background image

Delta MCS-600 Power Shelf

 

Installation, Operations and   

Maintenance Manual 

 

 

 

REV.: 03 

10-3 

Customer Specification Confidential

 

--- T --- 

TB Terminal 

Block 

THD 

Total Harmonic Distortion 

--- U --- 

UL Underwriters 

Laboratory 

--- V --- 

V Volt 

VAC Volts 

AC 

VDC Volts 

DC 

--- W --- 

W Watt 

--- X --- 

--- Y --- 

--- Z --- 

 

 

Содержание MCS-600 Series

Страница 1: ...www deltaww com DELTA MCS 600 Series Power System Installation Operation and Maintenance Manual...

Страница 2: ...Delta MCS 600 Series Power System Installation Operations Maintenance Manual DELTA ELECTRONICS INC...

Страница 3: ...Specifications 3 1 3 3 Operation and Adjustment 3 4 3 4 System Alarm 3 5 3 5 PSU Block Diagram 3 5 3 6 PSU Operating Principle 3 5 4 Alarm Control Unit 4 1 4 1 Description 4 1 4 2 Specifications 4 1 5...

Страница 4: ...arms and Troubleshooting 8 1 8 1 AC Fail Voltage Alarm Description 8 1 8 2 High Voltage Shutdown Alarm 8 1 8 3 High Voltage Alarm Description 8 1 8 4 Low Voltage Alarm 8 2 8 5 Low Voltage Disconnect A...

Страница 5: ...ntial Table of Contents Figure 4 Breaker Position A 6 Figure 5 Battery and Load Cable Connection Terminal A 7 Figure 5 1 A 8 Figure 6 Alarm Relay Output Position A 9 Figure 7 Power Shelf Rear View A 1...

Страница 6: ......

Страница 7: ...on or maintenance craftsperson of a potential hazard to either the equipment or the craftsperson if the warning is not followed 1 2 Safety Notice Delta Energy Systems is not liable for any hazards inc...

Страница 8: ......

Страница 9: ...owser The ALU also provides automatic derating of the output power over the whole operating line voltages Figure 1 shows different functional blocks of the system 2 2 Product Main Features The Power S...

Страница 10: ...system input specifications Table 1 System Input Specifications Specification Value Nominal range 90 275 VAC Operational range 175 275 VAC Frequency 45 65 Hz Power Factor 0 99 THD 5 Efficiency 90 2 3...

Страница 11: ...USE ALM AC Fail AC FAIL 2 3 3 4 Mechanical Data Table 3 displays the system mechanical data Table 3 System Mechanical Data Dimension Value Height 5 22 in 132 6mm Depth 12 in 304 4mm Width 19 in 483mm...

Страница 12: ......

Страница 13: ...ding uninterrupted service The rectifier unit has an active power factor correction of greater than 0 99 for maximum AC utilization Each module is equipped with an AC switch located at the front of th...

Страница 14: ...Voltage Recovery Time 1 ms to 1 Rated Output Voltage Protection Fuse 3 2 1 3 Protection Table 7 displays the protection specifications Table 7 Protection Specifications Condition Response High Output...

Страница 15: ...on Conforms to EN 61000 3 3 EN 60555 3 Electrostatic discharge Conforms to EN 61000 4 2 IEC 1000 4 2 IEC 801 2 Level 4 Radiated susceptibility Conforms to IEC 1000 4 3 IEC 801 3 Level 3 Electrical fas...

Страница 16: ...ustment Verify the required float voltage setting per battery manufacturer specification If the factory setting differs from the battery manufacturer recommended setting the ALU float voltage paramete...

Страница 17: ...panel The rectifier fail alarm signal is sent to the ALU which processes the alarm closes the RFA alarm contacts and lights the alarm LEDs 3 5 PSU Block Diagram Refer to Figure 8 3 6 PSU Operating Pri...

Страница 18: ......

Страница 19: ...he ALU automatically derates the system output current according to the following table Table 12 Voltage Ranges Input Voltage Range Output 90 120 VAC 50 121 175 VAC 70 176 275 VAC 100 The module is ho...

Страница 20: ...D1 Green FL System Float State LED2 Yellow EQU System Equalize State LED3 Red HV DC High Voltage Alarm Minor LED4 Red LV DC Low Voltage Alarm Minor LED5 Yellow MIN System Minor Alarm LED6 Red MAJ Syst...

Страница 21: ...the DC output voltage is lower than the parameter setting AC Fail The alarm condition exists when the AC voltage is absent LVDS The alarm condition exists when the DC output voltage is lower than the...

Страница 22: ...0 000 ft Weight 4 4 lbs 2Kg ESD IEC 1000 4 2 Contact 4KV Air 8KV 4 2 8 Remote monitoring and control The ALU provide the flowing remote monitoring methods 1 Use RS232 Interface 2 Use Internet Web serv...

Страница 23: ...connects the batteries from the system bus 5 3 Battery Connections The battery connections which are behind the distribution module should be made through the breaker BAT for battery positive and BAT...

Страница 24: ......

Страница 25: ...s isolation 2 Loosen the fixed thumbscrew on the rectifier and pull the rectifier out 3 Loosen the fixed thumbscrew on the ALU panel and pull the ALU out 4 Reverse the procedure to install the rectifi...

Страница 26: ...Description ACF AC Fail MAJ Major HVSD High Voltage Shutdown HV High Voltage Alarm LV Low Voltage Alarm LVD Low Voltage Disconnect FA Fuse Alarm MIN Minor 2 Each alarm connection is provided with a n...

Страница 27: ...arm and status conditions 7 3 Basic Functional Verification After system start up basic functional verification should proceed as follows 1 Check the ALU status and alarm LEDs 2 Compare the rectifier...

Страница 28: ......

Страница 29: ...serve batteries When the DC voltage falls below the HVSD threshold voltage and push the HVSD RST Button then the system recovers The ALU extinguishes the HVSD LED returns the rectifiers to service and...

Страница 30: ...nsation voltage decreases the float voltage below the LV threshold during hot temperature operation During this alarm condition the system continues to operate 8 5 Low Voltage Disconnect Alarm 8 5 1 D...

Страница 31: ...fire 8 7 Alarm Unit Fail 8 7 1 Description During an ALU fail condition the ALU fail and status LEDs are extinguished and all alarm contacts open During an ALU failure the rectifiers status changes f...

Страница 32: ......

Страница 33: ...distribution module the ALU and the rectifiers If necessary use a gentle detergent to clean Warning Do not use a spray cleanser to clean the equipment Using a spray cleanser directly on the equipment...

Страница 34: ......

Страница 35: ...entigrade CB Circuit Breaker CE European Community CISPR International Special Committee on Radio Interference CL Current Limit CUL Canadian Underwriters Laboratory D E EMI Electro Magnetic Interferen...

Страница 36: ...Low Voltage Battery Disconnect LVDS Low Voltage Disconnect Switch M M Meter Max Maximum MHz Megahertz Mm Millimeter Ms Millisecond MTBF Mean Time Between Failure MV Millivolt mVrms Millivolt root root...

Страница 37: ...Installation Operations and Maintenance Manual REV 03 10 3 Customer Specification Confidential T TB Terminal Block THD Total Harmonic Distortion U UL Underwriters Laboratory V V Volt VAC Volts AC VDC...

Страница 38: ......

Страница 39: ...600 Power Shelf Installation Operations and Maintenance Manual REV 03 A 1 Customer Specification Confidential Figure 1 Functional Blocks Power Shelf Power Supply Units Alarm Control Unit PDU Module LV...

Страница 40: ...00 Power Shelf Installation Operations and Maintenance Manual REV 03 A 2 Customer Specification Confidential Figure 1 1 Functional Blocks Power Shelf Power Supply Units Alarm Control Unit LVDS Module...

Страница 41: ...Manual REV 03 A 3 Customer Specification Confidential Figure 2 Control Supervisory Unit System Voltage Measurment System Current Measurement Manual Float Equalizing Button High Voltage Shut Down Reset...

Страница 42: ...EV 03 A 4 Customer Specification Confidential Figure 2 2 Control Supervisory Unit System Voltage Measurment System Current Measurement Manual Float Equalizing Button High Voltage Shut Down Reset SMR R...

Страница 43: ...Delta MCS 600 Power Shelf Installation Operations and Maintenance Manual REV 03 A 5 Customer Specification Confidential Figure 3 Switching Mode Rectifier...

Страница 44: ...Delta MCS 600 Power Shelf Installation Operations and Maintenance Manual REV 03 A 6 Customer Specification Confidential Figure 4 Breaker Position...

Страница 45: ...Delta MCS 600 Power Shelf Installation Operations and Maintenance Manual REV 03 A 7 Customer Specification Confidential Figure 5 Battery And Load Cable Connection Terminal...

Страница 46: ...Delta MCS 600 Power Shelf Installation Operations and Maintenance Manual REV 03 A 8 Customer Specification Confidential Figure 5 1 Battery And Load Cable Connection Terminal Load4 Load3 Load2 Load1...

Страница 47: ...Delta MCS 600 Power Shelf Installation Operations and Maintenance Manual REV 03 A 9 Customer Specification Confidential Figure 6 Alarm Relay Output Position...

Страница 48: ...Delta MCS 600 Power Shelf Installation Operations and Maintenance Manual REV 03 A 10 Customer Specification Confidential Figure 7 Power Shelf Rear View...

Страница 49: ...ustomer Specification Confidential Figure 8 PSU Block Diagram Input Fuse Inrush C K T EMI Filter and Bridge PFC Boost Converter Insulated Half Bridge DC DC Converter Output Filter PFC Controller and P...

Страница 50: ...Detection SMR Current Limit Detection Temp Sensor Lock Off Breaker or Fuse Fail FL EQU Exchange Signal SMR Fail Reset SMR Current 1 5 Load Current 1 Batt Temperature DC Voltage AC voltage Current Ala...

Страница 51: ...Delta MCS 600 Power Shelf Installation Operations and Maintenance Manual REV 03 A 13 Customer Specification Confidential Figure 10 Schematics of MCS 600 Series System 48...

Страница 52: ...FFICE 186 RUEY KUANG ROAD NEIHU TAIPEI 114 TAIWAN R O C TEL 886 2 87972088 FAX 886 2 87972120 CHUNGLI PLANT 3 TUNG YUAN ROAD CHUNGLI INDUSTRIAL ZONE CHUNGLI TAOYUAN HSIEN 320 TAIWAN R O C TEL 886 3 45...