TERMINATION CAP

AIR SUPPLY INLET

GAS METER

RESTRICTED AREA
(TERMINATION PROHIBITED)

A = clearance above grade, veranda, porch, deck, or balcony 

[*12 inches (305mm) minimum]

B =  clearance to window or door that may be opened 

[12 inches (305mm) minimum]

C = clearance to permanently closed window [minimum 12 inches 

(305mm) recommended to prevent condensation on window]

D = vertical clearance to ventilated soffit located above the terminal

within a horizontal distance of 24 inches (610mm) from the
center-line of the terminal [18 inches (457mm) minimum]

E = clearance to unventilated soffit [12 inches (305mm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly within 

36 inches  (914mm) horizontally from the center-line of the regulator

I = clearance to service regulator vent outlet [*72 inches (1829mm)

minimum]

J = clearance to non-mechanical air supply inlet to building or the 

combustion air inlet to any other fireplace [*12 inches (305mm) 
minimum]

K = clearance to a mechanical air supply inlet [*72 inches (1829mm)

minimum]

L = † clearance above paved side-walk or a paved driveway located on 

public property [*84 inches (2133mm) minimum]

M = clearance under veranda, porch, deck [*12 inches (305mm) minimum ‡]
N = clearance above a roof shall extend a minimum of 24 inches (610mm)

above the highest point when it passes through the roof surface and
any other obstruction within a horizontal distance of 18 inches (457mm) 

† vent shall not terminate directly above a side-walk or paved driveway which is located between two

single family dwellings and serves both dwellings*

‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
* as specified in CAN/SGA B149 (.1 or .2) Installation Codes (1991) for Canada or for U.S.A. installation follow

the current 

National Fuel Gas Code, ANS Z223.1

Note: Local codes or regulations may require different clearances

A = 6" (152mm)

Inside Corner

V

B

E

V

B = 6" (152mm)

C = Maximum depth of 48" (1219mm) for

recessed location

D = Minimum width for back wall of 

recessed location -
Combustible - 38" (965mm)
Noncombustible - 24" (610mm)

E = Clearance from corner in 

recessed location-
Combustible - 6" (152mm)
Noncombustible - 2" (51mm)

Outside Corner

Recessed Location

G

H

G = Combustible 24" (610mm)

Noncombustible 18" (457mm)

Balcony with No Side Wall

V

J

Combustible & 
Noncombustible
H = 24" (610mm)
J = 20" (508mm)

Balcony with Perpendicular Side Wall

C

D

C

Termination Clearances for Buildings with Combustible and Noncombustible Exteriors

Figure 8 - Minimum Clearances for Vent Terminations

GENERAL VENTING

Continued

Содержание Comfort Glow CHDV37N

Страница 1: ...itional information consult a qualified installer service agency or the gas supplier Aftermarket Completion of sale not for purpose of resale from the manufacturer WARNING If the information in this m...

Страница 2: ...indicated on fire place nameplate 14 This appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electri cal Code ANS...

Страница 3: ...a piezo ignitor This sys tem requires no matches batteries or other sources to light fireplace Figure 1 Comfort Glow Direct Vent Fireplace HDV Series Glass Door Assembly Blower Adjustment Optional In...

Страница 4: ...tain a minimum 1 clearance to combustibles 37 1 2 41 1 2 34 3 4 20 Vertical Termination 19 Horizontal Termination Note Where two numbers are given the top number is exclusive to the 37 Fireplace and t...

Страница 5: ...delines OnlyuseComfortGloworSimpsonDura Vent GS venting components or kits spe cifically approved for this fireplace Minimum clearance between vent pipes and combustible materials is 1 25 mm except wh...

Страница 6: ...above paved side walk or a paved driveway located on public property 84 inches 2133mm minimum M clearance under veranda porch deck 12 inches 305mm minimum N clearance above a roof shall extend a minim...

Страница 7: ...r length of vent pipe for the type of termination you choose It is also important to note the wall thickness For Horizontal Termination Select the amount of vertical rise desired The horizon tal run o...

Страница 8: ...ion of pipe and el bows to the appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have four locking lugs indentations T...

Страница 9: ...p Position the vent cap in the center of the 7 1 2 or 10 hole on the exterior wall with the arrow on the vent cap pointing up Insure proper clearance of 1 to combustibles is maintained At tach the ven...

Страница 10: ...figuration for use with corner installation Horizontal Venting See information in Figure 17 for Vertical V and Horizontal H maximums and minimums The same amounts apply for flexible venting Note Figur...

Страница 11: ...x 8 min 8 min 20 max 20 max 8 max 20 max Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max 20 max 20 max Figure 19 Horizontal Termina...

Страница 12: ...g members Note Pay spe cial attention to these installation in structions for required clearances air space to combustibles when passing through ceilings walls roofs enclo sures attic rafters etc Do n...

Страница 13: ...e Figure 23 Align the support box vertically and horizontally using a level Temporarily tack the support box in place through the inside walls and into the roof sheathing 4 Using tin snips cut the sup...

Страница 14: ...Vertical Rigid Venting Configuration With No Horizontal Run VENTING INSTALLATION Continued Venting with Two 90 Elbows Vertical V1 Horizontal H 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note V...

Страница 15: ...2 Firestop Support Roof Flashing RTV Silicone Vertical Termination and 26 screws CD1000 7 x 12 Galvanized Coaxial Pipe Qty 1 CD1010 7 x 24 Galvanized Coaxial Pipe Qty 1 CD1020 7 x 48 Galvanized Coaxia...

Страница 16: ...ating system you may run system scirculatingblowerwhile using heater This will help circu late the heat throughout the house In the event of a power outage you can use this heater as your primary heat...

Страница 17: ...port bracket if exiting through the right side see Figure 33 Route power cord through both plastic bushing s and plug the power cord into a properly grounded 3 prong wall receptacle near the firebox...

Страница 18: ...lator with the vent pointing down as shown in Figure 34 Pointing the vent down protects it from freezing rain or sleet WARNING A qualified ser vice person must connect fire place to gas supply Follow...

Страница 19: ...rough one of the access holes on side of fireplace 3 Attach a 45 flare union gas connector to flexible gas line from gas supply see Figure 36 Connect flare union to flex ible gas line attached to gas...

Страница 20: ...l shutoff valve see Fig ure 37 2 Open propane LP supply tank valve for propane LP fireplace or main gas valve located on or near gas meter for natu ral gas fireplace 3 Make sure control knob of firepl...

Страница 21: ...ire hazard will occur 7 Connect one bare wire end to each ter minal W and R of the thermostat base see Figure 42 8 Install the base to the wall with screws provided with thermostat 9 Move the temperat...

Страница 22: ...y both sides and ease it upward off of the lower bracket see Figure 46 4 To replace glass door follow the above instructions in reverse Figure 46 Removing Replacing Glass Door Figure 45 Removing Top L...

Страница 23: ...brackets to grate Brackets are adjustable left to right to allow proper placement of panel These will hold rear panel in place while installing side panels 5 Install left side brick panel by sliding...

Страница 24: ...der burner Placing lava rock on burner could cause performance problems It is not necessary to use all of the lava rock provided Each log is marked with a number These numberswillhelpyouidentifythelog...

Страница 25: ...wise to PILOT 9 Push in gas control knob all the way and hold Immediately light the pi lot by repeatedly depressing the piezo spark ignitor until a flame appears Continue to hold for about one 1 minu...

Страница 26: ...omfort level you select The ideal comfort setting will vary byhouseholddependingupontheamount of space to be heated the output of the central heating system etc 1 After lighting let pilot flame burn f...

Страница 27: ...r leveling Upon installation the thermostat must be allowed to stabilize at room tempera ture for a minimum of 30 minutes for proper operation To turn the fireplace off adjust thermo stat to the lowes...

Страница 28: ...corrosion of caps pipes and fittings and can be caused by having excessive lateral runs too many el bows or exterior portions of the sys tem being exposed to cold weather 4 Inspect joints to verify t...

Страница 29: ...ose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holdin...

Страница 30: ...urner until air is removed from line Have gas line checked by local pro pane LP or natural gas company 3 Clean burner see Cleaning and Mainte nance page 28 or replace burner orifice 1 Adjust the log s...

Страница 31: ...2 Air holes at burner inlet blocked 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when control knob is in OFF position Gas od...

Страница 32: ...hen servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Note Use only original replacement parts Thiswillprotectyourwarrantycoveragefor...

Страница 33: ...WITH SQUARE LEG STYLING UNFINISHED GMC511U 37 GMC513U 41 For use with all models This oak veneer mantel is unfinished and ready to stain or paint Complete assembly instructions are in cluded along wi...

Страница 34: ...P REMOTE OFF ON 28 5 44 1 2 3 4 5 6 5 5 7 7 8 9 10 11 Included in Hardware Pack 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 29 30 31 6 6 38 32 33 34 35 59 36 33 37 39 2 39 3 39 1 42 43 45 48 47 46...

Страница 35: ...01 Rear Burner Natural 41 1 27 104488 03 Burner Manifold 1 28 104489 01 Burner Gasket 1 29 104506 04 Orifice 1 30 104506 08 Orifice 37 1 104506 11 Orifice 41 1 31 104507 01 Brass Elbow 1 32 104574 01...

Страница 36: ...P REMOTE OFF ON 28 5 44 1 2 3 4 5 6 5 5 7 7 8 9 10 11 Included in Hardware Pack 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 29 30 31 6 6 38 32 33 34 35 59 36 33 37 39 2 39 3 39 1 42 43 45 48 47 46...

Страница 37: ...104574 01 Brass Elbow 1 33 104508 01 Brass Fitting 3 34 104608 02 Aluminum Tubing Assy 37 1 104608 01 Aluminum Tubing Assy 41 1 PARTS LIST DIRECT VENT FIREPLACE CHDV37P AND CHDV41P This list contains...

Страница 38: ...pairing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRES...

Отзывы: