Delta HEC1000PB Скачать руководство пользователя страница 5

Part no. :   

Delta model no. : HEC1000PB 

 
 

 

 

Page 5   

  Warning: 

1. 

Installation  work  and  electrical  wiring  must  be  done  by  qualified  person(s)  in  accordance  with  all 

applicable codes, standards and national wiring

 

regulations. 

2. 

Use this unit only in the manner intended by the manufacturer. If you have questions, please contact the 

manufacturer. 

3. 

Install  the  air  conditioner  in  accordance  with  the  instructions  in  this  installation  manual.  Improper 

installation may result in water leakage, electric shocks or fire. 

4. 

Make sure that all wiring is secured, the specified wires are used, and there is no strain on the terminal 

connections or wires. 

5. 

If refrigerant gas leaks during installation, ventilate the area immediately. Do not directly touch refrigerant 

that has leaked from refrigerant pipes or other areas, as there is a danger of frostbite. 

6. 

Before serving or cleaning unit, switch power off and disconnect power supply. 

7. 

When cutting or drilling into wall or ceiling, do not damage electrical wiring or hidden utilities. 

8. 

Be sure to use only the specified accessories and parts for installation work. 

9. 

Protective  earth  connection:  The  enclosure  must  be  earthed  at  the  protective  earth  terminal.  Use  2.5 

mm

2

 (14 AWG) wire and use spring washer to avoid loosening. 

10. 

The air conditioner shall be not accessible to the general public. 

11. 

The installation must contain a device to disconnect all poles of the air conditioner from the power supply. 

The contact distance in all poles must be 3 mm minimum. 

12. 

To reduce the risk of electrical shock. Means for disconnection must be incorporated in the fixed wiring in 

accordance with the wiring rules. 

13. 

This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, 

or for commercial use by lay persons”

.

 

 

  Caution 

1.  Install the air conditioner on a wall/ door strong enough to withstand the weight of the unit. 

2.  Do not block air inlets or exits. 

3.  Do not install the air conditioner at any place where there is a danger or flammable gas leakage. 

4.  Arrange the drain to ensure complete drainage. 

Содержание HEC1000PB

Страница 1: ...v Delta Model No HEC1000PB Rev 02 Sample Date Code Sample Issue Date SEP 15 2020 DELTA ELECTRONICS INC 252 SHANG YING ROAD KUEI SAN TEL 886 0 3 3591968 TAOYUAN CITY 333 TAIWAN FAX 886 0 3 3591991 Plea...

Страница 2: ...nce 12 1 6 Thermal and Airflow 13 2 Electrical Specification 14 2 1 Indicator Connector 14 2 1 1 Power Supply Alarm Connector 14 2 1 2 Protection 15 3 Environmental Condition 17 3 1 Operating Temperat...

Страница 3: ...Part no Delta model no HEC1000PB Page 3 9 Reclaim 21 10 Versions 21...

Страница 4: ...objects on it Please pay attention to the following icons on the package If air conditioner is toppled over slanted or dropped unfortunately please follow below steps a stand for 12 hours to ensure re...

Страница 5: ...ing into wall or ceiling do not damage electrical wiring or hidden utilities 8 Be sure to use only the specified accessories and parts for installation work 9 Protective earth connection The enclosure...

Страница 6: ...onditioner while moving or storage 8 The hole in the bottom of the air conditioner should be connected to a sealed container through a drainpipe 9 The appliance is not to be used by persons including...

Страница 7: ...n for Approval Customer Description Air conditioner for Equipment with 1000 W Rated Cooling Capacity Through Wall Mounting Customer P N Rev Delta model no HEC1000PB Rev 02 Sample revision Date Code Sa...

Страница 8: ...od Dimension H x W x D without flange mm inch 700 x 500 x 200 27 7 x 19 8 x 7 9 Application Outdoor Weight Kg lbs 28 0 61 7 Mounting Method Door Side Color optional RAL7035 Environmental Protection Pe...

Страница 9: ...o HEC1000PB Page 9 Power Range Input Voltage VDC 48 Max Operating DC Current A 14 3 Alarm N A Dry Contact Output Key Components Controller Built in Smart Controller Fans Delta High Efficiency Blowers...

Страница 10: ...Part no Delta model no HEC1000PB Page 10 1 3 Dimension mm inch 1 Material Case SGCC Sheet 2 Finish Powder coating 75 120 uM Color RAL 7035 3 Dimensional Tolerance 1 mm...

Страница 11: ...Part no Delta model no HEC1000PB Page 11 1 4 Mounting Panel Cutout Inside Outside Gasket...

Страница 12: ...an clean the condenser with water directly The external side fan blade can also be cleaned with normal pressure water if there is dust accumulation Please do not use strong water jet to impact the cen...

Страница 13: ...protecting cover is sealed with silicon for IP55 requirement Please do not dismantle the sealed cover or will lose the quality assurance of the compressor 1 6 Thermal and Airflow The internal and ext...

Страница 14: ...3 N A N A 4 N A N A 5 N A N A Pin Description 3 Alarm 4 Alarm System alarm default setup Note Customers can setup the N O or N C by themselves when any alarm happen through display board d1 6 Dry cont...

Страница 15: ...rmally and the LED will light in green If the system gets into self test mode and the LED will flash in green Fan In When the inner fan is running normally and the LED will light in green Fan Out When...

Страница 16: ...PB Page 16 Allow reverse voltage 42 58 VDC Short Ckt If compressor UVW short for any both phase the compressor will not operate Compressor H T protection Tcomp 105 oC Eva L T protection TEVA 0 oC Powe...

Страница 17: ...otection Rating IP55 IEC60529 on external side GR487 on external side 4 Reliability Table Test item Condition High temperature IEC 60068 2 2 Low temperature IEC 60068 2 1 High temp High humidity IEC 6...

Страница 18: ...Table 7 1 System Setup Item System Parameter Default Range d1 1 System Version 2 5 N A d1 2 Alarm Logs 0 0 N A d1 3 Inside over temp Setup 60 oC 40 oC 70 oC d1 4 Auto Self Test Function Enable Enable...

Страница 19: ...ection 2 2 PWB Temperature Protection 2 3 IPM Temperature Protection 2 4 Amb Temperature Protection 2 5 3 Temperature Sensor Fault Amb Temperature Sensor 3 1 Eva Temperature Sensor 3 2 Cond Temperatur...

Страница 20: ...onditioner is running but the cabinet temperature is still high no obvious cooling effect 1 The air conditioner capacity is not match the load of the system 2 The ambient temperature is too high 3 Low...

Страница 21: ...te It must be taken to a special local authority differentiated waste collection center or to a dealer providing this service 10 Versions REV Description Owner Date 00 Issue SPEC VIC 2015 06 15 01 Mod...

Отзывы: