FAULT
Message
Possible cause
Action
HW DC
Injection
1. Utility waveform is
abnormal
2. Detection circuit
malfunction
1. Check the utility waveform.
Grid connection of inverter need to be
far away from non-linear load if necessary
2. Check the detection circuit inside the
inverter
Temperature
High
1. The ambient is over 60
℃
(The installation is abnormal)
2. Detection circuit malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
Temperature
Low
1. Ambient temperature is
<-30
℃
2. Detection circuit
malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter (RTM1, RTB1, RTG1 and RTH1)
HW NTC1
Fail
1. Ambient temperature
>90
℃
or <-30
℃
2. Detection circuit
malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter (RTM1)
HW NTC2
Fail
1. Ambient temperature
>90
℃
or <-30
℃
2. Detection circuit
malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter (RTB1)
HW NTC3
Fail
1. Ambient temperature
>90
℃
or <-30
℃
2. Detection circuit
malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter (RTG1)
HW NTC4
Fail
1. Ambient temperature
>90
℃
or <-30
℃
2. Detection circuit
malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter (RTH1)
HW DSP
ADC1
1. Insufficient input power
2. Auxiliary power circuitry
malfunction
3. Detection circuit
malfunction
1. Check the input voltage, must >150Vdc
2. Check the auxiliary circuitry inside the
inverter
3. Check the detection circuit inside the
inverter
HW DSP
ADC2
1. Insufficient input power
2. Auxiliary power circuitry
malfunction
3. Detection circuit
malfunction
1. Check the input voltage, must >150Vdc
2. Check the auxiliary circuitry inside the
inverter
3. Check the detection circuit inside the
inverter
42
Error message and Trouble Shooting
Содержание RPI Series
Страница 2: ......
Страница 52: ......
Страница 53: ...RPI M15A M20A The power behind competitiveness www deltaww com English 1 53 103...
Страница 55: ...55...
Страница 57: ...2 1 RPI M15A M20A 2 1 2 2 1 2 2 2 1 2 2 57...
Страница 58: ...2 2 RPI M15A RPI M20A 1 1 pcs 1 pcs 1 pcs 1 pcs RPI 2 3 AC AC 4 5 DC 4 sets DC 2 1 58...
Страница 59: ...2 3 2 3 2 3 59...
Страница 61: ...PV array IEC 61730 Class A 3 AC DC 1 12 M6 3 3 2 3 2 M6 3 4 3 1 61...
Страница 62: ...90 Not Recommended Not Recommended Keep 30 cm from floor and water if installed this way 3 2 62...
Страница 63: ...M6 Screw 6 Wall M6 Screw 6 3 3 3 4 M6 Screw 63...
Страница 64: ...3 5 25 60 40 30 cm 20 cm 50 cm 30 cm 30 cm 3 5 64...
Страница 89: ...6 1 6 1 PV Inverter 6 AC DC 6 1 89...
Страница 90: ...6 2 6 3 6 2 6 3 6 3 4 90...
Страница 97: ...8 AC DC OFF voltmeter AC DC AC DC RS 485 97...
Страница 101: ...10 NO 3 Fans 8 Kgf cm 0 8N m 1 Air inlet 8 Kgf cm 0 8N m 2 Fan panel 8 Kgf cm 0 8N m 10 1 1 101...
Страница 103: ...RPI M15A M20A The power behind competitiveness www deltaww com English 1 53 103...
Страница 105: ...105...
Страница 107: ...2 1 RPI M15A M20A 2 1 2 2 1 2 2 2 1 2 2 107...
Страница 108: ...2 2 RPI M15A RPI M20A 1 1 pcs 1 pcs 1 pcs 1 pcs RPI 2 3 AC AC 4 5 DC 4 sets DC 2 1 108...
Страница 109: ...2 3 2 3 2 3 109...
Страница 111: ...PV array IEC 61730 Class A 3 AC DC 1 12 M6 3 3 2 3 2 M6 3 4 3 1 111...
Страница 112: ...90 Not Recommended Not Recommended Keep 30 cm from floor and water if installed this way 3 2 112...
Страница 113: ...M6 Screw 6 Wall M6 Screw 6 3 3 3 4 M6 Screw 113...
Страница 114: ...3 5 25 60 40 30 cm 20 cm 50 cm 30 cm 30 cm 3 5 114...
Страница 139: ...6 1 6 1 PV Inverter 6 AC DC 6 1 139...
Страница 140: ...6 2 6 3 6 2 6 3 6 3 4 140...
Страница 147: ...8 AC DC OFF voltmeter AC DC AC DC RS 485 147...
Страница 151: ...10 NO 3 Fans 8 Kgf cm 0 8N m 1 Air inlet 8 Kgf cm 0 8N m 2 Fan panel 8 Kgf cm 0 8N m 10 1 1 151...
Страница 153: ......
Страница 154: ...Version 05190319 5013242902...