background image

Содержание SOLIVIA 2.5 AP G3 TR

Страница 1: ...SOLIVIA 2 5 AP G3 TR Operation and installation manual ...

Страница 2: ......

Страница 3: ...stems Germany GmbH All rights reserved This manual accompanies our equipment for use by the end users The technical instructions and illustrations contained in this manual are to be treated as confidential and no part may be reproduced without the prior written permission of Delta Energy Systems Service engineers and end users may not divulge the information con tained herein or use this manual fo...

Страница 4: ...2 Operation and installation manual SOLIVIA 2 5 AP G3 TR ...

Страница 5: ... 5 Ambient temperature 12 7 6 Grid connection 12 7 7 Connection of PV modules 13 7 7 1 Output power over PV voltage 14 7 7 2 Output power over AC voltage 15 7 7 3 Efficiency 15 7 8 Interface connection RS485 EIA485 16 7 9 Electrical connection and operational start up 18 7 10 Setup settings 19 7 11 LED operation and fault display 21 8 Operating concept 21 8 1 The display 21 8 2 Navigation in the d...

Страница 6: ... 2 5 AP G3 TR 9 Diagnostics and data evaluation 31 9 1 Malfunction rectification 31 9 2 Display messages 32 10 Technical data 34 11 Appendix 36 11 1 Connection examples 36 11 2 Overview of connection diagrams 38 12 Glossary 40 13 Certificates 43 ...

Страница 7: ...on the installation and operation of the solar inverter Take note of and follow the information on safe use see 3 General safety instruc tions page 6 The installer and the operator must have access to this manual and must be familiar with the safety instructions 1 2 Warnings and symbols The following section explains the warnings and symbols used in this manual Danger Indicates a dangerous situati...

Страница 8: ...specified ambient conditions The solar inverter contains monitoring devices including an anti islanding device The solar inverter may only be used for the specified intended purpose 3 General safety instructions Danger Danger of death from hazardous voltage Hazardous voltage is applied to the solar power inverter during op eration Hazardous voltage is still present 5 minutes after all power source...

Страница 9: ...rrent value see 10 Technical data page 34 The ground wire MUST be connected before the start of operation Only equipment in accordance with SELV EN 60950 may be connected to the RS485 interfaces Do not remove any warning signs that the manufacturer has installed on the solar inverter In order for IP65 protection to be granted all used and unused connections must be sufficiently sealed 4 Scope of d...

Страница 10: ... ensure that the maximum open circuit voltage of 540 VDC is never exceeded Please note that the maximum open circuit voltage will occur at the lowest temperatures anticipated You will find more detailed information about temperature dependency in the data sheet of the PV modules The device s power consumption is kept to a minimum The high quality aluminum casing corresponds to protection class IP6...

Страница 11: ...ation agency guarantees secure disconnection in case of circuit isolation or interruptions in power supply and avoids isolated operation The disconnection equipment allows for automatic isolation for in plant generation sys tems of nominal power 4 6 kVA with single phase parallel feed in through the solar inverter into the grid 5 3 Equipment overview 1 Connections for PV modules 2 Grid connection ...

Страница 12: ...nverter 7 Installation of equipment 7 1 Installation location Install the device on a non flammable support base Avoid installation on resonating bodies light construction walls etc Installation is possible both indoors and in protected outdoor areas An increased ambient temperature can reduce the efficiency of the PV system The inverter may produce moderate noise during operation Please select in...

Страница 13: ...while in operation To avoid the casing of the solar inverter becoming soiled it should be cleaned periodically User serviceable parts are not contained in the device Under no circumstances should the solar inverter be opened 7 4 Installation You should utilize the delivered mounting plate for problem free installation of the solar inverter Installation to the wall should be implemented with the pr...

Страница 14: ...Grid connection The grid AC output is connected over a Wieland RST25i3S AC connector You can find the correct allocation on the screw type terminal connection of the connector The solar inverter must be connected to the grid over a three core line L N PE The con nected AC line must be switched potential free before the disconnection or the insertion of the AC connector The connection to the Wielan...

Страница 15: ...C positive pole on the connector lower row The connectors are coded to prevent you from acci dentally plugging them into the wrong terminal Please ensure the following at all times That there is never any risk of anyone coming into contact with the solar inverter connection terminals due to the risk of dangerous voltages across them That under no circumstances are the PV modules to be disconnected...

Страница 16: ...kit Grounding Set A Solar EOE99000275 The grounding connection is monitored and should be configured in the Setup menu see 8 3 7 Submenu S Setup page 28 Alternatively it is possible to turn off the insulation and grounding monitoring ISO GND OFF Required cable coupler types for DC cable connection to inverter CABLE COUPLER POLARITY WIRE SIZE 2 5 MM2 AWG 14 WIRE SIZE 4 0 MM2 6 0 MM AWG 12 10 FEMALE...

Страница 17: ...500 W 2700 W 2900 W 3100 W 3300 W 3500 W 3700 W 190 VAC 210 VAC 230 VAC 250 VAC 270 VAC 7 7 3 Efficiency The best efficiency of the solar inverter is obtained at input voltages 250 V 84 86 88 90 92 94 96 0 W 400 W 800 W 1200 W 1600 W 2000 W 2400 W 2500 W 150 V 2500 W 250 V 2500 W 350 V 2500 W 450 V ...

Страница 18: ...ctor supplier HARTING Deutschland GmbH Co KG P O 2451 32381 Minden Germany www harting com Order designation 09 45 145 1510 Cable Manager Blue IP67 Push Pull Data Plug 09 45 145 1500 Cable Manager White IP67 Push Pull Data Plug 230 V House connection line RS485 EIA485 Connection Datalogger RS485 EIA485 terminating resistor 8 1 Pin 1 Reserved 2 Reserved 3 Reserved 4 GND RS485 5 Reserved 6 RX_B RS48...

Страница 19: ... connected in series and the total length of the data line measures 2 m or more the following option is available for terminating the RS485 EIA485 interface Power controller Operating and system control MPP Tracker Booster Isolation DC Bus Solar inverter DC DC DC DC String A String B String C String D AC Public grid Anti islanding protection Communication ...

Страница 20: ...nsure correct polarity 3 AC connection Please install the Wieland AC mating connector to the AC output cable and then put the AC connector to the solar inverter Please make sure that the sleeve nut is properly fixed and tighten 4 Before switching on the power check all feeders and connections one last time 5 Close the DC disconnector 6 Close the circuit breaker on the AC output side 7 In case of s...

Страница 21: ...ection To unlock the enter keys you need to switch off the DC voltage and then switch it on again see 9 2 Display messages page 32 1 In certain states in Australia power limitation is required With power limitation the output AC power of SOLIVIA 2 5 AP G3 TR will be as followed Power limitation setting AU PL Max power 2490 W To activate power limitation please select dedicated country Australia PL...

Страница 22: ...try by following the steps as listed below 1 Please click ESC for few seconds to get the key information 2 Provide the key code to the Solar Support Team at support australia solar inverter com or support india solar inverter com to get the PIN code valid for one use only 3 Once you get the PIN code you need to press ESC 4 Then you will be asked to insert the PIN code and to confirm it twice 5 Aft...

Страница 23: ...red on yellow on Initialization Input voltages UPV 100 V to 150 V self test ongoing green flashes red off yellow off Input and grid monitoring Starting conditions are tested green on red off yellow off Feed in operation Normal operational state UPV 150 V to 450 V green off red on off yellow on off Equipment fault Internal or external fault interrupted feed See also 9 2 Display messages page 32 gre...

Страница 24: ... in automatic operation the display lighting is switched on If no key is pressed within 30 seconds the display lighting automatically goes out The setup menu enables selection between continuous or automatic lighting Through pressing the ENTER key the display lighting is switched on again 8 3 Main menu The main menu consists of 7 menu items which are subdivided into submenus Menu N Now Menu D Day ...

Страница 25: ...tatistic Menu T Total statistic Menu S Setup inverter Down Down Down Down Down Down Up Up Up Up Up Up Down to 2 1 Up to 1 2 Submenu N Now Submenu D Day Submenu W Week Submenu M Month Submenu Y Year Submenu T Total Submenu S Setup ESC ESC ESC ESC ESC ESC ESC ENTER ENTER ENTER ENTER ENTER ENTER ENTER Remarks ESC in main menu jumps to first entry of corresponding sub menu ...

Страница 26: ...WD DD MM YYYY Down Down Down Down Down Down Down Up Up Up Up Up Up Up Down to 2 1 Up to 1 2 Submenu N Now ESC ESC ESC ESC ESC ESC ESC Remarks ESC in main menu N jumps to first entry of sub menu N ESC ENTER Display of the active output power Display of the active output voltage Display of the active output current Display of the active mains frequency Display of the active PV cell voltage Display o...

Страница 27: ...wn Up Up Up Up Up Up Up Down to 2 1 Up to 1 2 Submenu D Day ESC ESC ESC ESC ESC ESC ESC Remarks ESC in main menu D jumps to first entry of sub menu D ESC ENTER D AC Freq Min Value Hz ESC Down Up Display of the daily energy gain Display of the daily revenue Display of the daily maximum output power Display of the daily max output voltage Display of the daily min output voltage Display of the daily ...

Страница 28: ...ain menu M Month statistic M Energy Value kWh M AC Revenue Value AUD M Runtime Value h Down Down Up Up Down to 2 1 Up to 1 2 Submenu M Month ESC ESC Remarks ESC in main menu M jumps to first entry of sub menu M ESC ENTER Display of the monthly energy gain Display of the monthly revenue Display of the monthly operating time of the solar inverter 8 3 5 Submenu Y Year This menu item displays the aver...

Страница 29: ...ue kOhm T Runtime Value Min Down Down Down Down Down Down Down Up Up Up Up Up Up Down to 2 1 Up to 1 2 Submenu T Total ESC ESC ESC ESC ESC ESC ESC Remarks ESC in main menu T jumps to first entry of sub menu T ESC ENTER Up Display of the total energy gain Display of the total revenue Display of the max PV cell voltage Display of the max PV cell current Display of the max PV cell power Display of th...

Страница 30: ... ESC ESC ESC ESC ENTER Up S Time HH MM SS Down ESC Up S Date WD DD MM YYYY Down ESC Up S Firmware Down ESC Up Adjustment of the firmware Adjustment of the brightness of the LCD display between 0 9 Adjustment of the LCD background lighting Selection of the start menu on restart of the device Entry of feed in remuneration in AUD per kWh Input of the ID number of the solar inverter Adjustment of the ...

Страница 31: ...nu within the submenu S Setup Submenu Setup Solar ISO GND S Solar ISO GND ISO ON Warning S Solar ISO GND ISO ON Failure S Solar ISO GND ISO GND OFF S Solar ISO GND PV grounded S Solar ISO GND PV grounded Down Down Down Down Up Up Up Up Down to 5 6 Up to 6 5 ESC ESC ESC ESC ESC ENTER Use old setting ENTER ENTER ENTER ENTER ENTER Use new value ...

Страница 32: ...untry settings Undervoltage x V x xx s S Country settings Overvoltage x V xmin S Country settings Critical overvoltage x V x xx s S Country settings Low frequency xx xx Hz x xx s S Country settings High frequency x xx Hz x xx s S Country settings Islanding Active Not active Down Down Down Down Down Down Down Up Up Up Up Up Up Up Down to 5 6 Up to 6 5 ESC ESC ESC ESC ESC ESC ESC ENTER S Country set...

Страница 33: ...tion 9 1 Malfunction rectification The solar inverter is provided with an automatic diagnostics system which indepen dently identifies certain faults and which can make them visible on the display Troubleshooting in the field In principle it is always worth attempting a reset by reinitializing the solar inverter whenever an error message appears on the display To reset the device proceed as follow...

Страница 34: ... grid automatic circuit breaker green off red off yellow on AC relay failure One of the anti islanding protection output relays is faulty defective The solar inverter is defective Return the device green flashes red off yellow off Calibration ongoing Check internal settings Normal function before input mode green off red off yellow on DC injection failure DC component of input side alternating cur...

Страница 35: ...ff yellow off PV power too low Insufficient input power Insufficient insolation dawn twi light Check the PV cell voltage via the display in the N menu green flashes red off yellow off PV voltage too low PV generator voltage bet ween 100 V and 150 V Insufficient insolation Check the PV cell voltage via the display in the N menu green flashes red off yellow off Synchronize to AC Checks grid voltage ...

Страница 36: ...ominal power Total harmonic distortion THD 3 nominal power GENERAL SPECIFICATION AUSTRALIA INDIA Model name SOLIVIA 2 5 AP G3 TR Part number Delta EOE45010272 Max efficiency 96 Efficiency EU 94 8 Operating temperature 25 70 C Storage temperature 25 80 C Humidity 0 98 Max operating altitude 2000 m above sea level 1 The maximum AC power value indicates the power an inverter might be able to deliver ...

Страница 37: ...3 LEDs 2 line LCD STANDARDS DIRECTIVES AUSTRALIA INDIA Protection degree IP65 Safety class I Configurable trip parameters Yes Insulation monitoring Yes Overload behavior Current limitation power limitation Anti islanding protection Grid regulation AS 4777 2 AS 4777 3 IEC 60255 5 VDE 0126 1 1 EMC AS 4777 1 AS 4777 2 AS 4777 3 EN 61000 6 2 IEC EN 61000 6 3 IEC EN 61000 6 2 IEC EN 61000 6 3 Safety AS...

Страница 38: ...ark A meter can also be employed which registers both energy directions separately 400 220 V 400 230 V Consumer equipment of the customer Photovoltaic generator with power inverter max 4 6 kVA Switching equipment Electric circuit distributor Anti islanding protection with voltage and frequency monitoring as well as network impedance measurement Short circuit protection Overload protection Individu...

Страница 39: ...f the customer system Consumer equipment of the customer Photovoltaic generator with power inverter max 4 6 kVA Switching equipment Electric circuit distributor Anti islanding protection with voltage and frequency monitoring as well as network impedance measurement Short circuit protection Overload protection Individual in plant generation system in parallel operation without isolated operation po...

Страница 40: ...ouse connection box Selective main line circuit breaker House connection line Consumer equipment Automatic circuit breaker type B 25 A PV generator PV generator Solivia 2 5 DC disconnector Automatic circuit breaker type B 25 A PV generator DC disconnector Automatic circuit breaker type B 25 A PV generator kWh kWh Customer Meter for power feed in Meter for power consumption Solivia 2 5 Solivia 2 5 ...

Страница 41: ...EN 39 Operation and installation manual SOLIVIA 2 5 AP G3 TR DC disconnector 1 2 3 PV generator L1 N PE L2 N PE L3 N PE Fuse L1 N n PE L2 L3 Solivia 2 5 ...

Страница 42: ...EMC concerns the technical and legal basics of the mutual influencing of electrical devices through electromagnetic fields caused by them in electrical engineering Initialization Under initialization cf English to initialize is understood the part of the loading process of a program in which the storage space required for the execution e g variable code buffers for the program is reserved and is f...

Страница 43: ...ing wire protective grounding device soil grounding or PE Eng lish protective earth Photovoltaics abbr PV The conversion of PV energy into electrical energy The name is composed of the component parts Photos the Greek word for light and Volta after Alessandro Volta a pioneer in electrical research Potential isolation No conductive connection between two component parts Power dissipation Power diss...

Страница 44: ... Designates a group of electrical PV modules switched in series String solar inverter solar inverter concept The PV generator is divided up into individual strings which feed into the grid over their own string solar inverters in each case In this way the installation is considerably facilitated and the gain decrease which can arise from the installation or from different shading conditions of the...

Страница 45: ... batch or serial number if available Brand Name Delta Model Number SOLIVIA2 5APG3 Description Solar Inverter Compliance with Radiocommunications Electromagnetic Compatibility Standard 2008 The above mentioned product complies with the requirements of the Radiocommunications Electromagnetic Compatibility Standard 2008 Evidence of compliance is demonstrated by test reports to the following applicabl...

Страница 46: ...44 ...

Страница 47: ......

Страница 48: ... Fax 61 3 9544 0606 Support Email support australia solar inverter com Delta Energy Systems India Pvt Ltd Ozone Manay Tech Park A Block 3rd Floor Survey No 56 18 55 9 Hosur Road Hongasandra Village Bangalore 560068 Karnataka Phone 9180 67164711 Phone 9180 67164777 Support Email support india solar inverter com 25 October 2012 www solar inverter com ...

Отзывы: