73
Modbus
Offset
Register
Detailed Description
* System=sum of three phases
(kVARh, resettable)
47033
7032
Negative kVARh L1 MSW
Individual Phase Negative Reactive Energy MSW
(kVARh, resettable)
47034
7033
Negative kVARh L2 LSW
“
47035
7034
Negative kVARh L2 MSW
“
47036
7035
Negative kVARh L3 LSW
“
47037
7036
Negative kVARh L3 MSW
“
47038
7037
Negative kVAR L1
Individual Phase Negative Instantaneous Reactive
Powers (kVAR)
47039
7038
Negative kVAR L2
“
47040
7039
Negative kVAR L3
“
47041
7040
kVAh L1 LSW
Individual Phase Apparent Energy LSW (kVAh,
resettable)
47042
7041
kVAh L1 MSW
Individual Phase Apparent Energy MSW (kVAh,
resettable)
47043
7042
kVAh L2 LSW
“
47044
7043
kVAh L2 MSW
“
47045
7044
kVAh L3 LSW
“
47046
7045
kVAh L3 MSW
“
47047
7046
kVA L1
Individual Phase Instantaneous Apparent Powers
(kVA)
47048
7047
kVA L2
“
47049
7048
kVA L3
“
47050
7049
Negative Displacement PF L1
Individual Phase Negative Displacement Power
Factors (dPF); Register is 100x actual value (If the
Individual dPF(44050) is Negative, this register will
contain that value else it will be zero)