12
104433
VENT-FREE NATURAL GAS HEATER
15,000 TO 30,000 BTU/HR
Tee Joint
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap
Test
Gauge
Connection *
Tee Joint
Pipe Nipple
Cap
Sediment
Trap
Pressure
Regulator
3/8" NPT
Pipe Nipple
Ground
Union
Joint
Heater
Cabinet
3" Minimum
Note: Burner bracket
not shown for clarity
Equipment Shutoff
Valve *
From Gas Meter
(5" W.C. to 10.5"
W.C. Pressure)
Figure 20 - Gas Connection
* An CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is an
acceptable alternative to test gauge connection. Purchase the optional CSA/AGA design-
certified equipment shutoff valve from your dealer. See Accessories, page 21.
We recommend that you install sediment
trap in supply line as shown in Figure 20,
below. Locate sediment trap where it is
within reach for cleaning. Install in piping
system between fuel supply and heater.
Locate sediment trap where trapped matter
is not likely to freeze. A sediment trap traps
moisture and contaminants. This keeps them
from going into heater controls. If sediment
trap is not installed or is installed wrong,
heater may not run properly.
IMPORTANT:
Hold pressure regulator with
wrench when connecting it to gas piping
and/or fittings.
CONNECTING TO GAS
SUPPLY
WARNING: A qualified service
person must connect heater to gas
supply. Follow all local codes.
IMPORTANT:
Check gas line pressure be-
fore connecting heater to gas line. Gas line
pressure must be no greater than 14 inches
of water. If gas line pressure is higher,
heater regulator damage could occur.
Installation must include a equipment shutoff
valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from
heater (see Figure 20).
IMPORTANT:
Install equipment shutoff
valve in an accessible location. The equip-
ment shutoff valve is for turning on or
shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.
WARNING: Never connect
heater to private (non-utility) gas
wells. This gas is commonly
known as wellhead gas.
CAUTION: Use only new,
black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
or greater diameter to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.
CAUTION : Use pipe joint seal-
ant that is resistant to liquid pe-
troleum (LP) gas.
INSTALLATION
Continued
WARNING: This appliance re-
quires a 3/8" NPT (National Pipe
Thread) inlet connection to the
pressure regulator.