background image

www.desatech.com

124452-01A

7

 

Example:

 

 

Gas water heater 

   _________ Btu/Hr

 

Vent-free fireplace 

+  _________ Btu/Hr

 

Total 

=  _________ Btu/Hr

4.  Compare  the  maximum  Btu/Hr  the  space 

can support with the actual amount of Btu/Hr 
used.

 

  _______ Btu/Hr (maximum the space can 
support) 

 

  _______ Btu/Hr (actual amount of Btu/Hr 
used)

 

Example:

  51,200  Btu/Hr  (maximum  the 

space can support) 

 

 

71,500 Btu/Hr (actual amount of 
Btu/Hr used)

The space in the example is a confined space 
because the actual Btu/Hr used is more than the 
maximum  Btu/Hr  the  space  can  support.  You 
must  provide  additional  fresh  air. Your  options 
are as follows:
A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides an 
unconfined space, remove door to adjoining 
room or add ventilation grills between rooms. 
See 

Ventilation  Air  From  Inside  Building

page 7.

B.  Vent  room  directly  to  the  outdoors.  See 

Ventilation Air From Outdoors

, page 7.

C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr 

size makes room unconfined. 

If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support,

 

the space is 

an unconfined space. You will need no additional 
fresh air ventilation.

 WARNING: If the area in which 

the heater may be operated does 

not meet the required volume for 

indoor combustion air, combus

-

tion and ventilation air shall be 

provided by one of the methods 

described  in  the 

National  Fuel 

Gas Code, ANSI Z223.1/NFPA 54, 

the

 International Fuel Gas Code,

 

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining 
unconfined  space.  When  ventilating  to  an 
adjoining unconfined space, you must provide 
two permanent openings: one within 12" of the 

40,000
31,500
71,500

AIR FOR COMbUSTION AND VENTILATION

Continued

Figure 2 - Ventilation Air from Inside 

Building

Or 

Remove 

Door into 
Adjoining 

Room, 
Option 

Ventilation Grills  

Into Adjoining Room, 

Option 2 

Ventilation

Grills Into

Adjoining 

Room,

Option 1

12" 

12" 

Figure 3 - Ventilation Air from Outdoors

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

ceiling and one within 12" of the floor on the 
wall connecting the two spaces (see options 
1 and 2, Figure 2). You can also remove door 
into adjoining room (see option 3, Figure 2). 
Follow  the 

National  Fuel  Gas  Code  ANSI 

Z223.1/NFPA  54,  Air  for  Combustion  and 
Ventilation

  for  required  size  of  ventilation 

grills or ducts.

Ventilation Air From Outdoors

Provide  extra  fresh  air  by  using  ventilation 
grills or ducts. You must provide two perma-
nent openings: one within 12" of the ceiling 
and one within 12" of the floor. Connect these 
items directly to the outdoors or spaces open 
to the outdoors. These spaces include attics 
and crawl spaces. Follow the 

National Fuel 

Gas  Code  ANSI  Z223.1/NFPA  54,  Air  for 
Combustion and Ventilation

 for required size 

of ventilation grills or ducts.

IMPORTANT:

  Do  not  provide  openings  for 

inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering 
the attic will activate the power vent.

Содержание VyS18NC

Страница 1: ...o not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installat...

Страница 2: ...vented gas fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven tilation...

Страница 3: ...warnings Keep this manual for reference It is your guide to safe and proper operation of this fireplace WARNING Any change to this heater or its controls can be dangerous WARNING Do not use a blower i...

Страница 4: ...less than 100 lbs capacity is not recommended propane LP units only 4 If you smell gas shut off gas supply do not try to light any appliance do not touch any electrical switch do not use any phone in...

Страница 5: ...heaters Non thermostat models may also be operated as a vented decorative ANSI Z21 60 product by opening flue damper Safety Pilot This heater has a pilot with an Oxygen Deple tion Sensing ODS safety s...

Страница 6: ...whose volume is less than 50 cubic feet per AIR FOR COMBUSTION AND VENTILATION Continued 1 000 Btu per hour 4 8 m3 per kw of the ag gregate input rating of all appliances installed in that space and a...

Страница 7: ...asCode or applicable local codes VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating to an adjoining unconfined space you...

Страница 8: ...at resistant sealant Do not seal chimney flue damper Installation WARNING Never install the heater in a bedroom or bathroom un less installed as a vented appli ance see page 11 in a recreational vehic...

Страница 9: ...he ceiling should not be less than 42 Figure 4 Minimum Clearance for Combustible to Wall Minimum 16 from Side Wall Example INSTALLATION Continued NOTICE Manual control heaters may be used as a vented...

Страница 10: ...nces you must operate heater with chimney flue damper open Go to Install ing Damper Clamp Accessory for Vented Operation page 11 INSTALLATION Continued Mantel Clearances In addition to meeting noncomb...

Страница 11: ...ented heater ap pliance must be installed only in a solid fuel burning fireplace with a working flue and constructed of noncombustible material You may use this heater as a vented product There are th...

Страница 12: ...ealant resistant to propane LP gas not provided electric drill with 3 16 drill bit flathead screwdriver 1 Apply pipe joint sealant lightly to male threads of the fitting to be threaded into gas regula...

Страница 13: ...regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 14 of water If you do not reduce incoming gas pressure heater regulator damage could occur Install...

Страница 14: ...regulator 2 Cap off open end of gas pipe where equip ment shutoff valve was connected 3 Pressurize supply piping system by either opening propane LP supply tank valve for propane LP gas or opening mai...

Страница 15: ...ingto the log installation instructions in this manual Flames contact ing log will create soot It is very important to install these logs exactly as instructed Do not modify logs Only use logs supplie...

Страница 16: ...in Figure 19 The bottom of the log is marked with a C for center Match square peg on center of rear log with square hole in bottom of center crossover Match round peg on center of front log with round...

Страница 17: ...R SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these instructions exactly a fire or explosion may result causing property damage per sonal injury or loss of life A This appliance has a pi...

Страница 18: ...30 sec onds after lighting pilot After 30 seconds release control knob Note If pilot goes out repeat steps 3 through 7 If control knob does not pop out when released contact a qualified service perso...

Страница 19: ...own If pilot flame pattern is incorrect as shown in Figure 24 turn heater off see To Turn Off Gas to Ap pliance page 18 see Troubleshooting page 21 Note The pilot flame on natural gas units will have...

Страница 20: ...older located at the end of the burner tube again Remove any large particles of dust dirt lint or pet hair with a soft cloth or vacuum cleaner nozzle Figure 25 Injector Holder On Outlet Burner Tube Bu...

Страница 21: ...in gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When control knob is pressed in and turned to pilot...

Страница 22: ...or propane LP gas company 1 Contact local natural or propane LP gas company 2 Clean burner see Cleaning and Maintenance page 19 or replace burner orifice 1 Clean burner see Cleaning and Maintenance pa...

Страница 23: ...burner until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum instal lation clearances see page 8 4 Clean burner see Cleaning and Maintenance...

Страница 24: ...see Checking Gas Con nections page 14 1 Open window and or door for ventilation 2 Contact local natural or propane LP gas company 3 Clean ODS pilot see Cleaning and Maintenance page 19 1 Locate and co...

Страница 25: ...Maximum 10 5 W C Minimum 5 W C Shipping Weight 27 lbs For the purpose of input adjustment Service Hints When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition heater...

Страница 26: ...www desatech com 124452 01A 26 Parts Variable Manually Controlled VYS18NC VYS18PC VYS24NC AND VYS24PC 15 17 3 17 4 18 Models 17 4 24 Models 3 14 16 11 10 4 2 12 8 5 14 13 7 9 1 15 15 17 5 17 2 17 1...

Страница 27: ...1 107186 06 Injector 1 107186 07 Injector 1 107186 08 Injector 1 12 098354 01 Control Knob 1 13 099387 08 Pilot Tube 1 14 M11084 38 HWH AB 8 18 x 0 38 Screw 1 15 M11084 26 HWH AB 10 16 x 0 38 Screw 8...

Страница 28: ...446 1446 Fax 616 791 8270 www nbmc com Washer Equipment Co 1715 Main Street Kansas City MO 64108 2195 KS MO AR 816 842 3911 www washerparts com East Coast Energy Products 10 East Route 36 W Long Bran...

Страница 29: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Страница 30: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Страница 31: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Страница 32: ...proved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use origin...

Отзывы: