DETAIL  A

ALWAYS REMOVE POWER & BATTERY

CONNECTIONS BEFORE SERVICING UNIT

24VAC INPUT 500mA MAX CURRENT

SERVICE     BYPASS

NORMAL

see step 5 & DETAIL A

  OR                                OR                                     OR

5 min                           10 min                              20 min                             40 min

MAX BYPASS TIME SETTINGS

DOOR TAMPER SWITCH HAS A SERVICE BYPASS MODE. PULL

SWITCH OUT TO BYPASS DURING UNIT SERVICING & ADJUSTMENT

STATUS INDICATOR

DISABLE AUTO REARM

O

N

O

N

O

N

O

N

O

N

O

N

O

N

O

N

Fig. 3

+/ -

BATTERY

see step 5

CONTROL

BOARD

CABLE

POWER

12V AC

24V AC/DC

DISPLAY

BOARD

CABLE

see step 5

see Detail C

Tamper Switch

Battery

TAMPER

Magswitch

Surface (SK1) and Flush (FK1)

Closed Connection

Door Secure

Magnetic Switch

Flush Mount

MS2049S Option

connections

Magnetic switch

White

Red

(NOT Used)

Black

Magnetic Switch

Surface Mount

DISPLAY BOARD

POWER BOARD

2. MAGNETIC SWITCH INSTALLATION:

Install magnetic contact switch onto door using magnetic switch instructions. For wire requirements, see Manufacture's

Recommendation Chart. Route wires to Exit Alarm location.

Magnetic Contact Switch:

Within 6 feet: 2 conductor cable, 22AWG

20 feet or less: Twisted wire, 20AWG

50 feet or less: Twisted wire, 18AWG

3. TRANSFORMER INSTALLATION

:

Connect power wires to the two terminals on the 12VAC to 24VAC transformer. Route wires to Exit Alarm location per applicable

building code(s). 

DO NOT APPLY POWER AT THIS TIME.

Power Leads from Transformer to Exit Alarm:

20 feet or less: 20AWG

50 feet or less: 18AWG

(MAGNETIC SWITCH may be sold separately)

103140   Page 3

Содержание EAX-3500

Страница 1: ...ght bar meter illuminates gradually as more By Pass time is added NOTE If By Pass time expires while door is open alarm will sound TO SILENCE ALARM Close door insert and rotate key CCW TO ACTIVATE TIMED BY PASS 1 Rotate key counterclockwise CCW light bar meter flashes then release key 2 To add By Pass time press ACTIVATE TIMED BY PASS button Light bar illuminates gradually as more bypass time is a...

Страница 2: ... 10 x 1 10 x 1 PPH PPH Tools Required Pencil Metal Applications All other Applications Drill Bit Fastener Table Comments w Anchors EAX 3500 Installation and Usage Guide Display Board p n 103943 Cover Lock Key 102966 Bracket p n 103970 p n 100783 Cam Assembly p n 102680 p n 102627 15 2 pls Battery Strap p n 103963 Modular Cable p n 104017 5 12V Battery p n 103952 Power Supply Board p n 103941 Tampe...

Страница 3: ...nt MS2049S Option connections Magnetic switch White Red NOT Used Black Magnetic Switch Surface Mount DISPLAY BOARD POWER BOARD 2 MAGNETIC SWITCH INSTALLATION Install magnetic contact switch onto door using magnetic switch instructions For wire requirements see Manufacture s Recommendation Chart Route wires to Exit Alarm location Magnetic Contact Switch Within 6 feet 2 conductor cable 22AWG 20 feet...

Страница 4: ...onnect power wires to the two place terminal block located on lower left corner of power board Wires are not polarity sensitive Fig 3 By Pass time is factory set for 5 minutes See detail B above for additional By Pass time options To By Pass for service extend plunger on tamper switch See DETAIL C Insert access control key into mortise cylinder on front side of hinged panel Install battery supplie...

Страница 5: ... release Then press the Activate Timed By Pass button Make sure door is fully closed Make sure wiring to the magnetic switch is not damaged or cut Check AC power to the device and that building power is present at the outlet Make sure optional plug in transformer is plugged in and the holding screw installed Check for damaged wiring between the transformer and the EAX 3500 The battery should be re...

Отзывы: