Operation and installation manual SOLIVIA 5.0 AP G3
LED STATUS
DISPLAY
MESSAGE
CAUSE
ELIMINATION
green: <off>
red: <off>
yellow: <on>
Error # 302
The device trips and
reverts to grid input mode
once the temperature has
dropped.
- Check the installation site (no direct
sunlight, air circulation).
green: <off>
red: <on>
yellow: <off>
Error # 506
Error # 508
Isolation resistance fault
on the DC side during
start-up phase (# 508) or
running phase (# 506).
- Check the isolation resistance on the DC
side of the PV modules.
green: <on>
red: <on>
yellow: <off>
Isolation start-
up warning
Isolation run-
ning warning
Isolation resistance fault
on the DC side during
start-up phase or running
phase.
- You must check the isolation resistance
on the DC side of the PV modules.
Solar inverter is still feeding!
green: <on>
red: <on>
yellow: <off>
PV+ groun-
ding fault
PV- grounding
fault
Connection PV+ (PV-)
to GND is interrupted or
wrong pole is connected
to GND.
- Check that the GND connection has been
made correctly and/or check the fuse in
the grounding path. Change the fuse if
necessary. The solar inverter remains in
feed-in operation.
green: <off>
red: <off>
yellow: <on>
Revision error
Versions of hard- and soft-
ware are not compatible.
- If the fault persists after the device has
been reset, please inform your service
technician.
green: <on>
red: <on>
yellow: <on>
Self test
ongoing
Initialization of solar inver-
ter on start-up.
The first time the solar inverter is started
up:
- Normal function with a PV cell voltage
of between 100 V and 150 V.
green: <flashes>
red: <off>
yellow: <off>
PV power too
low
Insufficient input power.
- Insufficient insolation (dawn/twilight).
- Check the PV cell voltage via the
display in the N menu.
green: <flashes>
red: <off>
yellow: <off>
PV voltage
too low
PV generator voltage bet-
ween 100 V and 150 V.
- Insufficient insolation.
- Check the PV cell voltage via the
display in the N menu.
green: <flashes>
red: <off>
yellow: <off>
Synchronize
to AC
Checks grid voltage and
grid frequency for grid
input mode.
- Normal function before input mode.
green: <on>
red: <off>
yellow: <flashes>
Varistor
warning
Internal varistor at the DC
input is defective.
- Although you can, in theory, carry on
using the solar inverter, the varistors
should be replaced at the earliest oppor
tunity. This will involve returning the
device.
Please follow the instructions above before contacting your service technician!
Содержание SOLIVIA 5.0 AP G3
Страница 1: ...Operation and installation manual for SOLIVIA 5 0 AP G3 5 0 AP...
Страница 2: ......
Страница 4: ...2 Operation and installation manual SOLIVIA 5 0 AP G3...
Страница 38: ...36 SOLIVIA 5 0 AP G3...
Страница 39: ...37 SOLIVIA 5 0 AP G3 Delta Energy Systems Germany GmbH Delta Energy Systems www solar inverter com...
Страница 40: ...38 SOLIVIA 5 0 AP G3...
Страница 42: ...40 SOLIVIA 5 0 AP G3 1 SOLIVIA 5 0 AP G3 AC 2 SOLIVIA 5 0 AP G3 9 18kg 5...
Страница 43: ...41 SOLIVIA 5 0 AP G3 3 12 IP65 4 MPP 4 1 PC...
Страница 44: ...42 SOLIVIA 5 0 AP G3 4 2 DC AC MPP MPP 150V 450V 540 VDC IP65 25 C 60 C RS485 EMC 4 6kVA...
Страница 45: ...43 SOLIVIA 5 0 AP G3 4 3 1 2 3 RS485 EIA485 4 5 LED 1 4 5 2 3...
Страница 46: ...44 SOLIVIA 5 0 AP G3 5 TAB 2000 9 6 6 1 LED IP65 III 6 2 10cm 50cm DC IP65 50 cm 10 cm 50 cm 10 cm Wall Wall...
Страница 47: ...45 SOLIVIA 5 0 AP G3 319 5 150 320 200 6 5 12 12 5 90 38 12 410 0 5 6 3 6 4 1 6mm 8 4 2 32 0kg 3 4 5...
Страница 53: ...51 SOLIVIA 5 0 AP G3 6 9 MPP DC DC DC DC DC A AC B C D 51 SOLIVIA 5 0 AP G3...
Страница 68: ...66 SOLIVIA 5 0 AP G3 10 10 1 400 220V 400 230 V VNB Z 1 Z 2 1 2 400 220 V 400 230 V 4 6kVA...
Страница 69: ...67 SOLIVIA 5 0 AP G3 400 220V 400 230 V VNB Z 1 Z 2 1 2 3 400 220 V 400 230 V 4 6kVA...
Страница 71: ...69 SOLIVIA 5 0 AP G3 DC 1 2 3 L1 N PE L2 N PE L3 N PE L1 N n PE L2 L3 Solivia 5 0...
Страница 73: ...71 SOLIVIA 5 0 AP G3 RJ45 8 RJ Registered Jack RS485 EIA485 DC AC TAB 2000 TAB 2000 2000 DSO...
Страница 74: ...72 SOLIVIA 5 0 AP G3...
Страница 75: ...73 SOLIVIA 5 0 AP G3 www solar inverter com Delta Energy Systems Germany GmbH Delta Energy Systems...
Страница 76: ...74 SOLIVIA 5 0 AP G3...
Страница 78: ...76 SOLIVIA 5 0 AP G3 1 SOLIVIA 5 0 AP G3 2 SOLIVIA 5 0 AP G3 9 18 5...
Страница 79: ...77 SOLIVIA 5 0 AP G3 3 12 IP65 4 4 1 4 2 MPP Tracking 150V 450V 540V IP65 25 C 60 C...
Страница 80: ...78 SOLIVIA 5 0 AP G3 4 3 1 2 3 RS485 EIA485 4 5 LED RS485 EMC 4 6 kVA 4 3 1 4 5 2 3...
Страница 81: ...79 SOLIVIA 5 0 AP G3 5 TAB 2000 9 6 6 1 LED IP65 6 2 10 50 Tyco IP65 50 cm 10 cm 50 cm 10 cm Wall Wall...
Страница 82: ...80 SOLIVIA 5 0 AP G3 319 5 150 320 200 6 5 12 12 5 90 38 12 410 0 5 6 3 6 4 1 6 4 8 2 32 0 3 4 5...
Страница 87: ...85 SOLIVIA 5 0 AP G3 5V 0R 0R TX_A RX_B GND Pin 7 Pin 6 100 150 Ohm 0 25W 2 RS485 EIA485 A B C D...
Страница 88: ...86 SOLIVIA 5 0 AP G3 6 9 1 2 3 Wieland 4 5 6 7 UPV 150V 8 S Setup 7 3 7 6 9...
Страница 103: ...101 SOLIVIA 5 0 AP G3 10 10 1 400 220 400 230 VNB Z 1 Z 2 1 2 400 220 400 230 4 6...
Страница 104: ...102 SOLIVIA 5 0 AP G3 VNB Z 1 Z 2 Z 3 400 220 400 230 400 220 400 230 4 6 1 2 3...
Страница 105: ...103 SOLIVIA 5 0 AP G3 10 2 3 3 Z 3 Z 3 3 3 B 32 A Solivia 5 0 B 32 A B 32 A kWh kWh Solivia 5 0 Solivia 5 0...
Страница 106: ...104 SOLIVIA 5 0 AP G3 1 2 3 L1 N PE L2 N PE L3 N PE L1 N n PE L2 L3 Solivia 5 0...
Страница 109: ...107 SOLIVIA 5 0 AP G3...
Страница 110: ...108 SOLIVIA 5 0 AP G3...
Страница 111: ...109 SOLIVIA 5 0 AP G3 www solar inverter com Delta Energy Systems Germany GmbH Delta Energy Systems...
Страница 112: ...110 SOLIVIA 5 0 AP G3...
Страница 115: ...113 SOLIVIA 5 0 AP G3 3 12 IP65 4 4 1 4 2 150V 450V 540V IP65 25 C 60 C...
Страница 116: ...114 SOLIVIA 5 0 AP G3 4 3 1 4 5 2 3 RS485 EMC 4 6 kVA 1 2 3 RS485 EIA485 4 5 LED...
Страница 117: ...115 SOLIVIA 5 0 AP G3 5 TAB 2000 9 6 6 1 LED IP65 6 2 10cm 50cm Tyco IP65 50 cm 10 cm 50 cm 10 cm Wall Wall...
Страница 118: ...116 SOLIVIA 5 0 AP G3 319 5 150 320 200 6 5 12 12 5 90 38 12 410 0 5 6 3 6 4 1 6 4 8 2 32 0 3 4 5...
Страница 123: ...121 SOLIVIA 5 0 AP G3 6 9 121 SOLIVIA 5 0 AP G3...
Страница 138: ...136 SOLIVIA 5 0 AP G3 10 10 1 Z 1 Z 2...
Страница 139: ...137 SOLIVIA 5 0 AP G3 Z 1 Z 2 Z 3...
Страница 140: ...138 SOLIVIA 5 0 AP G3 10 2 3 3 Z 3 Z 3 3 3 kWh kWh...
Страница 141: ...139 SOLIVIA 5 0 AP G3 1 2 3 L1 N PE L2 N PE L3 N PE L1 N n PE L2 L3...
Страница 143: ...141 SOLIVIA 5 0 AP G3 RJ45 RJ RS485 ELA485 TAB 2000 TAB 2000 TAB 2000 DSO...
Страница 145: ...143...
Страница 146: ...144...
Страница 147: ......