5. OPERATION
5-1 POWER ON/OFF INVERTER
Power on Inverter
Switch on the AC input breaker on rear control panel, and the load will be energized.
When the AC input is normal, press the inverter “ON” button on front control panel for 3
seconds.
When the AC input fails, press the “ON” button for more than 3 seconds to turn on inverter
from batteries.
The UPS starts diagnostic test and shows the results on the back lit LCD display as shown
below.
DIAGNOSIS MODE
AC START
BATTERY START
D IAG N O STIC M O D E
FR EQ O U T= XXH Z
DIAGNOSTIC MODE
FREQ OUT=XXHZ
DIAGNOSTIC MODE
INPUT XXXV/XXHZ
DIAGNOSTIC MODE
RECTIFIER OK
DIAGNOSTIC MODE
BATTERY OK
DIAGNOSTIC MODE
DC BUS OK
DIAGNOSTIC MODE
TESTING INVERTER
ON BATTERY
LOAD=XXX% X.XXKW
.
D IAG N O STIC M O D E
IN PU T XXXV/XXH Z
D IAG N O STIC M O D E
R EC TIFIER O K
D IAG N O STIC M O D E
BATTER Y O K
13
D IAG N O STIC M O D E
D C BU S O K
D IAG N O STIC M O D E
TESTIN G IN VE R TER
O N LIN E M O D E
LO AD= XXX % X . XXKW
.
D IAG N O STIC M O D E
C H AR G ER O K