Desa CDCFNR Скачать руководство пользователя страница 8

www.desatech.com

111244-01G

8

aiR FoR ComBUsTioN 

aND VENTilaTioN

Continued

4.  Compare the maximum Btu/Hr the space can 

support with the actual amount of Btu/Hr used.

 

 _______

Btu/Hr (maximum the space can support) 

 

 _______

Btu/Hr (actual amount of Btu/Hr used)

 

Example:

  35,840 Btu/Hr (maximum the space 

can support) 

 

 

40,000  Btu/Hr  (actual  amount  of 

Btu/Hr used)

The space in the above example is a confined space 

because the actual Btu/Hr used is more than the maxi-

mum Btu/Hr the space can support. You must provide 

additional fresh air. Your options are as follows:

A.  Rework worksheet, adding the space of an adjoin

-

ing room. If the extra space provides an unconfined 

space, remove door to adjoining room or add 

ventilation grills between rooms. See 

Ventilation 

Air From Inside Building.

B.  Vent room directly to the outdoors. See 

Ventila-

tion Air From Outdoors

.

C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr 

size makes room unconfined. 

If the actual Btu/Hr used is less than the maximum Btu/Hr 

the space can support, the space is an unconfined space. 

You will need no additional fresh air ventilation.

  WARNING:  If  the  area  in 

which the fireplace may be oper-

ated is smaller than that defined 

as an unconfined space or if the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the 

National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 Section 5.3 

or applicable local codes. 

VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining un-

confined space. When ventilating to an adjoining 

unconfined space, you must provide two permanent 

openings: one within 12" of the ceiling and one within 

12" of the floor on the wall connecting the two spaces 

(see options 1 and 2, Figure 5). You can also remove 

door into adjoining room (see option 3, Figure 5). Fol

-

low the 

National Fuel Gas Code, ANSI Z223.1/NFPA 

54, Section 5.3, Air for Combustion and Ventilation

 

for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or 

ducts. You must provide two permanent openings: 

one within 12" of the ceiling and one within 12" 

of the floor. Connect these items directly to the 

outdoors or spaces open to the outdoors. These 

spaces include attics and crawl spaces. Follow the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, 

Section 5.3, Air for Combustion and Ventilation

 for 

required size of ventilation grills or ducts. 

IMPORTANT:

 Do not provide openings for inlet 

or outlet air into attic if attic has a thermostat-

controlled power vent. Heated air entering the attic 

will activate the power vent.

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Figure 5 - Ventilation Air from Inside 

Building

Or

Remove

Door into

Adjoining

Room,

Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

12"

12"

Figure 6 - Ventilation Air from Outdoors

Содержание CDCFNR

Страница 1: ...damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to ligh...

Страница 2: ...appliance is not convert ible for use with other gases Aftermarket Completion of sale not for purpose of resale from the manufacturer Table of Contents Safety Information 3 Product Identification 4 Op...

Страница 3: ...sand orgenerateschemicals known to the State of California to cause cancer or birth defects or other reproductive harm IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assembl...

Страница 4: ...uld occur due to log curing and fireplace burning manufacturing residues 8 To prevent the creation of soot follow the instructions in Cleaning and Maintenance page 28 9 Before using furniture polish w...

Страница 5: ...s to light fireplace Thermostatic Heat Control for thermostat Controlled Models Thermostat Controlled models have a thermostat sensing bulb and a control valve The thermostat will automatically modula...

Страница 6: ...4 Tighten screws firmly Figure 3 Removing and Installing Screen Screen Shoulder Screw Figure 4 Assembling Hood Hood Sheet Metal Screws Firebox Top Louver Air for Combustion and Ventilation WARNING Th...

Страница 7: ...d in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kw of the aggregate input rating of all appliances installed in that sp...

Страница 8: ...ction5 3 or applicable local codes VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining un confined space When ventilating to an adjoining unconfined space...

Страница 9: ...ng the full width and depth of the fireplace Use the dimensions shown for rough openings to create the easiest installation see Built In Fire place Installation page 10 CHECK GAS TYPE Use the correct...

Страница 10: ...wheremoving vehicle will not hit it For convenience and efficiency install fireplace where there is easy access for operation inspec tion and service in coldest part of room An optional blower kit is...

Страница 11: ...Wood Screws Wall Studs Note Aqualified installer should make all electri cal connections 3 Install gas piping to fireplace location This installation includes an approved flexible gas line if allowed...

Страница 12: ...e Installing Optional Blower Accessory GA3450TA page 13 1 Assemble cabinet mantel as shown in acces sory instruction sheet 2 If blower is installed install a properly grounded 120 volt three prong ele...

Страница 13: ...gn shim under adjusting plate as shown in Figure 15 4 Slide one end of adjusting plate shim in slot on mitered edge of top brass trim see Figure 15 5 Slide other end of adjusting plate shim in slot on...

Страница 14: ...ring Diagram For Blower Accessory Standard Installation Red Red Fan Switch Auto Off On Blue Blue Thermostat Switch N O Green White Green White On 110 115 V A C Blower Motor Black Off 1 2 3 Auto Remote...

Страница 15: ...Set cable bundle between the remote blower bracket and outer casing away from the burner 5 Test to make sure blower is working properly 6 Reinstall upper louver beginning with bottom screws see Figur...

Страница 16: ...TO GAS SUPPLY WARNING This appliance requires a 45 male flare fitting 5 8 18 UNF Unified National Fine Thread inlet connection and the flexible gas line provided WARNING A qualified service person mus...

Страница 17: ...tly to male threads of gas connector attached to flex ible gas line equipment shutoff valve see Figure 25 CAUTION Avoid damage to regulator Holdgasregulatorwith wrenchwhenconnectingittogas piping and...

Страница 18: ...opening main gas valve located on or near gas meter for natural gas or using compressed air 3 Check all joints from gas meter to equipment shutoffvalvefornaturalgasorpropane LPsup ply to equipment sh...

Страница 19: ...Disconnecting Wires From Control Valve Figure 30 Attaching Battery to Receiver Battery Clip 9 Volt Battery Receiver Terminal Wires Figure 31 Installing Remote Receiver Remote Receiver White Wire to T...

Страница 20: ...stat has been electroni cally calibrated at the factory No adjustment or leveling is necessary Figure 34 Back View of Thermostat Base Feed wires through rectangular slots W R Figure 35 Thermostat Base...

Страница 21: ...ward 3 Install left and right brick liners using brackets and screws from hardware kit as shown in Fig ure 38 Screw the bracket into top of firebox and against brick liners Adjust bracket before tight...

Страница 22: ...BEFORE LIGHTING WARNING If you do not fol low these instructions exactly a fire or explosion may result causing property damage per sonal injury or loss of life A This appliance has a pilot which mus...

Страница 23: ...LOT position THERMOSTAT CONTROL OPERATION The thermostat used on this fireplace senses the roomtemperature Attimestheroommayexceed thesettemperature Ifso theburnerwillshutoff The burner will cycle bac...

Страница 24: ...part has been underwater Immediatelycallaqualifiedser vicetechniciantoinspecttheapplianceandto replaceanypartofthecontrolsystemandany gas control which has been under water LIGHTING INSTRUCTIONS WARN...

Страница 25: ...clockwise to the OFF position 2 If Using Optional Hand Held Remote Set selector switch in the OFF position to prevent draining battery Shutting Off Burners Only pilot stays lit You may shut off the bu...

Страница 26: ...and Off Thermostat Series Model HRC200 Series The hand held remote can be operated using either the manual mode MANU or thermo static mode AUTO see Figure 50 To select Fahrenheit Centigrade mode displ...

Страница 27: ...m temperature for a minimum of 30 minutes for proper operation See installation instructions on page 19 optional GWMS2 Wall Mounted SWITCH MakesuretheheaterswitchisonAUTO Thiswall switchworksjustliket...

Страница 28: ...son Fireplace may need more frequent cleaning due to excessive lint from carpeting pet hair bedding material etc WARNING Failure to keep the primary air opening s of theburner s cleanmayresultin sooti...

Страница 29: ...from where the pilot flame comes out of the pilot assembly see Figures 57 or 58 depend ing on model With the unit off lightly blow air through the air inlet hole You may blow through a drinking straw...

Страница 30: ...PILOT position 4 Air in gas lines when in stalled 5 Depleted gas supply propane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor ca...

Страница 31: ...ODS pilot lights keep control knob pressed in 30 seconds 3 Wait one minute for safety in terlock system to reset Repeat ignition operation 4 Fully open equipment shutoff valve 5 A Contact local natur...

Страница 32: ...knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural gas company 3 Observe minimum installa tion clearances see page...

Страница 33: ...e Warning state ment at top of page 1 Not enough fresh air is avail able 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warning state ment at top of page 2 Control valve defective...

Страница 34: ...10 5 Minimum 5 Dimensions H x W x D including hood and screws 25 7 8 x 26 13 16 x 15 5 16 For purpose of input adjustment Remote Ready Models VDCFRP FDCFRP CDCFPR Rating 17 000 26 000 Btu Hr Gas Type...

Страница 35: ...placement Parts Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty Parts Under Warranty Contact authorized dealers of this product If t...

Страница 36: ...19 19 19 19 19 19 19 1 9 9 10 10 10 16 17 10 10 14 6 3 11 12 13 11 15 16 18 16 16 16 16 16 16 2 5 16 16 16 16 7 4 Illustrated Parts Breakdown firebox Models CDCFTNA CDCFTPA VDCFTN VDCFTP FDCFTN FDCFT...

Страница 37: ...rebox Wrapper 1 7 110339 01CK Outer Base 1 8 102635 02 Front Left and Right Sides 2 9 103209 01 Extruded Louver 2 103209 05 Extruded Louver 2 10 098304 01 Screw PPH AB 10 16 x 0 38 8 11 M10908 2 Screw...

Страница 38: ...111244 01G 38 Illustrated Parts Breakdown firebox Models CDCFNR and CDCFPR 8 10 8 14 14 14 14 14 14 14 1 9 9 10 10 20 21 22 10 16 17 10 10 6 3 11 12 13 23 19 24 11 15 16 18 16 16 16 16 16 16 16 2 5 16...

Страница 39: ...8 102635 02 Front Left and Right Sides 2 9 103209 05 Extruded Louver 2 10 098304 01 Screw PPH AB 10 16 x 0 38 12 11 M10908 2 Screw SLTD HWH TPG 6 32 x 0 38 4 12 104313 01 Right Pin Hinge 1 13 104313...

Страница 40: ...www desatech com 111244 01G 40 ILLUSTRATED PARTS BREAKDOWN THERMOSTAT MODELS FDCFTP FDCFTN VDCFTP VDCFTN CDCFTPA and CDCFTNA 8 7 5 6 6 12 2 4 19 18 15 16 9 9 17 11 14 3 13 20 9 1 21 10...

Страница 41: ...15 098522 13 Thermostat Gas Valve LP 1 098522 12 Thermostat Gas Valve NG 1 16 101381 01 Valve Cover with Piezo 1 17 101628 03 Flexible Connector 1 18 099211 01 Screw HWH AB 10 16 x 2 50 2 19 098544 0...

Страница 42: ...RATED PARTS BREAKDOWN REMOTE READY MODELS FDCFRN FDCFRP VDCFRN VDCFRP CDCFNR and CDCFPR O F F P I L O T O N H I L O 16 15 15 16 12 12 11 9 9 9 10 5 17 18 13 19 2 1 4 3 14 7 6 8 20 FDCFTN TP VDCFRN RP...

Страница 43: ...DS Nut 2 9 M11084 26 Screw HWH AB 10 16 x 0 38 10 10 Chamber Floor 1 11 110793 01 Piezo Bracket 1 12 102445 01 Piezo Ignitor with Palnut Fastener 1 13 101628 01 Flexible Connector 1 14 098271 10 Ignit...

Страница 44: ...dges of wall opening Included with all mantels THERMOSTAT CONTROLLED BLOWER KIT GA3450TA For all models Provides better heat distribution Makes fireplace more efficient Automatically turns off and on...

Страница 45: ...fire place to be operated in a manually or thermostati cally controlled mode You can turn the fireplace on and off without ever leaving the comfort of your easy chair A wall mount docking station is i...

Страница 46: ..._____________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________...

Страница 47: ..._____________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________...

Страница 48: ...2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 www desatech com 111244 01 Rev G 01 06 NOT A UPC 111244 01...

Отзывы: