UL864 Specific Considerations 

 

 

Wiring to and from the device shall be through power-limited circuits. 

Use only Core Components transformer, Model No. 120-024-100-2TF-CB, by Lectro 

Components Inc. to power the device. (Delta Part # 440008) 

Use only UL Listed Class 2 Power Supplies for auxiliary field devices. 

Use only UL Recognized Ethernet Switch, 571-580, by Siemens for Smoke Control Systems 

that utilize Ethernet communications. 

Impedance value for which ground faults are detected is zero ohms. 

Cautions or Warnings 

 

This controller is an Electro-statically sensitive device. Proper ESD protection (ground strap) 

should be used when installing this product so that damage to the product does not occur. 

Equipment damage or loss of data may occur if these procedures are not followed as 

specified. 

Installations requiring CE conformance

: All wiring for CE rated products must use an extra 

low voltage (SELV) or protective extra low voltage (PELV) transformer. Use safety-isolating 

transformers, (Class II transformer) per EN61558. The transformer must be rated for 100% 

duty cycle. 

Содержание DAC-633

Страница 1: ...controlling various packaged units and other equipment with small I O requirements As the controller is completely programmable GCL programs and BACnet objects can be tailored to the specific applica...

Страница 2: ...ations Impedance value for which ground faults are detected is zero ohms Cautions or Warnings This controller is an Electro statically sensitive device Proper ESD protection ground strap should be use...

Страница 3: ...ing The DAC 633 includes a plastic enclosure that can be quickly mounted with two screws not provided This controller should be mounted in an appropriate location within packaged equipment or another...

Страница 4: ...Delta Controls Page 4 of 12 Board Layout...

Страница 5: ...st still have a unique dip switch address even when using software to define the controller number DNA Controller Addressing The Dip Switch is a binary switch Each individual DIP switch represents a u...

Страница 6: ...gned to use a 24 VAC Class 2 power supply The proper specified cabling must be used 18 16 AWG 2 conductor wire A single transformer may be used to power multiple controllers and or auxiliary field dev...

Страница 7: ...d to ensure reliable communications 22 AWG twisted pair 100 120 ohms impedance 17 pF ft or lower capacitance with a braided or aluminum foil shield Controllers should always be wired together in a dai...

Страница 8: ...ors that use a 0 5 VDC signal 10V For sensors that use a 0 10 VDC signal Binary Output Power Source The binary triac outputs can be selected to use either an internal or external power source by placi...

Страница 9: ...ceiving data through the port If communication is good both LEDs will flash at a high rate Network NET2 MS TP RS485 Communication Status Indicators The green LED flashes to indicate when the controlle...

Страница 10: ...RJ 11 Jack Used with Delta Controls service tool devices for example CON 768 Inputs 6 Universal Inputs 10 bit jumper configurable for the following input types 0 5 VDC 0 10 VDC 10 K Thermistor Dry Con...

Страница 11: ...rmonics Class A EN 61000 3 3 1994 A1 2001 01 Power Line Fluctuations Pst 1 Plt 0 65 EN 61000 6 1 2001 Light Industrial Residential Immunity Requirements EN 61000 4 2 1995 A2 2000 11 ESD Immunity Level...

Страница 12: ...ul interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at...

Отзывы: