Power & Range 

Input Voltage 

VDC 

48 

Max. Operating DC Current 

14.3 

Alarm 

N/A 

Dry Contact Output 

Key Components 

Controller 

 

Built-in Smart Controller 

Fans 

 

Delta High Efficiency Blowers 

Compressor 

 

Rotary, DC 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание HEC1000PB

Страница 1: ...v Delta Model No HEC1000PB Rev 02 Sample Date Code Sample Issue Date SEP 15 2020 DELTA ELECTRONICS INC 252 SHANG YING ROAD KUEI SAN TEL 886 0 3 3591968 TAOYUAN CITY 333 TAIWAN FAX 886 0 3 3591991 Plea...

Страница 2: ...nce 12 1 6 Thermal and Airflow 13 2 Electrical Specification 14 2 1 Indicator Connector 14 2 1 1 Power Supply Alarm Connector 14 2 1 2 Protection 15 3 Environmental Condition 17 3 1 Operating Temperat...

Страница 3: ...Part no Delta model no HEC1000PB Page 3 9 Reclaim 21 10 Versions 21...

Страница 4: ...objects on it Please pay attention to the following icons on the package If air conditioner is toppled over slanted or dropped unfortunately please follow below steps a stand for 12 hours to ensure re...

Страница 5: ...ing into wall or ceiling do not damage electrical wiring or hidden utilities 8 Be sure to use only the specified accessories and parts for installation work 9 Protective earth connection The enclosure...

Страница 6: ...onditioner while moving or storage 8 The hole in the bottom of the air conditioner should be connected to a sealed container through a drainpipe 9 The appliance is not to be used by persons including...

Страница 7: ...n for Approval Customer Description Air conditioner for Equipment with 1000 W Rated Cooling Capacity Through Wall Mounting Customer P N Rev Delta model no HEC1000PB Rev 02 Sample revision Date Code Sa...

Страница 8: ...od Dimension H x W x D without flange mm inch 700 x 500 x 200 27 7 x 19 8 x 7 9 Application Outdoor Weight Kg lbs 28 0 61 7 Mounting Method Door Side Color optional RAL7035 Environmental Protection Pe...

Страница 9: ...o HEC1000PB Page 9 Power Range Input Voltage VDC 48 Max Operating DC Current A 14 3 Alarm N A Dry Contact Output Key Components Controller Built in Smart Controller Fans Delta High Efficiency Blowers...

Страница 10: ...Part no Delta model no HEC1000PB Page 10 1 3 Dimension mm inch 1 Material Case SGCC Sheet 2 Finish Powder coating 75 120 uM Color RAL 7035 3 Dimensional Tolerance 1 mm...

Страница 11: ...Part no Delta model no HEC1000PB Page 11 1 4 Mounting Panel Cutout Inside Outside Gasket...

Страница 12: ...an clean the condenser with water directly The external side fan blade can also be cleaned with normal pressure water if there is dust accumulation Please do not use strong water jet to impact the cen...

Страница 13: ...protecting cover is sealed with silicon for IP55 requirement Please do not dismantle the sealed cover or will lose the quality assurance of the compressor 1 6 Thermal and Airflow The internal and ext...

Страница 14: ...3 N A N A 4 N A N A 5 N A N A Pin Description 3 Alarm 4 Alarm System alarm default setup Note Customers can setup the N O or N C by themselves when any alarm happen through display board d1 6 Dry cont...

Страница 15: ...rmally and the LED will light in green If the system gets into self test mode and the LED will flash in green Fan In When the inner fan is running normally and the LED will light in green Fan Out When...

Страница 16: ...PB Page 16 Allow reverse voltage 42 58 VDC Short Ckt If compressor UVW short for any both phase the compressor will not operate Compressor H T protection Tcomp 105 oC Eva L T protection TEVA 0 oC Powe...

Страница 17: ...otection Rating IP55 IEC60529 on external side GR487 on external side 4 Reliability Table Test item Condition High temperature IEC 60068 2 2 Low temperature IEC 60068 2 1 High temp High humidity IEC 6...

Страница 18: ...Table 7 1 System Setup Item System Parameter Default Range d1 1 System Version 2 5 N A d1 2 Alarm Logs 0 0 N A d1 3 Inside over temp Setup 60 oC 40 oC 70 oC d1 4 Auto Self Test Function Enable Enable...

Страница 19: ...ection 2 2 PWB Temperature Protection 2 3 IPM Temperature Protection 2 4 Amb Temperature Protection 2 5 3 Temperature Sensor Fault Amb Temperature Sensor 3 1 Eva Temperature Sensor 3 2 Cond Temperatur...

Страница 20: ...onditioner is running but the cabinet temperature is still high no obvious cooling effect 1 The air conditioner capacity is not match the load of the system 2 The ambient temperature is too high 3 Low...

Страница 21: ...te It must be taken to a special local authority differentiated waste collection center or to a dealer providing this service 10 Versions REV Description Owner Date 00 Issue SPEC VIC 2015 06 15 01 Mod...