Both sensors are equipped with the Optical Integrity
(

oi

) test feature to assure proper operation of the

detector by checking the cleanliness of the optical
surfaces, sensitivity of the sensors, and proper func-
tioning of the electronic circuitry.  No testing with an
external test lamp is required.  The detector automati-
cally performs the same test that a maintenance per-
son with a test lamp would perform — once every
minute, 60 times per hour.  A successful automatic 

oi

test 

does not 

produce an alarm condition.

The U7652 can be programmed (using a jumper
plug) for automatic and/or manually initiated 

oi

test-

ing.  Use of automatic 

oi

is highly recommended.

Automatic 

oi

With automatic 

oi

selected, the 

oi

test is automatical-

ly performed on each sensor once every minute.  If a
fault is detected, the normally energized Fault relay is
de-energized and the LEDs on the faulty sensor stop
blinking.  When automatic 

oi

is selected, the detector

can also be tested using the manual 

oi

test.

Manual 

oi

The detector also incorporates a manual 

oi

feature

that provides the same test as the automatic 

oi

, and

in addition actuates the Alarm relay to verify output
operation.  The manual 

oi

feature is available in all

models and can be performed at any time.  

This test

requires bypass of all extinguishing devices to
avoid release resulting from a successful test.

RELAYS AND OUTPUTS

All U7652 Models

All U7652 Models are furnished with two standard
output relays that are rated for 5 amperes (resistive)
at 30 vdc.

Fire relay has SPDT (normally open/normally closed)
contacts:

— Normally de-energized (no fire).
— Energizes upon detection of fire.
— Field programmable for either latching or non-

latching operation.

Fault relay has SPST (normally open) contacts:

— Normally energized (no fault).
— De-energizes when fault is detected.
— Non-latching operation (automatically resets when

fault is corrected).

U7652C Model

The U7652C is furnished with either an auxiliary relay
or a 4 to 20 ma output in addition to the standard out-
puts.  The U7652C with auxiliary relay requires the
presence of radiation at only one sensor for relay
actuation-rated for 1 ampere at 30 vdc.  (Not recom-
mended for uncontrolled locations.)

Auxiliary relay has SPST (normally open) contacts.  

— Field selectable for actuation when “UV radiation

only” or “any UV or IR radiation” is detected.
(Factory-shipped with the field selectable jumper
plug in the “UV only” position.)

— Normally de-energized (selected radiation not

detected).

— Energizes upon detection of selected radiation.

— Non-latching when responding to UV only or IR

only condition.

— Latches in response to UV and IR radiation at

background levels (fire threshold not exceeded).

Table 1—Detector Status Chart 

2

Status

UV LEDs

IR LEDs

Fire Relay

Fault Relay

Normal

Blinking

Blinking

De-energized

Energized

UV Fault

Off 

Blinking

De-energized

De-energized

IR Fault

Blinking

Off

De-energized

De-energized

General Fault

Off

Off

De-energized

De-energized

Background UV

On

Off*

De-energized

Energized

Background IR

Off*

On

De-energized

Energized

Fire

On

On

Energized

Energized

Manual 

oi

Test

On

On

Energized

Energized

During normal operation when automatic 

oi

is selected, LEDs blink once

every 5 seconds.  During normal operation when manual 

oi

is selected, UV

and IR sides blink alternately every 5 seconds.

*Some earlier models will blink under these conditions.

Содержание U7652

Страница 1: ...tions 95 8385 06 Unitized UV IR Flame Detector U7652 Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750 3 01 95 8...

Страница 2: ...7 Figure 7 U7652B Wiring Terminal Configuration 7 Figure 8 Wiring Terminal Configuration for U7652C with Auxiliary Relay 7 Figure 9 Wiring Terminal Configuration for U7652C with 4 to 20 ma Output 8 F...

Страница 3: ...ouch the connector circuit board or electronic components 4 Alarm and extinguishing devices should be disconnected before performing the manual oi test DESCRIPTION The U7652 UV IR Flame Detector is an...

Страница 4: ...ormally de energized no fire Energizes upon detection of fire Field programmable for either latching or non latching operation Fault relay has SPST normally open contacts Normally energized no fault D...

Страница 5: ...is 10 degrees and were set for a 0 5 second time delay Response is dependent on the type of fuel the temperature of the fuel and the time required for the fire to build As with all fire tests results...

Страница 6: ...erence by EMI and RFI It will not respond to a 5 watt walkie talkie at a dis tance of greater than 1 foot VIEWING WINDOWS Keep the detector viewing windows as free of con taminants as possible in orde...

Страница 7: ...IREMENTS Use 16 to 22 gauge 1 5 to 0 5 mm2 cable A minimum input voltage of 18 vdc must be present at the detector Use cable that is suitable for the installation environ ment harsh environments requi...

Страница 8: ...SWIVEL CONDUIT SEAL A1478 Figure 3 Vertical Mounting B1437 TERMINAL BLOCK AUXILIARY RELAY OPERATION W4 LATCH NON LATCH W1 ALARM RESPONSE W3 oi TEST W2 CONNECTOR SCREWS 3 MOTHERBOARD ASSEMBLY Figure 4...

Страница 9: ...LT RELAY IS SHOWN DE ENERGIZED BUT IS NORMALLY ENERGIZED WITH POWER APPLIED AND NO FAULTS PRESENT 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 FIRE FAULT CON 1 CON 2 AUX AUX Figure 8 Wiring Terminal Configurat...

Страница 10: ...CON 1 CON 1 CON 2 CON 2 SPARE FAULT RELAY 0 47 F 400 VOLT CAPACITOR Figure 10 A Typical System Using U7652B Detectors FAULT RELAY IS SHOWN DE ENERGIZED BUT IS NORMALLY ENERGIZED WITH POWER APPLIED AND...

Страница 11: ...used pour the conduit seals and allow them to dry 7 Re install the junction box cover ensuring that the 9 pin D connectors are properly mated between the cover and the circuit board inside the enclo s...

Страница 12: ...e unit is programmed for non latch ing operation the Fire relay will become de ener gized and the LEDs will turn off when the UV IR source is removed If the unit is programmed for latching operation i...

Страница 13: ...und faults power supply transients and lightning strikes All Det Tronics systems are designed with extensive protec tion circuitry however damage can still occur The following field test procedure has...

Страница 14: ...background Background radiation as such does not cause a problem Radiation UV or IR radiation is indicated with the detector in most applications unless both UV and by steady illumination of the flick...

Страница 15: ...proper operation is observed If abnormal operation is evident start with the sensor exchange first then the detector cover assembly and finally the detector mother board assembly Always remove system...

Страница 16: ...e sensor housing Hand tighten the sensor housing into the base until the O ring is fully seated 8 Re install the cover locking device if used 9 Inspect the viewing windows and oi rings and clean if ne...

Страница 17: ...to the detector terminal blocks 8 Apply a small amount of lubricant to each of the six screws on the junction box cover Line up the D connector on the junction box cover with the connector on the mot...

Страница 18: ...sure that they are properly seated in the groove on the hous ing It is imperative that these O rings be properly installed and in good condition Failure to maintain these rings can allow water to ente...

Страница 19: ...cond ENCLOSURE MATERIAL Copper free aluminum red or 316 stainless steel with stainless steel mounting bracket TEMPERATURE RATING Operating 40 F to 167 F 40 C to 75 C Storage 40 F to 185 F 40 C to 85 C...

Страница 20: ...See Figures 5 and 6 MTBF 36 183 hours SHIPPING WEIGHT Approximate Pounds Kilograms Aluminum housing 6 0 2 7 Stainless steel housing 14 0 6 3 REPLACEMENT PARTS The electronic module is not designed to...

Страница 21: ...R Long Range Test Lamp RECOMMENDED SPARE PARTS oi ring for UV detector 1 per 10 units oi ring for IR detector 1 per 10 units O rings for UV and IR detectors 2 per 10 units UV module with LEDs 1 per 10...

Страница 22: ...ollowing performance criteria was verified by FMR using IR Module DE 5400 001 and UV Module DE1888 Response Characteristics Angle of View 45 to 45 off centerline in vertical and horizontal planes Fals...

Страница 23: ...Printed in USA Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750...