8
If the “multistate” function is enabled, for example, writing in 0028H means enabling bit5 and bit3 at the same time.
If there is already a set value in 4824H and you would like to modify it, reset it to 0 before you set up a new value.
Opposite Output
Function
The 8 channels on DTE10T can be set to opposite output, that is, when the output is set to 0, the actual output will be 1.
How to Operate
To set CH1 and CH3 to opposite output, first write 1234H into the address 47F1H and then 0005H into address 4821H to set on CH1 (bit0)
and CH3 (bit2).
CH8
CH7
CH6
CH5
CH4
CH3
CH2
CH1
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Delayed Alarm
Function
When the set condition for alarms is met, the alarm will be enabled after a pre-set period of time.
How to Operate
Set up the time using the table below. Unit: second
CH
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Address for
delayed alarm
1990H
1991H
1992H
1993H
1994H
1995H
1996H
1997H
Output Limits
Function
The output is limited between the maximum and minimum percentages.
How to Operate
Set up relevant parameters using the table below.
CH
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Max. output (%)
1980H
1981H
1982H
1983H
1984H
1985H
1986H
1987H
Min. output (%)
1988H
1989H
198AH
198BH
198CH
198DH
198EH
198FH
Note: When the output volume is limited at 20 to 80%, it means the output volume 0 to 100% calculated by the controller is corresponding
to the actual output 20 to 80%.
Programmable Control Time Unit
Function
The unit of programmable control time can be “minute” or “second”.
How to Operate
Write 0 to the address to set the time unit to “minute” (default) or write 1 to set it to “second”.
CH
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Address for time unit
1978H
1979H
197AH
197BH
197CH
197DH
197EH
197FH