-24-
www.detandt.com
High
pressure
protection
(HP Switch)
E1
☆☆☆☆☆
☆
●
(6 flashes 1
dark)
1) Too high air inlet
temp
2) Less water in the
tank
3) The electronic
expansion
valve
assembly blocked
4) Too much refrigerant
5)
The
switch
damaged
6) The uncompressed
gas is in refrigerant
system
7) PCB board failure
1) Check if the air inlet temp
is over the working limited
2) Check if the tank is full of
water. If not, charge water
3) Replace the electronic
expansion valve assembly
4)
Discharge
some
refrigerant
5) Replace a new switch
6) Discharge and then
recharge the refrigerant
7) change the PCB board
Low pressure
protection
(LP Switch)
E2
☆☆☆☆☆
☆☆
●
(7 flashes 1
dark)
1) Too low air inlet
temp
2) The electronic
expansion
valve
assembly blocked
3) Too less refrigerant
4)
The
switch
damaged
5) The fan assembly
can not work
6 )PCB board failure
1) Check if the air inlet temp
is over the working limited
2) Replace the electronic
expansion valve assembly
3) Charge some refrigerant
4) Replace a new switch
5) Check if the fan working
when
the
compressor
working. If not, some
problems with the fan
assembly
6) change the PCB board
Over
heat
protection
(HTP Switch)
E3
☆☆☆☆☆
☆☆☆
●
(8 flashes 1
dark)
1) Too high tank water
temp
2)
The
switch
damaged
3) PCB board failure
1) If the tank water temp is
over 85C, the switch will
open and the unit will stop for
protection. After the water
comes to normal temp,
2) Replace a new switch
3) Change the PCB board
Defrost
Defro
sting
indica
te
☆☆☆☆☆
☆☆☆
……(
all
long
flashes)
Communicati
on failure
E8
Bright
Содержание BATHERM A Series
Страница 30: ...29 www detandt com SCHEMA DE CABLAGE V rifier le sch ma de c blage sur la bo te lectrique...
Страница 61: ...28 www detandt com BEDRADINGSSCHEMA Controleer de bedradingschema op het elektriciteitskast...
Страница 71: ...7 www detandt com OVERVIEW OF THE UNIT Parts and descriptions...
Страница 91: ...27 www detandt com WIRING DIAGRAM Please refer to the wiring diagram on the electric box...