background image

www.desatech.com

113896-01D

6

AIR FOR COMBUSTION 

AND VENTILATION

Continued

Unusually Tight Construction

The air that leaks around doors and windows 

may provide enough fresh air for combustion and 

ventilation. However, in buildings of unusually 

tight construction, you must provide additional 

fresh air.

Unusually tight construction is defined as 
construction where:
a.  walls and ceilings exposed to the out-

side  atmosphere  have  a  continuous 
water  vapor  retarder  with  a  rating  of 
one perm (6 x 10

-11

 kg per pa-sec-m

2

) or 

less with openings gasketed or sealed 
and

b.  weather stripping has been added on 

openable windows and doors and 

c.  caulking  or  sealants  are  applied  to 

areas  such  as  joints  around  window 
and door frames, between sole plates 
and floors, between wall-ceiling joints, 
between  wall  panels,  at  penetrations 
for plumbing, electrical and gas lines 
and at other openings. 

If your home meets all of the three criteria 
above, you must provide additional fresh 
air.  See 

Ventilation  Air  From  Outdoors

page 7. 
If your home does not meet all of the three 
criteria  above,  proceed  to 

Determining 

Fresh-Air Flow For Fireplace Location

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1

 defines 

a confined space as a space whose volume is less 

than 50 cubic feet per 1,000 Btu per hour (4.8 m

3

 

per kw) of the aggregate input rating of all appli

-

ances installed in that space and an unconfining 

space as a space whose volume is not less than 

50 cubic feet per 1,000 Btu per hour (4.8 m

3

 per 

kw) of the aggregate input rating of all appliances 

installed in that space. Rooms communicating 

directly with the space in which the appliances 

are installed*, through openings not furnished 

with doors, are considered a part of the uncon

-

fined space.

* Adjoining rooms are communicating only if 

there are doorless 

DETERMINING FRESH-AIR FLOW 
FOR FIREPLACE LOCATION

Determining if You Have a Confined or 
Unconfined Space

Use this work sheet to determine if you have a 

confined or unconfined space.

Space:

 Includes the room in which you will install 

heater plus any adjoining rooms with doorless 

passageways or ventilation grills between the 

rooms.

1.  Determine the volume of the space (length x 

width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

 

Example: 

Space size 20 ft. (length) x 16 ft. 

(width) x 8 ft. (ceiling height) = 2560 cu. ft. 

(volume of space)

 

If additional ventilation to adjoining room is 

supplied with grills or openings, add the volume 

of these rooms to the total volume of the space. 

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support.

 

 __________

(volume of space) x 20 = (Maxi

-

mum Btu/Hr the space can support)

 

Example:

 2560 cu. ft. (volume of space) x 20 = 

51,200 (maximum Btu/Hr the space can support)

3.  Add the Btu/Hr of all fuel burning appliances in 

the space.

 

Vent-free fireplace 

 ___________ Btu/Hr

 

Gas water heater* 

 ___________ Btu/Hr

 

Gas furnace 

 ___________ Btu/Hr

 

Vented gas heater 

 ___________ Btu/Hr

 

Gas fireplace logs 

 ___________ Btu/Hr

 

Other gas appliances*  +

 __________ Btu/Hr

 

Total 

= __________ Btu/Hr

 

* Do not include direct-vent gas appliances. Di

-

rect-vent draws combustion air from the outdoors 

and vents to the outdoors.

 

Example:

 

Gas water heater 

__________ Btu/Hr

 

Vent-free fireplace 

+

  ________ Btu/Hr

 

Total 

=  ________ Btu/Hr

4.  Compare the maximum Btu/Hr the space can 

support with the actual amount of Btu/Hr used.

 

 _________

Btu/Hr (maximum the space can support)

 

 _________

Btu/Hr (actual amount of Btu/Hr used)

 

Example:

  51,200 Btu/Hr (maximum the space 

can support) 

 

 

56,000  Btu/Hr  (actual  amount  of 

Btu/Hr used)

  30,000

  26,000

  56,000

f i r e - p a r t s . c o m

Содержание Comfort Glow CF26NTA

Страница 1: ...y phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and serv...

Страница 2: ...s an unvented gas fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven ti...

Страница 3: ...rtain you read and understand all warn ings Keep this manual for reference It is your guide to safe and proper operation of this heater WARNING Any change to this heater or its controls can be dangero...

Страница 4: ...tilation to run properly This fireplace has an Oxygen Deple tion Sensing ODS safety shutoff system The ODS shuts down the fireplace if not enough fresh air is available See Air for Combustion and Vent...

Страница 5: ...s are built more energy efficient than ever New materials increased insulation and new construction methods help reduce heat loss in homes Home owners weather strip and caulk around windows and doors...

Страница 6: ...re considered a part of the uncon fined space Adjoining rooms are communicating only if there are doorless DETERMINING FRESH AIR FLOW FOR Fireplace LOCATION Determining if You Have a Confined or Uncon...

Страница 7: ...two perma nent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see options 1 and 2 Figure 2 You can also remove door into adjoining room see...

Страница 8: ...e minimum clearances shown in Figure4and5 page9 Ifyoucan providegreaterclearancesfrom floor ceiling and joining wall You can recess firebox into the wall You can also position fireplace in the optiona...

Страница 9: ...42 365 8 257 8 513 4 267 8 Figure 6 Rough Opening for Installing in Corner 267 8 267 8 3 4 Off The Floor Minimum 10 1 2 Figure 5 Rough Opening for Installing in Wall Figure 4 Minimum Clearance for Co...

Страница 10: ...the firebox front facing IMPORTANT Noncombustible materials such as brick tile etc may overlap the front facing but should never cover any necessary openings like louvered slots WARNING Do not allow n...

Страница 11: ...shim in slot on mitered edge of side trim see Figure 9 6 While firmly holding edges of trim together tighten both set screws on the adjusting plate with slotted screwdriver 7 Repeat steps 1 through 6...

Страница 12: ...nnection when servicingcontrols Wiringerrors cancauseimproperanddanger ous operation CAUTION Verify proper op eration after servicing Note If you are using a mantel with your heater use the following...

Страница 13: ...onnect red wire to theAUTO switch posi tion Reconnect blue wire to the ON switch position Reconnect green and white wires to the power cord 10 Install the switch plate on the blower control shield wit...

Страница 14: ...not included Outlet Receptacle Strain Relief Blue Red 1 Install a snap bushing found in hardware kit into one of the holes found on rear of blower control shield The other hole is for a strain relief...

Страница 15: ...ent trap tee joint pipe wrench test gauge connection ACSAdesign certified equipment shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the optional CSA desig...

Страница 16: ...ied equipment shutoff valve from your dealer See Accessories page 27 Minimum inlet pressure for purpose of input adjustment 3 Minimum Gas Control Propane LP From External Regulator 11 W C to 14 W C Pr...

Страница 17: ...l valve and equipment shutoff valve from gas supply piping system Pressures in excess of 1 2 psig will damage heater regulator 2 Cap off open end of gas pipe where equipment shutoff valve was connecte...

Страница 18: ...ernal joints for leaks 7 Turn off heater see To Turn Off Gas to Appli ance page 21 8 Replace front panel INSTALLING LOGS WARNING Failure to posi tion the parts in accordance with these diagrams or fai...

Страница 19: ...shutoff valve is fully open 3 Turn control knob clockwise to the OFF position 4 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in...

Страница 20: ...E 1 Follow steps 1 through 6 under Lighting Instructions page 19 2 Depress control knob and light pilot with match 3 Keep control knob pressed in for30 seconds after lighting pilot After 30 seconds re...

Страница 21: ...t hair with a soft cloth or vacuum cleaner nozzle 5 Blow air into the primary air holes on the injector holder 6 In case any large clumps of dust have now been pushed into the burner repeat steps 3 an...

Страница 22: ...1 Ignitor electrode not con nected to ignitor cable 2 Ignitor cable pinched or wet 3 Piezo ignitor nut is loose 4 Broken ignitor cable 5 Bad piezo ignitor 6 Ignitor electrode positioned wrong 7 Ignito...

Страница 23: ...toff valve 2 Turn control knob to PILOT position 3 Press in control knob while in PILOT position 4 Continue holding down con trol knob Repeat igniting op eration until air is removed 5 Contact local p...

Страница 24: ...rner for dirt and debris If found clean burner see Cleaning and Mainte nance page 21 2 Replace gas control 3 Problem will stop after a few hours of operation 1 Refer to Air for Combustion and Ventilat...

Страница 25: ...DS pilot seeCleaning and Maintenance page 21 1 Locate and correct all leaks see Checking Gas Connec tions page 17 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and...

Страница 26: ...call DESA Heating Products at 1 866 672 6040 for referral information When calling DESA Heating Products have ready model number of your heater the replacement part number Parts Central These Parts C...

Страница 27: ...SE Not Shown GMC83F Oak Finished Georgian Design CS26CP Black Red Oak Cottage Design GMC63UD Unfinished Traditional Design CMA208FB Light Oak Finished Traditional Design For all models Space saving ma...

Страница 28: ...www desatech com 113896 01D 28 Illustrated Parts Breakdown Models CF26PTA and CF26NTA 12 9 10 11 16 20 18 1 8 5 4 7 6 19 13 19 14 2 19 19 3 15 17 19 fire parts com...

Страница 29: ...nlet Tube 1 8 102983 06 Outlet Burner Tube 1 111331 08 Outlet Burner Tube 1 9 099056 29 Burner Orifice Injector 1 099056 20 Burner Orifice Injector 1 10 111124 01 Burner Retainer Spring 1 11 102980 01...

Страница 30: ...www desatech com 113896 01D 30 ILLUSTRATED PARTS BREAKDOWN Models CF26PTA and CF26NTA 5 8 15 17 13 14 11 2 11 1 19 4 12 16 10 6 5 9 1 2 18 7 20 2 20 3 20 1 18 18 16 21 3 18 16 3 21 fire parts com...

Страница 31: ...1 8 Bay Front Base 1 9 105421 01 Heat Deflector 1 10 105409 01 Fan Control Shield 1 11 1 105401 01 Screen Rod 1 11 2 105440 01 Screen Assembly 1 12 101386 02 Hinge 2 13 Rivets 8 14 105262 01CK Louver...

Страница 32: ...ts related to repairing a defective fireplace will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRAN...

Отзывы: