Object 6050h
:
vl slow down time
Index
6050h
Name
vl slow down time
Object Type
Variable
Data Type
UNSIGNED32
Read-Write Permission
RW
PDO MAPPING
SETTING
No
Setting Range
UNSIGNED32
Factory setting
10000
Unit
ms
This object is the time spent when the motor drive decelerates from 6042h to 0 RPM under the Velocity
Mode.
Object 6051h
:
vl quick stop time
Index
6051h
Name
vl quick stop time
Object Type
Variable
Data Type
UNSIGNED32
Read-Write Permission
RW
PDO MAPPING
SETTING
No
Setting Range
Motor drive parameter 01-45
Pr.01-45=0
,
Setting Range
:
10~600000
Pr.01-45=1
,
Setting Range
:
100~6000000
Factory setting
1000
Unit
ms
This object is at velocity mode. It’s the time required for decelerating from 6402h to 0 RPM.
Object 605Ah
:
Quick stop option code
Index
605Ah
Name
Quick stop option code
Object Type
Variable
Data Type
INTEGER16
Read-Write Permission
RW
PDO MAPPING
SETTING
No
Setting Range
0: Disable motor drive function
1: Decelerate to stop by slow down ramp then
Switch on Disabled (cannot be back to OP)
2: Decelerate to stop by quick stop ramp then
Switch on Disabled (cannot be back to OP)
5: Decelerate to stop by slow down ramp and
keep on Quick Stop status (can be back to OP)
6: Decelerate to stop by quick stop ramp and keep
on Quick Stop status (can be back to OP)
Factory Setting
2
This object is a choice behavior when 6040h (Controlword) triggers Quick Stop bit.
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com