HEX200PC  Heat  Exchanger  Instruction  Manual 

 

 

Page 4   

User can follow dry contact definition that is Normal Close (N.C.) to 

detect abnormal status from pin 10 & pin 11 

 

Definition 

N. C 

Connection 

Pin 10 & Pin 11 

Control board, NTC and fan are in 
normal status 

CLOSE 

NTC resistance is over range such as 
“open circuit” or “short circuit” 

OPEN 

Fan speed is lower than 50% of 
definition or fan is locked 

OPEN 

 

Dry contact max. rating : 75VDC/50mA 

 

LED indicator 

 

 

INNER FAN / OUTER FAN / STATUS LEDs indicate fan and NTC   

sensor status . 

Depress "TEST" button to start auto-test of outer and inner fans 

  running from low to high speed. Turn off by depressing the “TEST” button 

again . 

 

 

INNER FAN 

OUTER FAN 

STATUS 

Normal 

GREEN 

GREEN 

GREEN 

Failed* 

RED 

RED 

RED 

Normal   

(touch TEST / CLEAN) 

Blinking 

GREEN 

Blinking 

GREEN 

N/A 

Failed* 

(touch TEST / CLEAN) 

Blinking 

RED 

Blanking 

  RED 

N/A 

               

   

    * FAN failed : Fan speed is lower than 50% of definition or fan is locked 

                      * STATUS Failed : NTC resistance is over range such as “open circuit” or 

                                                        “short circuit” 

Содержание HEX200PC

Страница 1: ...Fremont Blvd Fremont CA 94538 U S A TEL 1 510 668 5100 FAX 1 510 668 0680 Cabinet Thermal Solutions deltaww com Taiwan Delta Electronics Inc 252 Shang Ying Road Kuei San District TEL 886 0 3 3591968...

Страница 2: ...Electrical specification 3 4 1 Connection and LED indicator on HEX panel 3 4 2 Standalone control mode 5 5 Mechanical feature 6 5 1 Thermal path and Airflow baffle 6 5 2 Configuration 6 6 Maintenance...

Страница 3: ...air loop conforms to IP55 protection rating 2 2 Specification Main feature Unit Model Number HEX200PC Outline Dimension H x W x D mm in 690 x 700 x 242 27 x 28 x 10 Cooling Capacity Note 1 W K W 135...

Страница 4: ...F 149 F Storage temperature 40 C 70 C 40 F 158 F Humidity External air circuit 0 100 RH Internal air circuit 0 90 RH Ingress protection on external side l IEC60529 IP55 NEMA 3 GR 487 720hrs salt spra...

Страница 5: ...out and waterproof foam sicking 4 Electrical specification 4 1 Connection and LED indicator on HEX panel Power Connection on panel plate CVILUX 3W3CS0000100000 mate with CVILUX 3W3CP0000100000 COMM co...

Страница 6: ...Dry contact max rating 75VDC 50mA LED indicator INNER FAN OUTER FAN STATUS LEDs indicate fan and NTC sensor status Depress TEST button to start auto test of outer and inner fans running from low to hi...

Страница 7: ...t Pin7 Pin8 via J13 connector on controller as shown as below to change sensor location 4 2 Standalone control mode HEX can detect ambient temperature to control cooling capacity Internal fan and exte...

Страница 8: ...g The air supply of the cold air will be used to cool down the system On the opposite side cooler air from the surrounding environment will be drawn in from the external air inlet side and push the he...

Страница 9: ...3 Note the connection location Use brush and low pressure air to remove dust on internal plate assy Item 7 internal fan item 4 and heat exchange core opening Hold internal plate assy Item 7 and connec...

Страница 10: ...d submit spare part s below for replacement Internal fan P N AFB1548EH BJ51 External fan P N AFB1548VH CH36 Controller P N HEX200PC 000C User can then refer to maintaince sequence on previous page or...

Страница 11: ...use caution at all times Incorrect installation may cause damage and or injury Installation and maintenance should be performed only by qualified personnel please use caution at all times Please make...

Отзывы: