Det-Tronics U7652 Скачать руководство пользователя страница 6

greater the intensity emitted radiation.  The U7652
ignores steady state IR sources that do not flicker.
However, it should be noted that if these steady state
IR sources are hot enough to emit adequate amounts
of IR radiation in the response range of the detector
and if this radiation becomes interrupted from the
view of the detector in a pattern characteristic of a
flickering flame, the IR sensor can respond.  The clos-
er the IR source is to the detector, the greater the
potential for the IR sensor to respond.

AMBIENT RADIATION

The U7652 is designed to reduce false actuations,
however, combinations of ambient radiation that
could activate both the UV and IR sensor must be
avoided.  For example, if IR radiation with an intensity
that exceeds the fire threshold of the IR sensor should
reach the detector as a flickering signal (activating
the IR sensor), and if at the same time an electric arc
welding signal also reaches the detector (activating
the UV sensor), an alarm output will be generated.

NON-CARBON FIRES

The U7652 uses a single frequency IR sensing device
with detection limited to the hot CO

2

emission peak,

therefore, it should not be used to detect fires that do
not contain carbon, such as hydrogen, sulfur and
burning metals without thorough verification testing.
Exceptions to this are when the U7652C is used.  The
U7652C with auxiliary relay can be set to activate to
UV only radiation.  The U7652C with 4 to 20 ma out-
put has a discrete milliampere output for UV only,
allowing it to monitor for UV only radiation.

GASES, VAPORS, SMOKE AND OTHER OBSTRUC-
TIONS

Radiation must reach the detector in order for it to
respond.  Keep physical obstructions out of the line of
view of the detector.  UV or IR absorbing gases or
vapors must not be allowed to accumulate between
the detector and protected hazard (see Table 4 for a
list of these substances).  Do not mount the detector
close to the ceiling or in other areas where smoke can
accumulate.

EMI/RFI INTERFERENCE

The U7652 is resistant to interference by EMI and RFI.
It will not respond to a 5 watt walkie-talkie at a dis-
tance of greater than 1 foot.

VIEWING WINDOWS

Keep the detector viewing windows as free of con-
taminants  as possible in order to maintain maximum
sensitivity and assure proper operation of the flame
detection system (refer to the “Maintenance” section
for cleaning instructions).  Commonly encountered
attenuating substances  include, but are not limited
to, the following:

— silicones
— oils and greases
— ice buildup
— dust and dirt buildup
— paint overspray.

4

Table 4—UV Absorbing Gases and Vapors

The following 38 substances exhibit significant UV
absorption characteristics. These are also generally haz-
ardous vapors. While usually of little consequence in
small amounts, these gases can restrict UV detection if
they are in the atmosphere in heavy concentrations. It
should also be determined whether or not large amounts
of these gases may be released as a result of a fire-
causing occurrence.

Acetaldehyde

Methyl Methacrylate

Acetone

Alpha-Methylstyrene

Acrylonitrile

Naphthalene

Ethyl Acrylate

Nitroethane

Methyl Acrylate

Nitrobenzene

Ethanol

Nitromethane

Ammonia

1-Nitropropane

Aniline

2-Nitropropane

Benzene

2-Pentanone

1,3 Butadiene

Phenol

2—Butanone

Phenyl Clycide Ether

Butylamine

Pyridine

Chlorobenzene

Hydrogen Sulfide

1-Chloro-1-Nitropropane

Styrene

Chloroprene

Tetrachloroethylene

Cumene

Toluene

Cyclopentadiene

Trichloroethylene

O-Dichlorobenzene

Vinyl Toluene

P-Dichlorobenzene

Xylene

If UV-absorbing gases may be a factor in a given applica-
tion, precautionary measures should be taken. Detectors
can be placed closer to the potential hazard area, and/or
the sensitivity of the detection system can be increased.
Contact the factory for further details.

Substances such as methane, propane, butane, cam-
phor, hexane and octane are not UV absorbing.

Absorption of infrared radiation in the range of 4.2 to 4.7
microns is not a significant problem with most organic
vapors, with the exception of those compounds that have
triple bonds such as acetylene, nitriles, silane, or iso-
cyanates.  Carbon dioxide concentrations higher than
normally present in the atmosphere can also cause sub-
stantial loss of fire detection sensitivity.

Содержание U7652

Страница 1: ...tions 95 8385 06 Unitized UV IR Flame Detector U7652 Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750 3 01 95 8...

Страница 2: ...7 Figure 7 U7652B Wiring Terminal Configuration 7 Figure 8 Wiring Terminal Configuration for U7652C with Auxiliary Relay 7 Figure 9 Wiring Terminal Configuration for U7652C with 4 to 20 ma Output 8 F...

Страница 3: ...ouch the connector circuit board or electronic components 4 Alarm and extinguishing devices should be disconnected before performing the manual oi test DESCRIPTION The U7652 UV IR Flame Detector is an...

Страница 4: ...ormally de energized no fire Energizes upon detection of fire Field programmable for either latching or non latching operation Fault relay has SPST normally open contacts Normally energized no fault D...

Страница 5: ...is 10 degrees and were set for a 0 5 second time delay Response is dependent on the type of fuel the temperature of the fuel and the time required for the fire to build As with all fire tests results...

Страница 6: ...erence by EMI and RFI It will not respond to a 5 watt walkie talkie at a dis tance of greater than 1 foot VIEWING WINDOWS Keep the detector viewing windows as free of con taminants as possible in orde...

Страница 7: ...IREMENTS Use 16 to 22 gauge 1 5 to 0 5 mm2 cable A minimum input voltage of 18 vdc must be present at the detector Use cable that is suitable for the installation environ ment harsh environments requi...

Страница 8: ...SWIVEL CONDUIT SEAL A1478 Figure 3 Vertical Mounting B1437 TERMINAL BLOCK AUXILIARY RELAY OPERATION W4 LATCH NON LATCH W1 ALARM RESPONSE W3 oi TEST W2 CONNECTOR SCREWS 3 MOTHERBOARD ASSEMBLY Figure 4...

Страница 9: ...LT RELAY IS SHOWN DE ENERGIZED BUT IS NORMALLY ENERGIZED WITH POWER APPLIED AND NO FAULTS PRESENT 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 FIRE FAULT CON 1 CON 2 AUX AUX Figure 8 Wiring Terminal Configurat...

Страница 10: ...CON 1 CON 1 CON 2 CON 2 SPARE FAULT RELAY 0 47 F 400 VOLT CAPACITOR Figure 10 A Typical System Using U7652B Detectors FAULT RELAY IS SHOWN DE ENERGIZED BUT IS NORMALLY ENERGIZED WITH POWER APPLIED AND...

Страница 11: ...used pour the conduit seals and allow them to dry 7 Re install the junction box cover ensuring that the 9 pin D connectors are properly mated between the cover and the circuit board inside the enclo s...

Страница 12: ...e unit is programmed for non latch ing operation the Fire relay will become de ener gized and the LEDs will turn off when the UV IR source is removed If the unit is programmed for latching operation i...

Страница 13: ...und faults power supply transients and lightning strikes All Det Tronics systems are designed with extensive protec tion circuitry however damage can still occur The following field test procedure has...

Страница 14: ...background Background radiation as such does not cause a problem Radiation UV or IR radiation is indicated with the detector in most applications unless both UV and by steady illumination of the flick...

Страница 15: ...proper operation is observed If abnormal operation is evident start with the sensor exchange first then the detector cover assembly and finally the detector mother board assembly Always remove system...

Страница 16: ...e sensor housing Hand tighten the sensor housing into the base until the O ring is fully seated 8 Re install the cover locking device if used 9 Inspect the viewing windows and oi rings and clean if ne...

Страница 17: ...to the detector terminal blocks 8 Apply a small amount of lubricant to each of the six screws on the junction box cover Line up the D connector on the junction box cover with the connector on the mot...

Страница 18: ...sure that they are properly seated in the groove on the hous ing It is imperative that these O rings be properly installed and in good condition Failure to maintain these rings can allow water to ente...

Страница 19: ...cond ENCLOSURE MATERIAL Copper free aluminum red or 316 stainless steel with stainless steel mounting bracket TEMPERATURE RATING Operating 40 F to 167 F 40 C to 75 C Storage 40 F to 185 F 40 C to 85 C...

Страница 20: ...See Figures 5 and 6 MTBF 36 183 hours SHIPPING WEIGHT Approximate Pounds Kilograms Aluminum housing 6 0 2 7 Stainless steel housing 14 0 6 3 REPLACEMENT PARTS The electronic module is not designed to...

Страница 21: ...R Long Range Test Lamp RECOMMENDED SPARE PARTS oi ring for UV detector 1 per 10 units oi ring for IR detector 1 per 10 units O rings for UV and IR detectors 2 per 10 units UV module with LEDs 1 per 10...

Страница 22: ...ollowing performance criteria was verified by FMR using IR Module DE 5400 001 and UV Module DE1888 Response Characteristics Angle of View 45 to 45 off centerline in vertical and horizontal planes Fals...

Страница 23: ...Printed in USA Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750...

Отзывы: