Chapter 1 Introduction
1 - 3
1_
1.1
Specification
DVP02TK-S/DVP02TU-S
Supply voltage
24VDC
Max. rated power
consumption
2.4W, supplied by external power source in compliance with UL61010-2-201 \ IEC61131-2
Connector Type
European standard removable terminal block (Pin pitch: 3.5mm)
Operation/storage
temperature
Operation: 0°C ~ 55°C (temperature), 5 ~ 95% (humidity), Pollution degree: 2
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity), Attitude: up to 2000m;
For use in dry location only
Vibration/Shock
resistance
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc) / IEC 61131-2 & IEC 68-2-27
(TEST Ea)
Connection to
DVP-PLC
The modules are numbered from 0 to 7 automatically by their distance from DVP-PLC. Max. 8
modules are allowed to connect to DVP-PLC and will not occupy any digital I/O points.
I/O points
2 points of universals analog inputs (CH1, CH2), 2 analog outputs (OUT1, OUT2) or 4 digital
outputs (OUT1~OUT4)
General Analog Input
Input
CH1,
CH2
Thermal resistance: Pt100, JPt100, Pt1000, Ni100, Ni120, Ni1000, Cu50, Cu100, LG-Ni1000
Thermocouple : J, K, R, S, T, E, N, B, U, L, TXK (L), C, PL II
Voltage input: 0~+50mV, 100~+100mV, 0~+5V, 0~+10V
Current input: 0mA~+20mA, 4~+20 mA
Hardware Resolution
16 bits
Distance
100 meters
Input disconnection
detection
Supported by exceeded temperature input range
Analog / Digital Output
Analog
OUT1~
OUT2
Analog output, 12-bit: 0~+10V, 0/4~+20mA
Digital
OUT1~
OUT4
4 channels digital output, 250VAC, 60Hz/24VDC, 2A, Relay
4 channels digital output, Voltage pulse output, 24VDC, 300mA
A/D Function Specification
Analog / Digital
Voltage Input
Maximum rated input
0V~10V
0V~5V
Overall accuracy
(normal temperature)
±
0.5
%
Overall accuracy
(full temperature range)
±
1
%
Hardware resolution
16 bits
Input impedance
650K
Ω
Содержание DVP02TK-S
Страница 3: ......
Страница 19: ...DVP02TK S DVP02TU S Temperature Control Module Manual 1 14 _1 MEMO ...