Desa K42EN Series Скачать руководство пользователя страница 13

111922-01C

For more information, visit www.desatech.com

For more information, visit www.desatech.com

13

13

INSTALLATION FOR VERTICAL TERMINATION

Note:

 Vertical restrictor must be installed in all vertical installations.

1.

Determine the route your vertical venting will take. If ceiling
joists, roof rafters, or other framing will obstruct the venting
system, consider an offset (see Figure 19) to avoid cutting load
bearing members. 

Note:

 Pay special attention to these instal-

lation instructions for required clearances (air space) to com-
bustibles when passing through ceilings, walls, roofs, enclo-
sures, attic rafters, etc. Do not pack air spaces with insulation.
Also note maximum vertical rise of the venting system and
any maximum horizontal offset limitations.

2.

Set the fireplace in desired location. Drop a plumb line down
from the ceiling to the position of the fireplace exit flue. Mark
the center point where the vent will penetrate the ceiling. Drill
a small locating hole at this point.
Drop a plumb line from the inside of the roof to the locating
hole in the ceiling. Mark the center point where the vent will
penetrate the roof. Drill a small locating hole at this point.

VENTING INSTALLATION
INSTRUCTIONS

Continued

Flat Ceiling Installation

1.

Cut a 10 

3

/

4

" square hole in the ceiling using the locating hole as

a center point. The opening should be framed to 10 

3

/

4

"x10 

3

/

4

"

(273 mm x 273 mm) inside dimensions, as shown in Figure 9
on page 8 using framing lumber the same size as the ceiling
joists. If the area above the ceiling is an insulated ceiling or a
room, nail firestop from the top side. This prevents loose insula-
tion from falling into the required clearance space. Otherwise,
install firestop below the framed hole. The firestop should be
installed with no less than three nails per side (see Figure 20).

Figure 19 - Offset with Wall Strap and 45° Elbows

Figure 20 - Installing Firestop

If area above is not a room, install
firestop below framed hole.

If area above is a room, install
firestop above framed hole.

2.

Assemble the desired lengths of pipe and elbows necessary to
reach from the fireplace flue up through the firestop.  Be sure
all pipe and elbow connections are fully twist-locked (see Fig-
ure 8, page 8).

3.

Cut a hole in the roof using the locating hole as a center point.
(Cover any exposed open vent pipes before cutting hole in roof.)
The 10 

3

/

4

"x10 

3

/

4

" hole must be measured on the horizontal;

actual length may be larger depending on the pitch of the roof.
There must be a 1" clearance from the vent pipe to combustible
materials. Frame the opening as shown in Figure 9, page 8.

4.

Connect a section of pipe and extend up through the hole.

Note:

 If an offset is needed to avoid obstructions, you must

support the vent pipe every 3 feet. Use wall straps for this
purpose (see Figure 19). Whenever possible, use 45° elbows
instead of 90° elbows. The 45° elbow offers less restriction to
the flow of the flue gases and intake air.

5.

Place the flashing over the pipe section(s) extending through
the roof. Secure the base of the flashing to the roof and fram-
ing with roofing nails. Be sure roofing material overlaps the
top edge of the flashing as shown in Figure 19. There must be
a 1" clearance from the vent pipe to combustible materials.

6.

Continue to add pipe sections until the height of the vent cap
meets the minimum building code requirements described in
Figure 7 on page 6. 

Note: 

You must increase vent height for

steep roof pitches. Nearby trees, adjoining rooflines, steep
pitched roofs, and other similar factors may cause poor draft
or down-drafting in high winds. Increasing the vent height may
solve this problem.

7.

Twist-lock the vent cap onto the last section of vent pipe.

Note:

 If the vent pipe passes through any occupied areas above the

first floor, including storage spaces and closets, you must enclose
pipe. You may frame and sheetrock the enclosure with standard
construction material. Make sure and meet the minimum allowable
clearances to combustibles. Do not fill any of the required air spaces
with insulation.

VENTING INSTALLATION INSTRUCTIONS

Installation for Vertical Termination

45° Elbow

Wall Strap

Roof Flashing

Ceiling Firestop

Содержание K42EN Series

Страница 1: ...n service or maintenance can cause injury orpropertydamage Refertothis manual for correct installation and operational procedures For assistance or additional infor mation consult a qualified in stall...

Страница 2: ...liance is not convertible for use with other gases unless a certified kit is used 2 For propane LP fireplace do not place propane LP supply tank s inside any structure Locate propane LP supply tank s...

Страница 3: ...This appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the Ca nadian Electrical C...

Страница 4: ...he location of your fireplace follow these rules Do not connect this fireplace venting to a chimney flue serving a separate solid fuel burning fireplace or appliance Due to high temperatures do not lo...

Страница 5: ...s tible mantels may discolor PRE INSTALLATION PREPARATION Continued NOTICE This fireplace is intended for use as supple mental heat Use this fireplace along with your pri mary heating system Do not in...

Страница 6: ...nlet 72 inches 182 9cm minimum L clearance above paved side walk or a paved driveway located on public property 84 inches 213 3cm minimum M clearance under veranda porch deck 12 inches 30 5cm minimum...

Страница 7: ...ng ceilings or attic spaces Install horizontal venting with a 1 4 rise for every 12 of run toward the termination VENTING INSTALLATION INSTRUCTIONS NOTICE Read these instructions completely be fore at...

Страница 8: ...ctions together and twist one section clockwise approximately one quarter turn until the sections are fully locked see Figure 8 Note Horizontal runs of vent must be supported every three feet Use wall...

Страница 9: ...sition the standoff cap assembly in the center of the 10 3 4 square hole and attach to exterior wall with wood screws provided see Figure 11 The siding standoff must sit flush against the exterior fas...

Страница 10: ...igure includes a chart with critical minimum and maximum dimensions which MUST be met IMPORTANT Rememberthatahorizontalrunofventingmust have a 1 4 rise for every 12 of run toward the termination Figur...

Страница 11: ...throughwall over 12 horizontal pipe Basement installation where one foot clearance from ground to termination is possible SNORKEL TERMINATION INSTALLATION Recommended Applications Installations requir...

Страница 12: ...max 12 max 7 min 6 max 18 max 8 min 8 max 20 max 20 max 8 max 20 max 45 Elbow Figure 18 Horizontal Termination Configuration for Venting Using Two 90 Elbows with Termination at 90 with Fireplace Figu...

Страница 13: ...oom install firestop above framed hole 2 Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop Be sure all pipe and elbow connections are f...

Страница 14: ...wo90 Elbows Vertical Round High Wind Termination Shown VENTING INSTALLATION INSTRUCTIONS Installation for Vertical Termination Cont Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5...

Страница 15: ...Wall Pipe Galvanized PA58 712 Adjustable7 12 SectionDoubleWallPipe Galvanized FPA58 6 6 DuraventCollartoFMIPipeAdaptor 6 Collar Pipe Section DPA58 6 6 FMICollartoPipeDuraventAdaptor 6 Collar Pipe Sec...

Страница 16: ...ructions provided in the blower accessory kit 1 Attach the power cord to the blower motor by firmly pushing the two female terminals at the end of the power cord onto the two spade terminals on the bl...

Страница 17: ...e thermodisc must be oriented near the fireplace bottom as shown in Figure 28 in order to sense temperature and properly operate The blower will be held in position against the back wall by the magnet...

Страница 18: ...External Regulator with Vent Pointing Down Propane LP Only Propane LP Supply Tank External Regulator Vent Pointing Down FIREPLACE INSTALLATION Continued FIREPLACE INSTALLATION Installing Optional Blow...

Страница 19: ...provided by installer from equipment shutoff valve to fireplace Route flexible gas supply line through one of the access holes on side of fireplace 3 Attach flexible gas line from gas supply to contro...

Страница 20: ...ection fluid to all joints Bubbles forming show a leak Correct all leaks at once 5 Light fireplace see Operating Fireplace pages 24 and 25 Check all other internal joints for leaks 6 Turn off fireplac...

Страница 21: ...tch Cleaning Glass Door See Cleaning and Maintenance on page 26 Figure 38 Installing Rear Left and Right Brick Panels Rear Brick Panel INSTALLING BRICK LINER MODELS BL42DA SA BL42DHA SA WARNING If fir...

Страница 22: ...ber Material Figure 44 Placing Ember Material on Burner 8 9 Figure 43 Installing Logs No 8 and No 9 WARNING The glass door must be securely in place before running this fireplace Do not run this firep...

Страница 23: ...ttery by removing the insulat ing tab on the back of the handset see Figure 46 The battery is included pre installed 4 Once the battery is activated the unit is ready to use 5 Close lower louver panel...

Страница 24: ...ars at pilot If lighting the appliance for the first time each season it may take several attempts before the supply gas can reach the pilot and main burners If the appliance will not stay lit after s...

Страница 25: ...ove any dust dirt or other obstructions that will hinder the flow of air BURNER FLAME PATTERN Burner flames will be steady not lifting or floating Flame patterns will be different from unit to unit an...

Страница 26: ...ed CLEANING AND MAINTENANCE CAUTION Wear gloves and safety glasses while handling or removing broken glass Do not remove if glass is hot Keep children and pets away from glass WARNING Donotoperatefire...

Страница 27: ...e and repair 3 Remove debris and dirt inspect and clean any other possible obstructions 4 Contact your gas supplier to check pressure 5 Have a qualified technician replace pi lot line 6 Replace contro...

Страница 28: ...erial OBSERVED PROBLEM Fireplace produces a clicking ticking noise just after burner is lit or shut off Slightsmokeorodorduringinitialoperation Gas odor even when control knob is in OFF position Gas o...

Страница 29: ...CAL SERVICE You may have further questions about installation operation or troubleshooting If so contact DESA s Customer Service Depart mentat1 866 672 6040 Whencalling pleasehaveyourmodeland serial n...

Страница 30: ...rmation visit www desatech com 30 ILLUSTRATED PARTS BREAKDOWN Models V K42EN V K42ENH V K42EP V K42EPH ILLUSTRATED PARTS BREAKDOWN MODELS V K42EN V K42ENH V K42EP V K42EPH 6 7 20 17 18 13 2 12 19 8 1...

Страница 31: ...4 108331 01 Top Louver Assembly 1 5 108331 02 BottomLouver Assembly 1 6 Fireplace Top 1 7 Fireplace Top Insulation 1 8 Fireplace Surround 1 9 109082 02 Heat Shield 1 10 111925 01 Log Set 1 10 1 11193...

Страница 32: ...visit www desatech com 32 ILLUSTRATED PARTS BREAKDOWN Models V K42EN V K42ENH V K42EP V K42EPH ILLUSTRATED PARTS BREAKDOWN BURNER ASSEMBLY FOR MODELS V K42EN V K42ENH V K42EP V K42EPH 7 9 8 12 12 6 1...

Страница 33: ...02 Screw 8 32 x 3 8 PPH Zinc 2 8 108866 01 Pilot Natural Gas 1 108866 02 Pilot Propane LP Gas 1 9 111316 01 Pilot Bracket 1 10 111913 02 Burner Base Gasket 1 11 111310 02 Firebox Bottom 1 12 11165 Scr...

Страница 34: ...s FPD42P Filligree Panel Kit Platinum FPD42PB Filligree Panel Kit Polished Brass LOUVER TRIM KIT Rolled Louvers Only Not Shown LT42B Rolled Louver Trim Kit Brushed Brass LT42P Rolled Louver Trim Kit P...

Страница 35: ...Completed College Completed Graduate School 13 Age of Purchaser Under 20 20 29 30 39 40 49 50 59 60 or Over 14 Buyer s total annual household income Under 15 000 15 000 to 19 999 20 000 to 34 999 35...

Страница 36: ...111922 01C For more information visit www desatech com For more information visit www desatech com 36 2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 Postage Required TAPE TAPE...

Страница 37: ...___________________________________________________________ _______________________________________________________________________________________________ ____________________________________________...

Страница 38: ...ansportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE...

Отзывы: