www.desatech.com
124452-01A
11
INSTALLATION
Continued
14"
Min.
Combustible
Material
Noncombustible Material
Hearth
5"
Min.
Combustible
Material
Figure 8 - Minimum Fireplace Clearances
Above Combustible Flooring
Figure 7 - Minimum Fireplace Clearances
If Installed at Floor Level
FLOOR CLEARANCES
A. If installing appliance on floor level, you
must maintain the minimum distance of
14" to combustibles (see Figure 7).
B. If combustible materials are less than 14"
to fireplace, you must install appliance at
least 5" above combustible flooring (see
Figure 8).
Area of Various Standard Round Flues
Diameter
Area
5"
20 sq. inches
6"
29 sq. inches
7"
39 sq. inches
8"
51 sq. inches
Chimney
Height
Minimum Permanent
Flue Opening
6' to 15'
39 sq. inches
15' to 30'
29 sq. inches
INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION
Note: When used as a vented heater, ap-
pliance must be installed only in a solid-fuel
burning fireplace with a working flue and
constructed of noncombustible material.
You may use this heater as a vented product.
There are three reasons for operating your
heater in the vented mode.
1. The fireplace does not meet the clear-
ance to combustibles requirements for
vent-free operation.
2. State or local codes do not permit vent-
free operation.
3. You prefer vented operation.
If reasons number 1 or 2 apply to you, you
must permanently open chimney flue damper.
You must install the damper clamp accessory
(to order, see
Accessories
, page 28). This
will insure vented operation (see Figure 9).
The damper clamp will keep damper open.
Installation instructions are included with
clamp accessory.
See chart below for minimum permanent flue
opening you must provide. Attach damper
clamp so the minimum permanent flue open-
ing will be maintained at all times.
Figure 9 - Attaching Damper Clamp
Manufactured
Fireplace
Masonry Fireplace
Damper
Damper
Clamp
Damper
Damper