background image

18

104637

UNVENTED PROPANE/LP GAS FIREPLACE

®

OBSERVED PROBLEM

Burner does not light after ODS/pilot is lit

Delayed ignition burner

Burner backfiring during combustion

Slight smoke or odor during initial operation

Moisture/condensation noticed on windows

Heater produces a whistling noise when
burner is lit

White powder residue forming within burner
box or on adjacent walls or furniture

Remote does not function

REMEDY

1. Clean burner (see Cleaning and Mainte-

nance, page 21) or replace burner orifice

2. Contact local propane/LP gas company
3. Replace burner orifice
4. Reconnect leads (see Wiring Diagram,

page 20)

5. Replace battery in transmitter and re-

ceiver

1. Contact local propane/LP gas company
2. Clean burner (see Cleaning and Mainte-

nance, page 21) or replace burner orifice

1. Clean burner (see Cleaning and Mainte-

nance, page 21) or replace burner orifice

2. Replace damaged burner
3. Replace gas control

1. Check burner for dirt and debris. If

found, clean burner (see Cleaning and
Maintenance
, page 21)

2. Replace gas control
3. Problem will stop after a few hours of

operation

1. Refer to Air for Combustion and Venti-

lation requirements (page 4)

1. Turn control knob to LO position and

let warm up for a minute

2. Operate burner until air is removed

from line. Have gas line checked by
local propane/LP gas company

3. Observe minimum installation clear-

ances (see pages 8 through 10)

4. Clean burner (see Cleaning and Mainte-

nance, page 21) or replace burner orifice

1. Turn heater off when using furniture

polish, wax, carpet cleaners, or similar
products

1. Replace 9-volt batteries in receiver and

remote control

TROUBLESHOOTING

Continued

POSSIBLE CAUSE

1. Burner orifice clogged

2. Inlet gas pressure is too low
3. Burner orifice diameter is too small
4. Thermopile leads disconnected or im-

properly connected

5. Burners will not come on in remote

position

1. Manifold pressure is too low
2. Burner orifice clogged

1. Burner orifice is clogged or damaged

2. Damaged burner
3. Gas regulator defective

1. Not enough air

2. Gas regulator defective
3. Residues from manufacturing processes

and logs curing

1. Not enough combustion/ventilation air

1. Turning control knob to HI position

when burner is cold

2. Air in gas line

3. Air passageways on heater blocked

4. Dirty or partially clogged burner orifice

1. When heated, vapors from furniture pol-

ish, wax, carpet cleaners, etc. turn into
white powder residue

1. Battery is not installed. Battery power

is low

www.desatech.com

Содержание Vanguard VCGF30PR

Страница 1: ...n and operational pro cedures For assistance or addi tional information consult a qualified installer service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxy ge...

Страница 2: ...structions in Cleaning and Main tenance page 21 9 Before using furniture polish wax car pet cleaner or similar products turn heater off If heated the vapors from these products may create a white pow...

Страница 3: ...e 4 Remove fireplace hood from carton insert 5 Check all items for any shipping dam age If damaged promptly inform dealer where you bought fireplace Figure 1 Log Base Assembly Figure 2 Fireplace REMOT...

Страница 4: ...his vent free fireplace is clean burning It requiresnooutsideventing Thereisnoheat loss out a vent or up a chimney Heat is generatedbybothrealisticflamesandglow ing embers When used without the blower...

Страница 5: ...____ Btu Hr Do not include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual am...

Страница 6: ...the ceiling and one within 12 of the floor Connecttheseitemsdirectlytotheoutdoors orspacesopentotheoutdoors Thesespaces include attics and crawl spaces Follow the National Fuel Gas Code NFPA 54 ANS Z2...

Страница 7: ...otted screwdriver NOTICE This heater is intended foruseassupplementalheat Use this heater along with your pri mary heating system Do not in stall this heater as your primary heat source If you have a...

Страница 8: ...STALLATION Continued 4 Place hearth base accessory against wall at installation location Cut an ac cess hole in hearth top to run gas line to fireplace see Figure 9 Make sure to locate access hole so...

Страница 9: ...16 17 3 4 1 Frame in rough opening Use dimen sions shown in Figure 13 for the rough opening If installing in a corner use dimen sions shown in Figure 14 for the rough opening The height is 33 which i...

Страница 10: ...IREPLACE LOCATION Installation Items Needed Before installing fireplace make sure you have the items listed below external regulator supplied by installer piping check local codes sealant resistant to...

Страница 11: ...replace see Figure 21 5 Check all gas connections for leaks See Checking Gas Connections page 12 6 Replace log base assembly back into fireplace Feed flexible gas line into fire place base area while...

Страница 12: ...essure Testing Gas Supply Piping System Test Pressures In Excess Of 1 2 PSIG 3 5 kPa 1 Disconnect appliance with its appliance main gas valve control valve and equipment shutoff valve from gas sup ply...

Страница 13: ...is seated into U shaped cutout in cen ter of chassis see Figure 24 IMPORTANT Make sure log does not cover any burner ports 2 Install front window assembly to front of fireplace by slipping bottom wind...

Страница 14: ...area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electr...

Страница 15: ...he burner may light if hand held remote ON button was on when selector switch was last turned off You can now turn the burner on and off with the hand held remote control unit IMPORTANT Do not leave t...

Страница 16: ...ote control unit must be near the heater Do not keep the hand held remote control unit too close to the heater The thermostat on the hand held remote control unit will heat up too quickly and turn the...

Страница 17: ...Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set Nut is located behind base panel 4 Re...

Страница 18: ...irements page 4 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local propane LP gas company 3 Observe minimum...

Страница 19: ...ilate room Stop using odor causing products while fire place is running 2 Locate and correct all leaks see Check ing Gas Connections page 12 1 Open window and or door for ventilation 2 Contact local p...

Страница 20: ...ational have ready your name and address model and serial numbers of your heater how heater was malfunctioning type of gas used propane LP or natural gas purchase date Usually we will ask you to retur...

Страница 21: ...talyst Use a brush with soft bristles a vacuum with a brush attach ment orcompressedairtoremoveloosedirt debris and dust After cleaning install the catalytic filter back to the unit CLEANING BURNER IN...

Страница 22: ...finished GM102W Series Off White Paint Shown with optional base and laminate hearth and mantel trim accessories Dimensions WxHxD 56 3 4 x 48 x 20 3 4 HARDWOOD HEARTH BASE G3000F Series Walnut Finished...

Страница 23: ...chair RECEIVER AND HAND HELD REMOTE CONTROL KIT GHRC SERIES Allowsthegaslogheatertobeturnedonand off by using a hand held remote control WALL MOUNT THERMOSTAT SWITCH GWMT1 Not Shown The desired comfo...

Страница 24: ...UNVENTED PROPANE LP GAS FIREPLACE ILLUSTRATED PARTS BREAKDOWN REMOTE READY CATALYTIC MODEL VCGF30PR 17 4 O F F P I L O T O N H I L O 8 12 26 7 6 4 3 2 1 5 9 14 13 25 15 16 21 11 10 19 19 20 19 23 24 2...

Страница 25: ...8265 02 Elbow Male 1 15 103782 01 Valve Bracket 1 16 103781 02 Gas Control Valve 1 17 098271 03 Ignitor Cable 1 18 102445 01 Piezo Ignitor 1 19 098304 01 Screw 15 20 099998 01 Switch 1 21 104241 01 Re...

Страница 26: ...26 104637 UNVENTED PROPANE LP GAS FIREPLACE ILLUSTRATED PARTS BREAKDOWN FIREPLACE VCGF30PR 4 26 24 25 24 11 14 8 14 3 14 2 22 21 23 23 10 17 13 5 16 15 18 9 1 27 19 6 7 28 5 5 20 12...

Страница 27: ...PPH 10 24 x 50 2 10 104717 01 Firebox Top Assembly 1 11 101346 01CK Outer Base 1 12 104638 01 Firebox Wrapper 1 13 101514 01CK Cover 1 14 M11084 26 Hex Screw 10 45 15 104242 01CK Bottom Louvered Door...

Страница 28: ...to repairing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER E...

Отзывы: