Delta Controls
Document Edition 1.9
Page 3 of 12
Size
•
4.5” x 2.75”x 1” (11.4 cm x 7 cm x 2.5 cm)
Weight
•
0.16 lb. (71 g.)
PCB Board Layout & Wiring
NOTE:
Do
not
use 4-wire multi-conductor cable. It will not meet the balanced cable
requirements for the MS/TP or LINKnet networks. Use two separate cables: one for
the network and the other for power.
Network
2-Wire Connection
(MS/TP or LinkNet)
Power
2-Wire Connection
(24 VAC)
Network Notes:
!
Ensure you use the specified balanced cable
and follow documented RS-485 installation
guidelines for MS/TP or LinkNet networks.
!
Do not terminate the shield on the BACs tat,
but ensure conductivity is maintained.
Power Notes:
!
If connected to LinkNet, Power may be
supplied from the Power Out port on a DAC
product.
!
Ensure polarity is observed when the same
transformer is connected to more than one
device.
!
If the same transformer is used for more than
one device, ensure it is sized properly.