- 5 -
Adjust A/D Conversion Curve
Users can adjust the conversion curves according to the actual needs by changing the
Offset value (CR#28 ~ CR#31) and Gain value (CR#34 ~ CR#37).
Gain: The corresponding voltage/current input value when the digital output value =
16,000.
Offset: The corresponding voltage/current input value when the digital output value = 0.
Equation for voltage input Mode0: 0.3125mV = 20V/64,000 = 10V/32,000
Offset
Gain
Offset
V
V
X
Y
32000
10
16000
)
(
)
(
Y=Digital output, X=Voltage input
Equation for voltage input Mode4 / Mode5 / Mode6: 0.15625mV = 10V/64,000 =
5V/32,000
Offset
Gain
Offset
V
V
X
Y
32000
5
16000
)
(
)
(
Y=Digital output, X=Voltage input
Equation for current input Mode1 / Mode2: 0.625
μ
A = 40mA/64,000 = 20mA/32,000
Offset
Gain
Offset
mA
mA
X
Y
32000
20
16000
)
(
)
(
Y=Digital output, X=Current input
Equation for current input Mode3: 0.5
μ
A = 16mA/32,000
Adopt the Equation of current input Mode3, substitute Gain for 19200 (12mA) and
Offset for 6400 (4mA)
6400
19200
6400
32000
20
16000
)
(
)
(
mA
mA
X
Y
Y=Digital output, X=Current input
Mode 0:
Mode 1:
Voltage input
+32000
+16000
-16000
10V
-32000
-10V
5V
0
Gain
Offset
Digital
output
+32384
-32384
Current input
+32000
+16000
-16000
20mA
-32000
-20mA
10mA
0
Gain
Offset
Digital
output
+32384
-32384
Mode 0 of CR#2 ~ CR#5
-10V ~ +10V
,
Gain = 5V (16,000)
,
Offset = 0V (0)
Mode 1 of CR#2 ~ CR#5
20mA ~ +20mA
,
Gain = 10mA (16,000)
,
Offset = 0V (0)
Range of digital conversion
-32,000 ~ +32,000
Max./Min. range of digital
conversion
-32,384 ~ +32,384