67
Installation and Operation Manual for RPI M50A
8 Settings
67
Installation and Operation Manual for RPI M50A
8.9 EPO (External Power Off)
Overview
With this function you can set the type of contact for the EPO function (normally open or normally closed).
Accessing the menu
Main menu > Install Settings > EPO
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1.
When the default information is displayed, press any button to open the
main menu. Otherwise, repeatedly press the button
ESC
until the main
menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the buttons
and
to select
Install Settings
.
To confi rm your selection, press the button
ENT
.
3.
The menu is protected by password 5555. Use the buttons
and
to set each digit.
To confi rm a digit, press the button
ENT
.
Grid Settings
DC Injection
Dry Contact
RCMU: ON
EPO: Normal Close
4.
Use the buttons
and
to select
EPO
. The current setting is
displayed behind the menu entry.
5.
To start editing the parameter value, press the button
ENT
.
6.
To change the parameter value, use the buttons
and
.
To confi rm your selection, press the button
ENT
To cancel the action, press the button
ESC
.
Confi gurable Parameters
Parameter
Description
Value range
EPO
Sets the type of contact for the relais (normally
closed or normally open).
Normal Open
|
Normal Close
Default setting:
Normal Close
Содержание RPI M50A_120
Страница 1: ...Installation and Operation Manual RPI M50A_120 RPI M50A_122 Europe...
Страница 9: ...9 Installation and Operation Manual for RPI M50A 3 Intended use...
Страница 107: ......