница 8: ...lectric heat Deduct heater static shown in heater static table Deduct coil static See Coil Specification Sheet Deduct 20 in wc 50 Pa for Downflow Subbase Kit Table 4 Airflow is blower only no coil att...

Страница 9: ...0 02 0 02 0 03 0 04 0 04 1900 0 01 0 02 0 02 0 03 0 04 0 05 2000 0 01 0 02 0 02 0 03 0 04 0 05 ACCESSORIES ELECTRIC AIR CLEANER The Electronic Air Cleaner may be connected to AHF as shown in Figure 1...

Страница 10: ...en call is satisfied Y drops out and there is a 90 second TDR before indoor fan relay opens D HEAT PUMP HEATING WITH AUXILIARY ELECTRIC HEAT Cooling Mode Same operation as above in Heat Pump Cooling M...

Страница 11: ...INSTALLATION INSTRUCTIONS AIR HANDLER AHF X40159 Rev E Specifications subject to change without notice 11 WIRING DIAGRAM...

Страница 12: ...RAPPER 9 PANEL TOP ASS Y 10 LEFT SIDE WRAPPER 7 SIDE BLOWER DECK 8 REAR BLOWER DECK 1 BLOWER DOOR ASS Y 6 FRONT BLOWER DECK DETTSON INDUSTRIES INC DETTSON COM ITEM NO CURRENT PART DESCRIPTION MF080014...

Отзывы: