background image

2

Compressor

Oil Removal

Filter

Aftercooler

Automatic Drain

Dryer

Separator

Receiver

TYPICAL COMPRESSED AIR SYSTEM

INSTALLATION

Ambient Air Temperature

Locate the dryer indoors where the ambient air temperature 

will be between 40°F (4°C) and 110°F (43°C). Intermittent op-

eration at ambient temperatures up to 113°F (45°C) will not 

damage the dryer but may result in a higher dew point or dryer 

shutdown due to high refrigerant discharge pressure (see Field 

Service Guide).
Do not operate dryers at ambient air temperatures below 40°F 

(4°C). Such operation may result in low suction pressure, caus-

ing freeze-up.

Location and Clearance

Mount the dryer on a level solid surface. Holes are provided in 

the dryer base to permanently mount the dryer to the floor. If 

the base vibrates, bolt the unit down using vibration dampeners. 

Allow at least 36 inches (914 mm) clearance on the sides and 

the front of the dryer for cooling airflow and for service access.

System Arrangement

Liquid water in the inlet air will adversely affect the performance 

of the dryer. Install the dryer downstream of an aftercooler or 

separator so that the temperature of the dryer inlet air does 

not exceed 120°F (49°C) and the inlet air does not contain any 

liquid water.
If the compressed airflow is relatively constant and does not 

exceed the dryer flow rating, it is recommended that the dryer 

be located downstream of the receiver tank. If the nature of the 

application is such that the air demand regularly exceeds the 

dryer flow rating, it is recommended that the dryer be located 

upstream of the receiver.
For safety and convenience, install inlet and outlet shutoff valves 

and depressurization valves. These valves allow the dryer to be 

isolated and depressurized for servicing. Bypass piping may 

be installed around the dryer for uninterrupted airflow when 

the dryer is serviced. If the compressed air operation cannot 

tolerate undried air for short periods, install a second dryer in 

the bypass line.
Compressed air systems commonly require filters to remove 

compressor oils, particulates, condensed liquids and other 

contaminants. When an oil-removal filter is used, it should be 

installed downstream of the refrigerated dryer. At this location, 

the life of the replaceable filter element is prolonged since 

some of the entrained oil is removed by the dryer and drained 

through the separator.

Piping and Connections

Piping must be furnished by the user unless otherwise speci-

fied. Connections and fittings must be rated for the maximum 

operating pressure given on the dryer data plate and must be 

in accordance with applicable codes. Support all piping; do not 

allow the weight of any piping to stress the dryer or filter con-

nections. Piping should be at least the size of the inlet and outlet 

connections to minimize pressure drop in the air system. See 

Engineering Data section for dryer inlet and outlet connections 
1.  Air Inlet - Connect compressed air line from air source to 

air inlet.

  Refer to Serial Number Tag for maximum working 

pressure. Do not exceed dryer's Maximum Working Pressure.

NOTE:

 Install air dryer in air system at highest pressure possible 

(e.g. before pressure reducing valves).

NOTE:

 Install dryer at coolest compressed air temperature 

possible. Maximum inlet compressed air temperature: 120°F 

(49°C). If inlet air exceeds this temperature, precool the air with 

an aftercooler.
2.  Air Outlet - Connect air outlet to downstream air lines.
3.  Bypass Piping - If servicing the dryer with interrupting the 

air supply is desired, piping should include inlet and outlet 

valves and an air bypass valve.

4.  Water-cooled models - cooling water inlet and outlet.

a)  Connect cooling water supply to cooling water inlet.
b)  Connect cooling water return line to cooling water 

outlet connection.

NOTE: 

Strainer and water regulating valve are supplied on water-

cooled models. Also, it is recommended to add water inlet/

outlet temperature and pressure gauges to the water piping.

Removing Condensate

Condensate must be drained from the dryer to prevent re-

entrainment. The dryers are equipped with automatic drain 

valves and internal drain hoses up to the drain connections on 

the dryer cabinets. The user must install a separate discharge 

line at the drain connection to carry off condensate to an envi-

ronmentally approved condensate collection/disposal system. 

Piping or copper tubing 1/2 inch or larger is recommended 

for condensate discharge lines.  Install the drain lines so that 

condensate can be seen as it drains.

Electrical Connections

The dryers are constructed according to NEMA Type 1 electrical 

standards. Field wiring must comply with local and national fire, 

safety and electrical codes. Installation must be in accordance 

with the National Electrical Code.  

IMPORTANT:

 Use copper supply wires only.

1.  Dryer is designed to operate on the voltage, phase, and 

frequency listed on the dryer serial number tag.

2.  Electrical entry is through a hole in the back of the cabinet. 

Route wires through the bottom of the electrical enclosure. 

Connect power source to the terminal strip in the electrical 

enclosure as shown on the electrical schematics included 

in this manual.

MCGUIRE AIR COMPRESSORS INC

1-888-229-9999

MCGUIRE AIR COMPRESSORS INC

1-888-229-9999

Содержание HGEN Series

Страница 1: ...GEN800 HGEN1000 HGEN1200 FOR M NO 7426448 R EVI S ION 10 2018 R EAD AN D U N D E R STAN D TH I S MAN UAL PR IOR TO OPE RATI NG OR S E RVICI NG TH I S PROD UCT I N STR UCTION MAN UAL MCGUIRE AIR COMPRE...

Страница 2: ...HGEN600A 11 Models HGEN800A through HGEN1200A 12 Air and Refrigerant Flow Schematics Model HGEN600A 13 Models HGEN800A through HGEN1200A 14 WATER COOLED UNITS General Arrangement Drawings Model HGEN60...

Страница 3: ...ators are attached to the shipping container before it leaves the factory Check these before accepting unit from carrier s agent Check for Visible Loss or Damage If this shipment shows evidence of los...

Страница 4: ...perating pressure given on the dryer data plate and must be in accordance with applicable codes Support all piping do not allow the weight of any piping to stress the dryer or filter con nections Pipi...

Страница 5: ...f Time using step 2 4 To store the Off Time press the Enter button 5 again 5 Exiting the Program will cause the Timer Drain to discharge and begin a new cycle NOTE Failure to perform step 3 within 10...

Страница 6: ...r connection and support of compressed air lines to the dryer check bypass valve system if installed 4 Energize Dryer Turn disconnect switch to ON position Green dryer ON OFF switch will illuminate En...

Страница 7: ...body may need to be cleaned under condi tions of gross particulate contamination To disassemble the drain valve body for cleaning and other maintenance 1 Turn power switch off 2 Disconnect main power...

Страница 8: ...ure too high Verify ambient temperature throughout day High pressure switch activated Press manual reset button to switch to reset button Compressor overheated Turn dryer off Contact local distributor...

Страница 9: ...igh a c 398 psig manual reset 27 4 barg manual reset High w c 313 psig manual reset 21 6 barg manual reset Air Cooled Condensers Air Flow Across Condenser cfm 60 Hz 2 825 4 120 4 120 4 120 Condenser F...

Страница 10: ...44 1281 3 4 86 123 5 7 94 201 6 3 23 82 0 26 74 679 2 20 24 514 4 18 106 2 40 94 1040 49 26 1251 2 2 NPT 344 156 DRIED AIR OUTLET WETTED AIR INLET AIR FLOW COOLING HOLE FOR MAIN POWER DRAIN OUTLET 5 1...

Страница 11: ...536 10 00 254 26 77 680 28 35 720 37 40 950 41 34 1050 59 83 1519 6 35 22 894 5 6 12 155 5 3 35 85 3 ANSI Flange 695 315 WETTED AIR INLET DRIED AIR OUTLET COOLING AIR FLOW REAR VIEW FRONT VIEW LEFT S...

Страница 12: ...629 6 38 68 982 5 6 59 167 5 3 35 85 4 ANSI Flange 744 337 HGEN1200A 31 60 802 7 20 60 523 3 11 00 279 4 26 77 680 28 35 720 41 34 1050 45 28 1150 64 16 1629 6 38 68 982 5 6 59 167 5 3 35 85 4 ANSI Fl...

Страница 13: ...TH Thermal Relay S3 Fan pressure switch S1 Switch on off S4 High pressure switch SENSOR Temperature Sensor GL1 Green Lamp SOL1 Electronic drain DCB Digtal Control Board 120V 0V 50VA 480V 0V TRANSFORME...

Страница 14: ...P1 CIRCUIT PROTECTOR FOR CONTROL POWER S1 SWITCH ON OFF MC2 MAGNETIC CONTACTOR FOR MOTOR S2 FAN PRESSURE SWITCH SENSOR TEMPERATURE SENSOR GL1 GREEN LAMP SOL1 ELECTRONIC DRAINVALVE 1 DCB2 DIGITAL CONTR...

Страница 15: ...DISPLAY TI SCHRADERVALVE REF AIR S WETTED AIR INLET DRIED AIR OUTLET AIR AIR MOISTURE SEPARATOR INTEGRATED BRAZED PLATE HEAT EXCHANGER STRAINER BALLVALVE DRAIN OUTLET TIMED ELECTRIC AUTO DRAINVALVE F...

Страница 16: ...ESSED AIR FLOW REFRIGERANT FLOW WETTED COMPRESSED AIR INLET DRYED COMPRESSED AIR OUTLET MOISTURE SEPARATOR INTEGRATED BRAZED PLATE HEAT EXCHANGER 1 S MOISTURE SEPARATOR INTEGRATED BRAZED PLATE HEAT EX...

Страница 17: ...4 86 123 5 7 94 201 6 3 23 82 26 74 679 2 20 24 514 4 18 106 2 40 94 1040 49 26 1251 2 4 52 114 8 9 84 250 1 97 50 2 NPT 3 4 NPT 358 162 DRIED AIR OUTLET WETTED AIR INLET COOLING WATER OUTLET COOLING...

Страница 18: ...36 10 00 254 26 77 680 28 35 720 37 40 950 41 34 1050 41 34 1050 35 22 894 5 6 12 155 5 3 35 85 6 40 162 5 9 84 250 1 97 50 3 ANSI Flange 3 4 NPT 534 242 AIR INLET AIR OUTLET COOLING WATER OUTLET COOL...

Страница 19: ...5 3 35 85 6 40 162 5 9 84 250 1 97 50 4 ANSI Flange 1 NPT 582 264 HGEN1200W 31 60 802 7 20 60 523 3 11 00 279 4 26 77 680 28 35 720 41 34 1050 45 28 1150 41 34 1050 38 68 982 5 6 59 167 5 3 35 85 6 4...

Страница 20: ...lay S1 Switch on off S2 High pressure switch SENSOR Temperature Sensor GL1 Green Lamp SOL1 Electronic drain DCB Digtal Control Board 120V 0V 50VA 480V 0V TRANSFORMER 460V 3PH 60Hz L2 F1 2A TH MC1 U1 V...

Страница 21: ...TH1 MANUAL MOTOR STARTER FOR REF COMP CP1 CIRCUIT PROTECTOR FOR CONTROL POWER S1 SWITCH ON OFF S2 HIGH PRESSURE SWITCH SENSOR TEMPERATURE SENSOR GL1 GREEN LAMP SOL1 ELECTRONIC DRAINVALVE 1 DCB2 DIGIT...

Страница 22: ...IGH PRESSURE SWITCH COMPRESSED AIR FLOW REFRIGERANT FLOW WETTED COMPRESSED AIR INLET DRYED COMPRESSED AIR OUTLET MOISTURE SEPARATOR INTEGRATED BRAZED PLATE HEAT EXCHANGER EXPANSIONVALVE CAPILLARY TUBE...

Страница 23: ...AIR FLOW REFRIGERANT FLOW WETTED COMPRESSED AIR INLET DRYED COMPRESSED AIR OUTLET MOISTURE SEPARATOR INTEGRATED BRAZED PLATE HEAT EXCHANGER 1 S MOISTURE SEPARATOR INTEGRATED BRAZED PLATE HEAT EXCHANG...

Страница 24: ...439991 1 14 Contactor Compressor 3242864 7439992 7439992 7439992 1 15 Contactor Fan Motor 3242863 7439993 7439993 7439993 1 16 Surpressor Spark Killer 7439994 7439994 7439994 7439994 1 17 Circuit Prot...

Страница 25: ...23 NOTES MCGUIRE AIR COMPRESSORS INC 1 888 229 9999 MCGUIRE AIR COMPRESSORS INC 1 888 229 9999...

Страница 26: ...24 NOTES MCGUIRE AIR COMPRESSORS INC 1 888 229 9999 MCGUIRE AIR COMPRESSORS INC 1 888 229 9999...

Страница 27: ...or the unexpired portion of the warranty applying to the original product The foregoing is the exclusive remedy of any buyer of the manufacturer s product The maximum damages liability of the manufact...

Страница 28: ...Improvements and research are continuous at SPX FLOW Inc Specifications may change without notice ISSUED 10 2018 Form No 7426448 Revision B COPYRIGHT 2018 SPX FLOW Inc HGEN Series Refrigerated Type Co...

Отзывы: