Table 5. Hi-Limit instrument Setup Parameters.
Code
Name
Description
Settings
inPt
Input type
Select thermocouple type. LBB Series Ovens use type
J thermocouples
J_tC
unit
Process unit.
Select between °C and °F for reading process
temperature
C (or F)
rESo
Display
resolution.
Select location of decimal point on process-related
parameters
No.dP
SHif
PV shift value
(offset).
Moves the display temperature to the oven
temperature
0
Filt
PV filter.
If the process value is unstable to read, increasing this
value steadies the input signal.
0
out1
Output 1
function.
Function of the output. Must be set to Hi. for Hi-Limit
control.
Hi.
o1.Hy
Output 1
hysteresis
value.
Amount of degrees the temperature must be below
the setpoint temperature before the Hi-Limit can be
reset
2.0
HSP.L
Lower limit of
HSP1.
Minimum temperature setting for the Hi-Limit
0 (32 if
F)
HSP.H
Upper limit of
HSP1.
Maximum temperature setting for the Hi-Limit
204 (400
if F)
out2
Second output
Despatch does not use this function
None
diSP
Normal display
format.
Used to select the display in normal condition:
PV = Process Value
SP! = Hi-Limit Setpoint
SAFE = The word “safe” in normal condition
PV
PuHi
Process value
high
Read-Only Data: Maximum process value since last
UNLOCK operation.
None
PuLo
Process value
low
Read-Only Data: Minimum process value since last
UNLOCK operation.
None
t.Abn
Abnormal time
Total accumulated minutes of abnormal conditions
since last UNLOCK operation.
None
5.4.8.
Change Hi-Limit instrument Display from Centigrade to
Fahrenheit
Warning!
Changing program parameters alters the function of the Control.
Proceed carefully and fully understand each parameter before
changing that parameter.