ERROR
Message
Possible cause
Action
Solar2
High
1. Actual Solar2 voltage is over
1000Vdc
2. Detection circuit malfunction
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2. Check the detection circuit inside the
inverter
Insulation
1. PV array insulation fault
2. Large PV array capacitance
between Plus to Ground or
Minus to Ground or both.
3. Detection circuit malfunction
1. Check the insulation of Solar inputs
2. Check the capacitance, dry PV panel
if necessary
3. Check the detection circuit inside the
inverter
Table 7-1 Error Message
Warning
Message
Possible cause
Action
Solar1
Low
1. Actual Solar1 voltage is under
the limit
2. Some devices were damaged
inside the inverter if the actual
Solar1 voltage is close to "0"
3. Detection circuit malfunction
1. Check the Solar1 voltage connection
to the inverter terminal
2. Check all switching devices in boost1
3. Check the detection circuit inside the
inverter
Solar2
Low
1. Actual Solar2 voltage is under
the limit
2. Some devices were damaged
inside the inverter if the actual
Solar2 voltage is close to "0"
3. Detection circuit malfunction
1. Check the Solar2 voltage connection
to the inverter terminal
2. Check all switching devices in boost2
3. Check the detection circuit inside the
inverter
HW FAN
1. One or more fans are locked
2. One or more fans are defective
3. One ore more fans are
disconnected
4. Detection circuit malfunction
1. Remove the object that stuck in the
fan(s)
2. Replace the defective fan(s)
3. Check the connections of all fans
4. Check the detection circuit inside the
inverter
SPD Fail
1. Inverter was struck by lighting.
2. One or more SPD are defective
3. One or more SPD are
disconnected
4. Detection circuit malfunction
1. Check inverter’s status
2. Replace the defective SPD
3. Check the connections of SPDs
4. Check the detection circuit inside the
inverter
Table 7-2 Warning Message
41
Error message and Trouble Shooting
Содержание RPI Series
Страница 2: ......
Страница 52: ......
Страница 53: ...RPI M15A M20A The power behind competitiveness www deltaww com English 1 53 103...
Страница 55: ...55...
Страница 57: ...2 1 RPI M15A M20A 2 1 2 2 1 2 2 2 1 2 2 57...
Страница 58: ...2 2 RPI M15A RPI M20A 1 1 pcs 1 pcs 1 pcs 1 pcs RPI 2 3 AC AC 4 5 DC 4 sets DC 2 1 58...
Страница 59: ...2 3 2 3 2 3 59...
Страница 61: ...PV array IEC 61730 Class A 3 AC DC 1 12 M6 3 3 2 3 2 M6 3 4 3 1 61...
Страница 62: ...90 Not Recommended Not Recommended Keep 30 cm from floor and water if installed this way 3 2 62...
Страница 63: ...M6 Screw 6 Wall M6 Screw 6 3 3 3 4 M6 Screw 63...
Страница 64: ...3 5 25 60 40 30 cm 20 cm 50 cm 30 cm 30 cm 3 5 64...
Страница 89: ...6 1 6 1 PV Inverter 6 AC DC 6 1 89...
Страница 90: ...6 2 6 3 6 2 6 3 6 3 4 90...
Страница 97: ...8 AC DC OFF voltmeter AC DC AC DC RS 485 97...
Страница 101: ...10 NO 3 Fans 8 Kgf cm 0 8N m 1 Air inlet 8 Kgf cm 0 8N m 2 Fan panel 8 Kgf cm 0 8N m 10 1 1 101...
Страница 103: ...RPI M15A M20A The power behind competitiveness www deltaww com English 1 53 103...
Страница 105: ...105...
Страница 107: ...2 1 RPI M15A M20A 2 1 2 2 1 2 2 2 1 2 2 107...
Страница 108: ...2 2 RPI M15A RPI M20A 1 1 pcs 1 pcs 1 pcs 1 pcs RPI 2 3 AC AC 4 5 DC 4 sets DC 2 1 108...
Страница 109: ...2 3 2 3 2 3 109...
Страница 111: ...PV array IEC 61730 Class A 3 AC DC 1 12 M6 3 3 2 3 2 M6 3 4 3 1 111...
Страница 112: ...90 Not Recommended Not Recommended Keep 30 cm from floor and water if installed this way 3 2 112...
Страница 113: ...M6 Screw 6 Wall M6 Screw 6 3 3 3 4 M6 Screw 113...
Страница 114: ...3 5 25 60 40 30 cm 20 cm 50 cm 30 cm 30 cm 3 5 114...
Страница 139: ...6 1 6 1 PV Inverter 6 AC DC 6 1 139...
Страница 140: ...6 2 6 3 6 2 6 3 6 3 4 140...
Страница 147: ...8 AC DC OFF voltmeter AC DC AC DC RS 485 147...
Страница 151: ...10 NO 3 Fans 8 Kgf cm 0 8N m 1 Air inlet 8 Kgf cm 0 8N m 2 Fan panel 8 Kgf cm 0 8N m 10 1 1 151...
Страница 153: ......
Страница 154: ...Version 05190319 5013242902...