Page | 4 

 

  

RLC IOM Aug 31 17  

 

 

 

Negative-Pressure Application 

 

When operating with a negative pressure plenum, 

install the RLC 

Air-Trap 

in a horizontal orientation with 

the arrowhead       pointing in the direction of water flow

 

and the clean out plug facing upward as shown in Fig. 

6.  Condensate enters the end of the trap with the 

centered connection and leaves the trap that has the 

off center connection.   

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 6:  Installation of the RLC for negative pressure 

showing arrowhead pointing in direction of water flow. 

RLC traps tested at 1.6 GPM of condensate flow. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 7:  Orientation for negative pressure after 

installation of RLC

 Air-Trap,

 showing cleanout port on 

top, condensate entering at left end center, and exiting 

at lowest point of trap on the right side.  No water 

remains in trap shortly after condensation ceases. 

 

 

The benefits and maintenance of the RLC 

Air-Trap

 

when used in the negative pressure mode are the 

same as for the positive mode with the added benefit 

that it eliminates the geyser effect that is caused when 

the standard P-Trap dries out and condensate begins 

to form.  The geyser effect is when air rushes into the 

HVAC unit and does not allow the condensate to drain, 

causing water to blow throughout the plenum 

compartment.  In addition, the RLC negative 

Air-Trap

 

requires less than half the height of a P-Trap.  

Dimension Y in Fig. 6 illustrates that the total height of 

the 

Air-Trap

 is only the height of the negative pressure 

plus one inch and not 2 times negative pressure plus 

two inches.  Dimension Y in inches is = negative 

pressure in inches of water column. 

 

  

 

 

 

 

 

.  

 

 

 

Caution, do not puncture the Float Valve.   

  

 

Limited Warranty 

Des Champs Technologies warrants to the original consumer purchaser 

(“Purchaser”) of its product, RLC SERIES 

Air-Trap

, that it is free from 

defects in material or workmanship.  If within the 12-month period from 

the date of the original consumer purchase this product shall prove to be 

defective, it shall be repaired or replaced at Des Champs Technologies 

option.  Your original receipt of purchase is required to determine 

warranty eligibility.  The warranty does not cover damage due to misuse, 

misapplication, lack of maintenance, or failure to comply with the 

manufacturer’s installation instructions or recommendations or any other 

loss or damage exceeding the purchase price of the equipment purchased 

from Des Champs Technologies or its appointed distributors.  Des 

Champs Technologies assumes no responsibility for damage or injury 

resulting from chemical incompatibility between its products and the 

process fluids to which they are subjected.  This warranty is limited to 

repair or replacement of the 

Air-Trap

 only and is the only warranty issued 

by Des Champs Technologies on its trap products. 

 

 

This product design is Patent Pending by Des Champs 

Technologies LLC, Natural Bridge Station, Virginia 

24579.   

 

Des Champs Technologies has other standard models 

of traps as well as engineered traps for high 

temperature, high pressure, and very high water flows.  

Call or go to the Website below for more information.

 

 

  

 

Negative 

 

Figure 8:  The standard 

connection is ¾” slip.  The 

O.D. of the connection 

accommodates a 1-inch 

bushing.  Therefore, any 

size PVC SCH 40 pipe from 

½

 to 2 inches connects 

with the aid of a bushing. 

Содержание HVAC Air-Trap RLC Series

Страница 1: ... RLC SERIES Air Trap in a vertical position for positive pressure and in a horizontal position for negative pressure Delivery Check Upon receipt of an Air Trap s inspect for damage that may have occurred during shipment and check to insure delivered items match purchased items Resolving Shipping Damage If damage or items are missing 1 Report all claims of shipping damage to the delivering carrier ...

Страница 2: ...t is required When dry essentially no air exits the HVAC unit When removing water the water exits the unit but essentially no air exits the unit through the drain connection Install the Air Trap in a vertical orientation With no production of condensate within the AHU the positive pressure that exists within the unit plenum that contains the drain line forces the ball valve downward onto the valve...

Страница 3: ...ocks screws and nuts from ever getting into the trap The Union Strainer is also a convenient way to prevent unwanted creatures and objects from entering at the terminus of the drain line like snakes rats lizards insects and plant growth The water flow is in direction of arrow shown in Fig 5 with the strainer cup oriented to capture debris within the cup There are several options for cleaning Optio...

Страница 4: ...lus one inch and not 2 times negative pressure plus two inches Dimension Y in inches is negative pressure in inches of water column Caution do not puncture the Float Valve Limited Warranty Des Champs Technologies warrants to the original consumer purchaser Purchaser of its product RLC SERIES Air Trap that it is free from defects in material or workmanship If within the 12 month period from the dat...

Отзывы: