VFD EtherNet/IP Option Card
Option Card Application Manual
27
4. Settings before Using
4.1 Drive Setting
If you need to operate the drive by using the option card via network, set the drive’s control to
option cards. Use the digital keypad to finish the setting by following the steps below:
1. After connecting with the option card successfully, check if the value of Pr.09-60 = 5
(EtherNet/IP).
2. Set Pr.09-75 = 0 (Static IP), and then set your own IP address.
3. Set the IP address of the option card (Pr.09-76–Pr.09-79), and its default value is
192.168.1.5. If you have modified the IP parameters manually, make sure that you set Pr.09-
91 = 2 to make the parameters valid.
4. Set Pr.00-20 = 8 (set the source of AUTO frequency command to option card)
5. Set Pr.00-21 = 5 (set the source of AUTO control to option card)
6. Set Pr.09-30 = 1 (set decoding method to 60xx or 20xx). For details on the decoding method,
see Section 4.2 <EtherNet/IP Control Method Standard>.
4.2 EtherNet/IP Control Method Standard
EtherNet/IP interface supports all control methods of the drive. Delta-defined control methods are
categorized into two types:
traditional method standard (Pr.09-30 = 0)
and
new method
standard (Pr.09-30 =1)
. The traditional method only supports speed control mode. The new
method supports all control modes of the drive, including speed, torque, position and homing.
EtherNet/IP
Control Method
Selection
Control Method
Speed
Torque
Position
Homing
Object
Instance
Attribute
Description
Object
Instance
Attribute
Description
Object
Instance
Attribute
Description
Object
Instance
Attribute
Description
Delta-defined Control
(Traditional
Method 20xx)
Pr.09-30 = 0
0x300
0x20
0x01
Target
speed
(Hz)
----- ----- ----- ----- ----- -----
Delta-defined Control
(New Method 60xx)
Pr.09-30 = 1
0x300
0x60
0x02
Target
speed
(Hz)
0x300
0x60
0x06
Target
torque
(%)
0x300
0x60
0x04
Position
command
L (signed
number)
----- -----
x300
0x60
0x03
Torque
Limit
(%)
0x300
0x60
0x07
Speed
limit
(Hz)
x300
0x60
0x05
Position
command
H (signed
number)
----- -----
EtherNet/IP
Control Method
Selection
Operation Control
Object
Instance
Attribute
Description
Delta-defined
Control
(Traditional
Method 20xx)
Pr.09-30 = 0
0x300
0x20
0x00
RUN command
Delta-defined
Control
(New Method 60xx)
Pr.09-30 = 1
0x300
0x60
0x00
RUN command