D
P M - C
5 2 0 / C 5 2 0 W O p e r a t i o n M a n u a l
4 - 6
_4
secondary-side current transformer.
9.
Press NEXT key to confirm the setting.
Note: You can go back to the previous setting item by pressing BACK key anytime, whether you have
completed or canceled the setting.
4.2.7
Potential Transformer Setup (PT)
Voltage for the primary-side potential transformer: ranging from 1 to 65535 V; default: 1 V.
Voltage for the secondary-side potential transformer: ranging from 1 to 9999 V; default: 1 V.
Steps:
1.
Press BACK key to enter the setting page.
2.
Press UP and DOWN keys at the same time for 5 seconds to unlock the setting.
3.
Press NEXT key to see the setting option CT & PT.
4.
Press DOWN key to enter the potential transformer (PT) setting page.
5.
Use UP and DOWN keys to select the number for the primary-side potential transformer.
6.
Press NEXT key to confirm the setting and start to set the next number for the primary-side
potential transformer.
7.
Repeat steps 5-6 till you complete the settings of the 5 digit number for the primary-side potential
transformer. Press NEXT key to set up the secondary-side potential transformer.
8.
When the option starts blinking, you can use UP and DOWN keys to select the number of the
secondary-side potential transformer.
9.
Press NEXT key to confirm the setting and start to set the next number for the primary-side
potential transformer.
10.
Repeat steps 5-6 till you complete the settings of the 4 digit number for the primary-side potential
transformer.
11.
Press NEXT key to confirm the setting.
Note: You can go back to the previous setting item by pressing BACK key anytime, whether you have
completed or canceled the setting.
4.2.8
Reset Setup (RST)
Default (DEF):
Restore all the settings back to the defaults (including wireless settings).
Energy (ENG):
Reset all the accumulated energy values and automatic energy values.
MaxMin (MM):
Clear all maximum values and minimum value logs.
Alarm (ALA):
Clear all the detected alarm logs.
Steps:
1.
Press BACK key to enter the setting page.
2.
Press UP and DOWN keys at the same time for 5 seconds to unlock the setting.
Содержание DPM-C520
Страница 1: ......
Страница 8: ...Chapter 1 Product Introduction 1 3 1_ 1 2 Overview DPM C520 DPM C520W...
Страница 11: ...DPM C520 C520W Operation Manual 1 6 _1 MEMO...
Страница 18: ...Chapter 2 Specifications 2 7 2_ DPM C520W Front DPM C520 C520W Back...
Страница 27: ...DPM C520 C520W Operation Manual 3 8 _3 _3 MEMO...
Страница 37: ...DPM C520 C520W Operation Manual 4 10 _4 3 Security Mode WPA WPA2 4 Password of AP password for WPA2 1234567890...
Страница 43: ...DPM C520 C520W Operation Manual 4 16 _4 Steps 1 Use DPMSoft to set up RS485 COM Port and connect to DPM C520W...
Страница 49: ...DPM C520 C520W Operation Manual 4 22 _4 MEMO...
Страница 50: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Страница 75: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 77: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 82: ...DPM C530 Operation Manual A 6 _A MEMO...