Chapter 4 Communication Setting
LD-E Operation Manual
4-1
Chapter 4
Communication Setting
4.1 Communication Address
◎
RS485 Communication Mode
◎
Baud Rate Supported: 9,600, 14400, 19200, 38400, 57600, 115200bps
◎
Communication Mode Supported: 8,N,1
、
8,N,2
、
8,O,1
、
8,O,2
、
8,E,1
、
8,E,2
、
7,O,1
、
7,E,1
、
7,O,2
、
7,E,2
◎
Communications Protocol: Modbus RTU, ASCII
◎
Communication Address Supported: 1 to 127
◎
Function Code `
03H: Read the contents of the register, 06H: Write 1 byte to the address
Address
Function
code
Name
Description
1000H (R/W)
(03H,06H)
Device address
Device address:1~127
1002H (R/W)
(03H,06H)
Communication
baud rate
0x01: 9600
0x02: 14400
0x03: 19200
0x04: 38400
0x05: 57600
0x06: 115200 (Default)
1003H (R/W)
(03H,06H)
Communication
format
0x01: ASCII, 8, N, 1
0x02: ASCII, 8, O, 1
0x03: ASCII, 8, E, 1
0x04: ASCII, 8, N, 2
0x05: ASCII, 8, O, 2
0x06: ASCII, 8, E, 2
0x07: RTU, 8, N, 1 (Default)
0x08: RTU, 8, O, 1
0x09: RTU, 8, E, 1
0x0A: RTU, 8, N, 2
0x0B: RTU, 8, O, 2
0x0C: RTU, 8, E, 2
0x0D: ASCII, 7, O, 1
Содержание LD-100E-M22
Страница 4: ...Chapter 1 Product Profile LD E Operation Manual 1 3 Wiring Instructions...
Страница 14: ...Chapter 2 Settings and Measurements LD E Operation Manual 2 9 Steps...
Страница 15: ...Chapter 2 Settings and Measurements LD E Operation Manual 2 10...
Страница 16: ...Chapter 2 Settings and Measurements LD E Operation Manual 2 11...
Страница 19: ...Chapter 3 Software Operation LD E Operation Manual 3 2 Next Close...
Страница 25: ...Chapter 3 Software Operation LD E Operation Manual 3 8 Parameter reading and writing operation area...