Chapter 4 Operation
4-3
4_
4.2
Setting Operation
4.2.1 Password Key (PASS)
Enter the password: The password key set for users to start operations. (Default: 0000)
Steps:
1.
Press NEXT key until the first figure starts flickering.
2.
Press UP or DOWN keys to select the first figure of the password.
3.
Press NEXT key to select the next figure.
4.
Repeat step 2 and 3 until the setting of the fourth figure is complete.
5.
Then press NEXT key to enter the setting page of power meter parameters.
Note:
In case that you enter a wrong figure, just press BACK key and the figure would stop flickering, then
press NEXT key to enter the figure again.
4.2.2 Station Setup (id)
Communication station (id):
The setting range of station is from 1 to 254 with 1 being the factory default
setting and 255 is set for the broadcasting station.
Steps:
1.
Press NEXT key and the figures would start flickering.
2.
Press UP and DOWN keys to select the figures of the station number.
3.
Press NEXT key to complete the setting.
Note:
You can go back to the previous setting item by pressing BACK key anytime, whether you have
completed or canceled the setting.