background image

SOLENOID VALVE 

MODELS: 463PS, 464PS & 466PS 

INSTALLATION INSTRUCTIONS

 

I-710 

 

Pg. 1 of 2 

Rev. F-37899   5/29/12

 

200°F

93°C

 

1.

 

INSTALLATION: 

Model 463PS has 3/8” NPT female pipe connections.  Model 464PS has ½” NPT female pipe connections.  Model 
466PS has 3/4” NPT female pipe connections.  They all have stainless steel bodies.  The valves may be installed in any 
position other than with the coil down.  Make sure fluid flow is in the direction of the arrow on the body.  Apply pipe 
dope to male threads, hand tighten, and then turn 1 ½ times with a wrench.  

Note: Wiring must comply with 

Local and National Electrical Codes. 

 

2.

 

FLUIDS:  

Valves are intended for water, air, light oil, and other noncorrosive fluids. They should 

not

 be used for 

gasoline and other hazardous or explosive fluids. Maximum fluid temperature is 200

 F (93.3

C). Ambient 

temperature shall not exceed 120

F (48.8

C).  

WARNING: NOT FOR USE WITH HAZARDOUS OR CORROSIVE OR EXPLOSIVE FLUIDS.

 

 

3.

 

OPERATION: 

When the solenoid coil is energized, the plunger is pulled up, thus opening the small “pilot port” in the center of the 
diaphragm plate.  This releases the pressure on top of the diaphragm allowing incoming pressure to lift it off the larger 
center port.  When the coil is de-energized, the solenoid plunger is pushed down by the kick-off spring and closes the 
pilot port.  Fluid passes through the small diaphragm bleed holes until pressure is equalized on both sides of the 
diaphragm to shut off the larger port. 

 

4.

 

SPECIFICATIONS: 

Maximum operating pressure differential

:  

125 PSI   

 

Power:

  10 Watts 

Safe working pressure

 

  150 

PSI 

  

Volt-Amp Rating

:Inrush - 16.0 VA 

Flow factor (CV):

       

 

 

2.0 

 

 

 

 

Holding - 11.5 VA 

Maximum temperature

 

 

180 °F fluid temp. 

120 °F ambient temp. 

 

5.

 

TROUBLE SHOOTING: 

A)

 

Failure to open: 

1)

 

No power or low voltage. 

2)

 

Coil burnout or an open circuit to coil. 

3)

 

Dirt prevents the plunger/diaphragm from 

operating. 
4)

 

Pressure differential over the (125 PSI Max.). 

5)   Low differential pressure ( 3 PSI Min. ). 

B)

 

Failure to close: 

1)

 

Coil still energized. 

2)

 

Valve installed backward. 

3)

 

Dirt  in diaphragm bleed hole. 

4)    Low differential pressure ( 3 PSI Min. ). 

C)

 

Water Hammer: 

Quick acting valves may cause water hammer 
when operated.  If this occurs, it may be 
minimized by the use of a standpipe or other 
commercially available shock absorber installed 
near the valve inlet. 

CAUTION:     WHEN SERVICING THE VALVE, BE SURE THAT REPLACEMENT PARTS HAVE BEEN 

INSTALLED ACCORDING TO THE DRAWING ON THE LAST PAGE. 

 
RETURNS:

 

NO MERCHANDISE MAY BE RETURNED FOR CREDIT WITHOUT DEMA’S 
WRITTEN PERMISSION.  RETURN MERCHANDISE AUTHORIZATION NUMBER 
REQUIRED IN ADVANCE OF RETURN. 

 
WARRANTY:

 

DEMA products are warranted against defective material and workmanship under normal use 
and service for one year from the date of manufacture.  This limited warranty does not apply to 
any products which have a normal life shorter than one year or failure and damage caused by 
chemicals, corrosion, improper voltage supply, physical abuse, or misapplication.  Rubber and 
synthetic rubber parts such as “O”- rings, diaphragms, squeeze tubing and gaskets are considered 
expendable and are not covered under warranty.  This warranty is extended only to the original 
buyer of DEMA products.  If products are altered or repaired without prior approval of DEMA, 
this warranty will be void. 

 

 

Defective units or parts should be returned to the factory with transportation prepaid.  If 
inspection shows them to be defective, they will be repaired or replaced without charge, F.O.B. 
factory.  DEMA assumes no liability for damages.  Return merchandise authorization number, to 
return units for repair or replacement, must be granted in advance of return. 

 

Отзывы: