66
Modbus
Offset
Register
Description
* System=sum of three phases
44082
4081
kVA Demand System Max
System Maximum Instantaneous kVA Demand (kVA,
resettable). It displays the default value after a CAM
until 1 demand window elapses. After a power cycle or
CPU reset the value is not reset but it does not update
again until 1 demand window elapses.
44083
4082
kVA Demand System Now
System Average kVA Demand For the most recent
(current) Demand Window.(resettable) Displays the
default value after a CAM or reset, or power cycle.
Updates every min thereafter. True demand value
takes a demand period to get to actual value. Similar
to 44005
44084
4083
kVAR Demand System Max
System Maximum kVAR Demand (kVAR, resettable). It
displays the default value after a CAM until 1 demand
window elapses. After a power cycle or CPU reset the
value is not reset but it does not update again until 1
demand window elapses.
P
OSITIVE
P
OWER
/E
NERGY
M
EASUREMENT
R
EGISTERS
Modbus
Offset
Register
Description
* System=sum of three phases
46001
6000
Positive kWh System LSW
System Positive True Energy LSW (kWh, resettable)
46002
6001
Positive kWh System MSW
System Positive True Energy MSW (kWh, resettable)
46003
6002
Positive kW System
System Positive Instantaneous Positive True Power
(kW) (net sum of all individual kWs, if sum is negative
value=0)
46004
6003
kW Demand System Max
System Maximum Demand (peak demand).
46005
6004
kW Demand System Now
Average Power (kW) for most recent demand window
46006
6005
Positive kW System Max
System Net Highest Instantaneous Positive Draw
Since Reset (kW, resettable)
46007
6006
Positive kW System Min
System Net Lowest Instantaneous Positive Draw Since
Reset (kW, resettable)
46008
6007
Positive kVARh System LSW
System Net Positive Reactive Energy LSW (kVARh,
resettable)
46009
6008
Positive kVARh System MSW
System Net Positive Reactive Energy MSW (kVARh,