For Cu AC wires:

AC cables should be flexible unarmored multi-strand and with suitable ampacity.

For Al AC wires:

To make sure good conductivity, bi-metal sleeves must be used in conjunction

with  aluminum wires. (Shown as 

Figure 3-9

)

Figure 3-9 : Bi-metal sleeves

Al

Cu

Extreme temperature rise at the clamping point

If the contact resistance between the aluminum conductor and clamping point is too
high, the clamping point can become very hot and even catch fire in extreme cases.

To ensure a safe and reliable contact, 

always

 perform the following work steps:

     Use a conductor cross-section at least one number larger due to the lower
     current-carrying capacity.
     Keep the installation location as free as possible from moisture or corrosive
     atmospheres.
     Connect the aluminum cables quickly.
     Mechanically clean the stripped end of the aluminum conductor (using for instance
     a knife blade to scrape off the oxide layer). Then immediately dip the aluminum
     conductor into acid-fee and alkaline-free (=neutral) Vaseline and straight away
     insert it into the terminal block.
     Tighten the clamping screw in the clamping body with the maximum permissible
     tightening torque.

NOTICE

25

Installation

Содержание M30A 230

Страница 1: ...M30A_230 Operation and Installation Manual Grid tie Transformerless Solar Inverter The power behind competitiveness www deltaww com English 1 71...

Страница 2: ......

Страница 3: ...n 3 1 Unboxing Review 3 2 Vertical wall mount 3 3 Electrical Installation for AC Wiring 3 3 1 AC Grid Types and Connections 3 3 2 Required Protective Devices 3 3 3 AC Wiring Preparation 3 3 4 AC Wirin...

Страница 4: ...Door 5 2 Replacement of Surge Protection Devices SPD 5 2 1 Replace AC SPD 5 2 2 Replace DC SPD 5 3 Replacement of Internal Fan 5 4 De Commissioning 6 Error Message and Trouble Shooting 6 1 Error Code...

Страница 5: ...Figure 3 17 Remove DC covers to expand DC inputs Figure 3 18 Mount the equipment grounding Figure 3 19 Communication module layout Figure 3 20 Location and access to communication module Figure 3 21...

Страница 6: ...wirings as connectors of AC SPD Figure 5 7 Steps of changing DC SPD Figure 5 8 Remove wirings as connectors of DC SPD Figure 5 9 Location of internal fan and fan connector Figure 5 10 Replacement of...

Страница 7: ...able 4 1 Inverter status Table 4 2 Inverter communication status Table 6 1A Error Codes Field Fault and Messages Table 6 2A Fault Codes inverter fault Messages Table 6 2B Fault Codes inverter fault Me...

Страница 8: ...has been installed and or repaired improperly b the product has been misused without following the instructions on this user manual c the product has failed due to incorrect unpacking 1 Safety 1 1 In...

Страница 9: ...ons for DELTA grid tie transformerless solar inverter The product is designed tested verified and certified according to international safety requirements certifications and standards but precautions...

Страница 10: ...afety instructions while you use the product 1 2 2 Symbols DANGER This warning indicates an immediate hazard which will lead to death or serious injury This warning indicates a possible hazard which m...

Страница 11: ...can lead to death or serious injury This warning indicates a potential burn hazard Use care when touching surfaces when operating the product Do not perform any task until the product cools down suff...

Страница 12: ...e types This user manual must be followed during installation operation and maintenance DELTA reserves the right to make modifications to the content and technical data in this user manual without pri...

Страница 13: ...nector for AC connection H4 Connector 6 pairs DC String inputs 2 1 pc 3 User Manual Important instructions for solar inverter Safety instructions should be followed during installation and maintenance...

Страница 14: ...NO Cable gland for AC output Component 6 NO Component 1 2 7 DC input H4 x 6 strings 3 8 Toggle Latch 4 SUB_1G module port option Wi Fi Antenna port 5 LED DC Switch Cable gland for RS 485 Table 2 2 Ove...

Страница 15: ...the operatoror installer Opening the housing will void the warranty Before working with the inverter you must read the supplied manual and follow the instructions contained therein This inverter is no...

Страница 16: ...llation High temperature may result in derated power output the unit should not be installed in direct sunlight Risk of injury when lifting the inverter or if it is dropped CAUTION WARNING Do not inst...

Страница 17: ...he unpacking procedure is shown as Figure 3 1 The position of hook attachment for crane transporting is shown as Figure 3 2 3 1 Unboxing Review Figure 3 1 Steps to unpacke the inverter 17 Installation...

Страница 18: ...Figure 3 2 Attaching the Hoisting hooks Hoisting Hook 18 Installation...

Страница 19: ...Figure 3 5 These are also grounding points for equipment grounding To ground the inverter please refer to Section 3 5 3 2 Vertical wall mount The mounting bracket provided with the unit is specially...

Страница 20: ...ing bracket dimensions 6 5 400 500 410 6 30 25 82 82 82 82 82 31 17 27 460 unit mm Figure 3 5 Positions of mounting screws Screw M6 Screw M5 Required position of at least 8 screws for mounting bracket...

Страница 21: ...itted and prohibited mounting positions Figure 3 6 Separation distance of plural inverters 90 Make sure it is high enough to have sufficient space for wiring 300mm 300mm 200mm 200mm 300mm 500mm 500mm...

Страница 22: ...tructions may damage AC cable If there is any conflict between installation instruction and electrical code please follow the electrical code CAUTION INVERTER AND EQUIPMENT DAMAGE MAY OCCUR WARNING Co...

Страница 23: ...Model Upstream circuit breaker M30A_230 60A max Size of each wire Cable diameter 13 3 25 mm 6 4 AWG 23 31 mm The AC wires must be jacketed and meet the specifications in Table 3 2 If there is any con...

Страница 24: ...Jacket W C D F B L End sleeve is not able to be installed if 25mm 4AWG is applied 16mm 6AWG dimensions of the recommended sleeve are indicated below WIRE SIZE DIMENSIONS mm L F C D W 28 18 B 10 5 8 6...

Страница 25: ...a safe and reliable contact always perform the following work steps Use a conductor cross section at least one number larger due to the lower current carrying capacity Keep the installation location a...

Страница 26: ...s tighten by 2 5mm wrench with 2 5 N m torque into Part B Figure 3 12 3 Rotate part A B as Figure 3 13 to fit and fix it onto the inverter Figure 3 10 Assemble the AC plug The connector is not designe...

Страница 27: ...Power system There are 5 wires that include L1 L2 L3 N PE For 3P3W Power system There are 4 wires that include L1 L2 L3 PE 13 3 25 mm 6 4 AWG tighten torque 2 5 N m Figure 3 12 AC wiring Figure 3 13...

Страница 28: ...er fault conditions Only PV modules that are listed with system voltage under 1100V are permitted for use Make sure the DC switch is in the OFF position and disconnect the PV array before plug in out...

Страница 29: ...re divided into positive and negative layout of the connectors is shown as Figure 3 15 Ensure the DC conductors used are Cu and sized to the correct ampacity per NEC or other local code Strip off all...

Страница 30: ...Figure 3 15 Location of H4 connectors to connect array wiring DC 30 Installation...

Страница 31: ...nt Grounding Figure 3 16 Mount the equipment grounding To ground the inverter please crimp the grounding wire to ring terminal lug and fix it on the grounding point shown as Figure 3 16 Screw M5 31 In...

Страница 32: ...ontact EPO and digital input terminals for various applications and it can be extended to ability to use Sub_1G 3 6 Communication Module Connections Figure 3 17 Communication module layout Dry Contact...

Страница 33: ...s See Figure 3 18 Loose the self retaining screws from the chassis and gently pull the carrier straight out of the chassis to withdrawthe communication module After passing the required signal cable t...

Страница 34: ...485 connection scenarios require different set up for the 120ohm bus termination resistor When multiple inverters are cascaded i e daisy chained only the last inverter in the chain must have its bus t...

Страница 35: ...iinverter connection illustration Terminal Resistor 120 1 2W DATA to DATA Table 3 4 Bus Termination switch settings Switch 1 Terminal Resistor ON Terminal Resistor OFF OFF ON RS485 USB or RS485 RS232...

Страница 36: ...V1 K0 A digital power reduction control function is provided which can be set to limit the available active output power of the inverter The control settings for this function are made by placing a ha...

Страница 37: ...ter The terminal block for this function is shown in Figure 3 21 The terminals marked in the figure identify the dry contact connection The dry contacts operation are usually open User can customize t...

Страница 38: ...rque 2 Connect the signal cable to the RS 485 terminal block of the communication module The wires definition of the signal cable is shown below 3 Bind the signal cable to the chassis with cable tie o...

Страница 39: ...enna for Wi Fi in the package item 8 Table 2 1 which must be mounted on the plastic carrier as the procedure below 1 Remove the protective nut 2 Tighten the antenna Figure 3 23 Installation of Wi Fi a...

Страница 40: ...he DC switch is in the OFF position 2 Place one probe in any DC connectors shown in Figure 3 24 and the other on the ground 3 8 On Site Insulation Test Figure 3 24 Precautions for on site insulation t...

Страница 41: ...or GRN LED Indicator GRN Condition Grid Green Alarm Red Yellow Countdown FLASH OFF OFF On Grid ON OFF OFF Inverter Fault Remote off Field Warning NO DC FW Upgrade OFF ON OFF Inverter Warning ON or OFF...

Страница 42: ...of Inverters and press 3 Show the inverter serial number and ID and the status display OK is completed The Auto ID function could set all inverter IDs at monitoring center after wiring RS 485 4 2 1 A...

Страница 43: ...ers of ID setting less than amounts of inverter status show False Figure 4 3 False of auto ID setting by tool The numbers of ID setting more than amounts of inverter status show False YES YES 43 Commi...

Страница 44: ...ure 4 4 Steps of set ID 2 1 Enter the ID you want to change 2 Click to complete The wrong ID setting of overlapping YES Figure 4 5 False of set ID To adjust the ID order please follow the settings bel...

Страница 45: ...ure 4 6 Steps of set country 2 2 Click the to complete country setting Enter as a country that does not exist YES Figure 4 7 False of set country Set country by the AUTO ID 1 Entry the local country I...

Страница 46: ...terference problem make sync time fail please try again YES Figure 4 9 False of synchronize time Figure 4 8 Steps of synchronize time YES Click the to complete time setting 1 Synchronize time by Auto...

Страница 47: ...Q U control volt var control Q by night Q setting 24 7 Anti PID Dry contact ARC fault detection Wi fi DSS Operation Manual APP MyDeltaSolar Operation and Installation Manual https mydeltasolar deltaww...

Страница 48: ...different seasons and weather effects 5 1 Open and Close the Door 5 1 1 Open Door 1 Loosen the screws on both latch covers with hexagon wrench attached on the latch cover Figure 5 1 2 Open the latch c...

Страница 49: ...ed 3 Remove the hexagon wrench and close the door 4 Buckle the latch and secure the latch cover with the hexagon wrench 5 The hexagon wrench can be fixed on the latch cover Due to corrosion of live pa...

Страница 50: ...hich is located behind the protective cover and can be replaced if damaged If the warning message AC Surge or DC Surge appears on the APP and DSS please follow the steps below to replace the SPD Figur...

Страница 51: ...n 5 1 1 to open the door 3 Loosen the screw and remove protective cover 4 Loosen 3 screws remove wires and disconnect signal cable to take off AC SPD 5 Install the new AC SPD unit with procedures abov...

Страница 52: ...Screw torque 0 8 N m Figure 5 6 Remove wirings as connectors of AC SPD 52 Maintenance...

Страница 53: ...ollow Section 5 1 1 to open the door 3 Slide open the protective cover 4 Loosen 3 screws remove wires and disconnect signal cable to take off DC SPD 5 Install the new DC SPD unit with procedures above...

Страница 54: ...Screw torque 0 8 N m BACK FRONT Figure 5 8 Remove wirings as connectors of DC SPD 54 Maintenance...

Страница 55: ...an cabinet 5 Loosen the screws to lift the entire fan assembly 6 Clean assembly or replace with a unit 7 Install the internal fan with procedures above in reverse order and tighten the screws with rec...

Страница 56: ...Screw torque 0 8 N m Screw torque 0 6 N m Screw torque 0 8 N m Screw torque 0 6 N m FAN 1 FAN 2 Figure 5 10 Replacement of internal fans 56 Maintenance...

Страница 57: ...2 Remove all communication cables from the module terminals 3 Reinstall the communication board assembly in inverter 5 4 De Commissioning If it is necessary to remove the inverter from active operati...

Страница 58: ...lug 1 Check the utility voltage within the suitable range 2 Check Grid code Grid setting 3 Check the connection in AC plug AC Volt High E11 1 Actual utility voltage is over the OVR setting 2 Incorrect...

Страница 59: ...detection failure Contact customer service for technical support Inveter Temp Fault F10 Inverter module temperature detection failure Contact customer service for technical support AC Sensor Fault F1...

Страница 60: ...it is disconnected Contact customer service for technical support Contact customer service for technical support Grid relay short Grid relay open Contact customer service for technical support AC RLY...

Страница 61: ...erter terminal 4 Check the utility voltage on the inverter terminal 5 1 Check the utility voltage on the inverter terminal 5 2 Check reactive power setting 6 Check the Solar voltage on the inverter te...

Страница 62: ...ted Output Power Nominal AC Voltage Operating Frequency Range Operating Voltage Range 7 Technical Information M30A_230 1100 V 1 3 50A per MPPT 200 1000 V 480 900 V 250 V Built in 600 V Each MPPT 20 4...

Страница 63: ...tion Operating Temp Range Protection Level Operating Elevation Cooling 98 6 98 2 RS 485 SUB_1G optional Wi Fi optional 651 x 520 x 220 mm 25 to 60 C Derating Above 40 C IP66 4000 m Natural cooling 42...

Страница 64: ...Figure 7 1 Efficiency Curve Efficiency Pn 30kW Efficiency Output voltage at 230Vac 400Vac 0 20 40 100 80 60 90 91 92 93 94 95 96 97 98 99 100 480V 600V 800V Output Power Technical Information 64...

Страница 65: ...Ambient Temprature PF 1 P Pn Pn 30kW Power Derating Curve with Ambient Temprature Output voltage at 230Vac 400Vac PF 1 Ambient Temperature C 30 0 10 20 40 50 60 50 40 30 60 70 80 90 100 110 20 480V 60...

Страница 66: ...bient Temprature PF 0 9 P Pn Pn 30kW Power Derating Curve with Ambient Temprature Output voltage at 230Vac 400Vac PF 0 9 Ambient Temperature C 30 0 10 20 40 50 60 50 40 30 60 70 80 90 100 110 20 480V...

Страница 67: ...dix Assembly Note NO Location Screw torque 2 Communication cover 8 0 kgf cm 0 8N m 1 Wi Fi module cover 8 0 kgf cm 0 8N m 3 SUB_1G case 10 2 kgf cm 1N m Appendix 1 Assembly Note 1 67 Technical Informa...

Страница 68: ...Internal fan 2 cover 6 0 kgf cm 0 6N m 1 Internal fan 2 8 0 kgf cm 0 8N m 3 Internal fan 1 4 Internal fan 1 cover 8 0 kgf cm 0 8N m 6 0 kgf cm 0 6N m H4 wire 5 12 10 AWG 4 6mm Appendix 2 Assembly Not...

Страница 69: ...tion 2 AC SPD board 1 AC SPD cover 3 DC SPD board 4 Communication port 8 0 kgf cm 0 8N m 8 0 kgf cm 0 8N m 8 0 kgf cm 0 8N m 20 AWG 0 5mm 5 AC wire 25 5 kgf cm 2 5N m 6 AWG 13 3 mm 4 AWG 25 mm Appendi...

Страница 70: ......

Страница 71: ...www deltaww com M30A_230 The power behind competitiveness English 1 71...

Страница 72: ......

Страница 73: ...87 89 92 93 93 93 96 98 101 102 103 104 106 107 108 109 110 Contents 1 1 1 1 1 1 1 1 2 1 2 1 2 1 1 2 2 2 2 1 2 2 3 3 1 3 2 3 3 3 3 1 AC 3 3 2 3 3 3 3 3 4 3 4 3 5 3 6 3 6 1 3 6 2 RS 485 3 6 3 EPO 3 6 4...

Страница 74: ...4 115 116 117 118 118 118 119 120 121 123 125 127 128 128 129 131 131 132 137 4 4 1 LED 4 2 ID 4 2 1 ID 4 2 2 ID 4 2 3 4 2 4 4 3 Delta 5 5 1 5 1 1 5 1 2 5 2 SPD 5 2 1 AC SPD 5 2 2 DC SPD 5 3 5 4 6 6 1...

Страница 75: ...101 102 103 105 106 107 108 109 110 111 112 113 114 114 115 115 116 116 2 1 2 2 2 3 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 3 10 3 11 3 12 3 13 3 14 3 15 H4 3 16 3 17 3 18 3 19 3 20 3 21 3 22 Wi Fi 3 23 S...

Страница 76: ...118 119 120 120 121 122 123 124 125 126 134 135 136 5 1 5 2 5 3 5 4 5 5 AC SPD 5 6 AC SPD 5 7 DC SPD 5 8 DC SPD 5 9 5 10 7 1 7 2 PF 1 7 3 PF 0 9 76...

Страница 77: ...Table 83 84 85 93 93 104 105 106 111 111 128 129 130 131 131 132 133 137 138 139 2 1 2 2 2 3 3 1 3 2 3 3 RS 485 3 4 3 5 EPO 4 1 LED 4 2 LED 6 1A 6 2A 6 2B 6 3A 6 4A 7 1A 7 1B 1 1 2 2 3 3 77...

Страница 78: ...DELTA ELECTRONICS INC All rights reserved DELTA ELECTRONICS INC DELTA ELECTRONICS INC 1 1 1 1 1 1 1 1 2 78...

Страница 79: ...L1 L2 L3 N DELTA 1 2 M30A_230 3 MPP 10 F DELTA 1 2 1 79...

Страница 80: ...1 2 2 80...

Страница 81: ...81...

Страница 82: ...M30A_230 EMI 2 L1 L2 L3 N DELTA 2 1 M30A_230 82...

Страница 83: ...M30A_230 1 DELTA 1 1 H4 2 6 1 H4 6 2 1 3 5 7 4 1 2 2 2 1 2 1 2 1 3mm H4 Wi Fi 1 8 Wi Fi 83...

Страница 84: ...NO NO M50 cable gland for AC output Component 6 NO Component 1 2 7 DC input H4 x 6 strings 3 8 Toggle Latch 4 SUB_1G module port option Wi Fi Antenna port 5 LED DC Switch 1 1 cable gland for RS 485 2...

Страница 85: ...60 seconds 2 3 2 3 2 3 2 3 WEEE marking 60 85...

Страница 86: ...3 1 2 3 86...

Страница 87: ...3 1 3 2 3 1 3 1 87...

Страница 88: ...3 2 88...

Страница 89: ...3 4 3 7 1 2 3 4 3 12 M6 3 5 4 5 2 M5 3 5 3 5 3 2 520 mm 490 mm 651 mm 220 mm 3 3 8 M6 89...

Страница 90: ...M6 M5 3 4 8 3 5 6 5 400 500 410 6 30 25 82 82 82 82 82 31 17 27 460 unit mm 90...

Страница 91: ...90 3 6 3 7 300mm 300mm 200mm 200mm 300mm 500mm 500mm 91...

Страница 92: ...3 3 92...

Страница 93: ...30 3 3 3 3 1 3 2 TNC system 220 380V 230 400V M30A_230 M30A_230 M30A_230 M30A_230 L1 L2 L3 PE N TNC S system 220 380V 230 400V L1 L2 L3 N PE TT system 220 380V 230 400V L1 L2 L3 N IT system 220 380V 2...

Страница 94: ...3 mm 25 mm 6 AWG 4 AWG 25 mm 4 AWG 70 mm MAX 22 2 mm PE N L1 L2 L3 Outer Jacket W C D F B L 25 mm 4 AWG 16 mm 6 AWG WIRE SIZE DIMENSIONS mm L F C D W 28 18 B 10 5 8 6 2 8 7 16mm 6AWG 70 mm 22 2 mm 3 8...

Страница 95: ...3 9 3 9 Al Cu 1 2 3 4 5 95...

Страница 96: ...Cable range 23 31 mm 1 3 10 A B 2 A B 3 12 3 A B 3 13 3 10 3 11 P F Part A 165 3 168 5 REF 60 0 5 3 3 4 A B D1 96...

Страница 97: ...A B Part B L1 L2 L3 N PE L1 L2 L3 PE 3P4W L1 L2 L3 N PE 3P3W L1 L2 L3 PE 13 3 25 mm 6 4 AWG tighten torque 2 5 N m 3 12 3 13 A B 97...

Страница 98: ...DC 3 4 1100V 1100V LED 98...

Страница 99: ...H4CMC4D MS H4CFC4D MS M30A_230 H4 3 14 NEC 6 5 7 5mm 12 10 AWG 4 6mm2 3 15 3 4 1 3 14 99...

Страница 100: ...3 15 H4 100...

Страница 101: ...M5 3 5 O 3 16 3 16 101...

Страница 102: ...x2 VCC RS 485 V1 x1 EPO x1 x6 12V 12V ON 1 3 6 3 22 12V VCC RS 485 EPO SUB_1G 3 17 102...

Страница 103: ...3 6 1 3 18 0 8 N m 3 18 103...

Страница 104: ...2V 12V ON 3 5 RS 485 DATA 4 6 RS 485 DATA 120 3 19 3 4 RS 485 3 27 RS 485 610m Belden 3105A RS 485 30m Pin Function 1 VCC 12V 2 GND 3 DATA 4 DATA 5 DATA 6 DATA 1 2 3 4 5 6 VCC GND D D D D 3 6 2 RS 485...

Страница 105: ...120 1 2W DATA to DATA ON OFF OFF ON RS485 USB or RS485 RS232 3 19 3 4 105...

Страница 106: ...EPO APP Delta Solar System DSS 3 6 3 EPO 3 20 3 5 EPO V1 K0 EPO 3 5 EPO 0 30 60 100 V1 K0 V1 K1 V1 K2 V1 K3 V1 K4 V1 K5 V1 K6 106...

Страница 107: ...Dry Contact B Dry Contact A M30A_230 3 21 APP DSS 3 6 4 3 21 107...

Страница 108: ...VCC GND D D D D SUB_1G DC1 SUB_1G PCB 1 1 N m 2 M4 2 RS 485 3 23 3 M4 1 N m RS 485 terminal block Red Black White Green VCC GND D D Cable Pin 0 8 N m 3 6 5 SUB_1G 3 22 SUB_1G 108...

Страница 109: ...3 7 Wi Fi 3 23 Wi Fi Wi Fi APP DSS 8 2 1 Wi Fi 1 2 Wi Fi APP QR code https mydeltasolar deltaww com p product_manual 109...

Страница 110: ...DC Switch OFF OFF ON 3 8 1 OFF 2 H4 3 24 H4 110...

Страница 111: ...OFF FLASH OFF OFF FLASH OFF FLASH SLOW FLASH OFF Standby FLASH OFF FLASH Check PV Power FLASH FAST OFF FLASH FAST OFF ON FLASH ON 1s OFF 1s FLASH FAST ON 0 25s OFF 0 25s FLASH SLOW ON 5s OFF 10s COMM...

Страница 112: ...YES 4 2 ID 4 2 ID 1 1 COM Port 2 3 ID OK RS 485 ID ID https mydeltasolar deltaww com dl_installer_guide php f autoid 4 2 1 ID 2 112...

Страница 113: ...ID ID 4 3 ID YES YES 113...

Страница 114: ...YES 4 2 2 ID 4 4 ID 2 1 ID 2 ID YES 4 5 ID ID 114...

Страница 115: ...4 2 3 YES 4 6 2 2 ID YES 4 7 Country ID 1 ID 115...

Страница 116: ...4 2 4 YES 4 9 4 8 YES 1 ID 116...

Страница 117: ...Q Auto ID Q U control volt var control Q by night Q setting 24 7 Anti PID Dry contact ARC fault detection Wi fi PPM DC1_100 Delta DSS Delta Solar System Software APP MyDeltasSolar DSS APP MyDeltaSola...

Страница 118: ...1 5 1 2 5 1 3 5 2 5 LED 5 1 5 1 1 5 1 118...

Страница 119: ...1 2 3 4 5 5 2 5 1 2 119...

Страница 120: ...APP DSS W18 AC Surge W17 DC Surge AC SPD DC SPD 5 2 SPD M30A_230 5 3 5 4 120...

Страница 121: ...1 LED 2 5 1 1 3 4 3 AC SPD 5 AC SPD 0 8 N m 3 6 0 8 N m 7 5 1 2 0 8 N m 0 8 N m 5 2 1 AC SPD 5 5 AC SPD 121...

Страница 122: ...0 8 N m 5 6 AC SPD 122...

Страница 123: ...1 LED 2 5 1 1 3 5 7 4 3 DC SPD 5 DC SPD 0 8 N m 3 6 7 5 1 2 0 8 N m 5 2 2 DC SPD 5 7 DC SPD 123...

