28
InfraSuite Power Management
Command
Description
Parameter
Response
SetPrefer
Set the preferred source.
1 or 2
Various kinds
SetDevID
Set the unit's device ID.
<20
characters>
alphanumeric
only
Various kinds
SetVtp2s
Set the primary to
secondary trip voltage.
165.0 ~ 175.0 Various kinds
SetVts2p
Set the secondary to
primary trip voltage.
165.0 ~ 175.0 Various kinds
SetVbp2s
Set the primary to
secondary brownout
voltage.
180.0 ~ 264.0 Various kinds
SetVbs2p
Set the secondary to
primary brownout voltage.
180.0 ~ 264.0 Various kinds
SetTdp2s
Set the recover time of
transfer from primary to
secondary.
12.0 ~ 1800.0 Various kinds
SetTds2p
Set the recover time of
transfer from secondary to
primary.
12.0 ~ 1800.0 Various kinds
SetMvs1
Set the max voltage of
comparing cycles for
primary AC blackout.
30 ~ 50
Various kinds
SetMvs2
Set the max voltage of
comparing cycles for
secondary AC blackout.
30 ~ 50
Various kinds
SetMts1
Set the max time of
comparing cycles for
primary AC blackout.
2.0 ~ 4.0
Various kinds
SetMts2
Set the max time of
comparing cycles for
secondary AC blackout.
2.0 ~ 4.0
Various kinds