Step 9: Test Feedback Device
deltamotion.com
19
Verify Feedback
1.
In the
Axis Status Registers
pane, on the
All
tab, expand
the
Feedback
section.
For secondary inputs, expand
the
Pressure/Force/Accel
Feedback
section.
2.
Depending on your feedback type, look at the
Counts
,
Volts
or
Current
register. It may be changing slightly.
3.
Use the Direct Output command to move the axis back and forth
(as described in the
Test an Actuator
section).
4.
As the axis moves, look for a corresponding change in the
Counts
,
Volts
or
Current
. If it does not change smoothly, recheck the
wiring, verify that the parameters on the
Setup
tab are correct,
and check for smoothly changing
Counts
,
Volts
or
Current
again.
5.
Save the project and update Flash.