Страница 124: ...0 8 N m 5 8 DC SPD 124...

Страница 125: ...1 LED 2 5 1 1 3 DC SPD 4 5 6 7 5 10 8 5 1 2 FAN 1 FAN 2 5 3 5 9 DC SPD 125...

Страница 126: ...0 8 N m 0 6 N m 0 8 N m 0 6 N m FAN 1 FAN 2 5 10 126...

Страница 127: ...5 4 42 AC DC H4 H4 Wi Fi RS 485 1 2 3 127...

Страница 128: ...Quality E07 AC phase abnormal E08 No Grid E09 AC Volt Low E10 1 2 3 AC AC Volt High E11 1 2 Insulation Fault E34 DC Voltage High E30 6 1A 6 1 6 4 6 1 6 1 2 1 2 AC AC 1 AC 2 AC 1 AC 2 AC 1 2 3 AC 1 2 3...

Страница 129: ...Temperature High F05 Temperature Low F07 Amb Temp Fault F06 Boost Temp Fault F08 Inveter Temp Fault F10 AC Sensor Fault F15 F18 1 2 AC RLY Fault F13 1 2 1 2 1 2 Idc Sensor Fault F17 F19 Eff Abnormal...

Страница 130: ...Iac Unbalance F26 RCMU Fault F27 AC RLY Short F28 AC RLY Open F29 Bus Unbalance F30 Bus Voltage High F31 F33 F35 Bus 1 DC 2 Voc 1000Vdc E30 AC Current High F36 F37 F38 F39 F40 F41 AC CT Fault F42 AC...

Страница 131: ...7 String fault W08 Fan Fail W11 DC SPD AC SPD Fault W18 1 DC SPD 2 DC SPD 1 AC SPD 2 AC SPD AC SPD DC SPD Fault W17 6 3A 6 3 6 4A 6 4 1 2 3 P F 4 P V 5 6 7 8 1 2 1 2 3 1 2 3 4 5 1 5 2 6 PV panel 7 PV...

Страница 132: ...V Each MPPT 20 4 kW Total 33 5 kW Each MPPT 30 A Total 72 A 2 strings MPPT Amphenol H4 Connector 50 A 30 kW 40 C 33 kW 35 C 33 kVA 50 60Hz 5Hz 80 to 130 of Nominal AC Voltage 3 Ph 220 380V 230 400V Y...

Страница 133: ...2 IEC 62920 CNS 15382 VDE AR N 4110 EN IEC 61000 6 3 4 98 6 98 2 RS 485 SUB_1G optional Wi Fi optional 651 x 520 x 220 mm 25 to 60 C Derating Above 40 C IP66 4000 m 42 kg M30A_230 Model 7 1B W x H x D...

Страница 134: ...Pn 30kW 230Vac 400 Vac 0 20 40 100 80 60 90 91 92 93 94 95 96 97 98 99 100 480V 600V 800V 7 1 134...

Страница 135: ...P Pn Pn 30kW 230 Vac 400 Vac PF 1 C 30 0 10 20 40 50 60 50 40 30 60 70 80 90 100 110 20 480V 600V 800V 900V 7 2 PF 1 135...

Страница 136: ...P Pn Pn 30kW 30 0 10 20 40 50 60 50 40 30 60 70 80 90 100 110 20 480V 600V 800V 900V 7 3 PF 0 9 230 Vac 400 Vac PF 0 9 C 136...

Страница 137: ...2 8 0 kgf cm 0 8N m 1 Wi Fi 8 0 kgf cm 0 8N m 3 SUB_1G 10 2 kgf cm 1N m NO 1 1 137...

Страница 138: ...2 2 6 0 kgf cm 0 6N m 1 2 8 0 kgf cm 0 8N m 3 1 4 1 8 0 kgf cm 0 8N m 6 0 kgf cm 0 6N m H4 5 12 10 AWG 4 6mm H4CMC4D MS H4CFC4D MS 2 2 NO 138...

Страница 139: ...2 1 3 4 8 0 kgf cm 0 8N m 8 0 kgf cm 0 8N m 8 0 kgf cm 0 8N m 20 AWG 0 5mm 5 AC 25 5 kgf cm 2 5N m 6 AWG 13 3 mm 4 AWG 25 mm 3 3 NO 139...

Страница 140: ......

Страница 141: ......

Страница 142: ...Version 03201125...

Отзывы: