TECHNICAL DATASHEET

 

CliQ DIN Rail Power Supply 

24V 60W 1 Phase / DRP024V060W1AA

 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (November 2020, Rev. 08)  

 

8

 

Output Load De-rating VS Input Voltage 

 

 

 

Assembly & Installation 

The power supply unit (PSU) can be mounted on 35mm DIN rails in accordance with EN 60715. The device should be installed with input 

terminal block at the bottom.  

 

Each device is delivered ready to install. 

 

Mounting 

 

 

 

 

 

 

 

            

 

 

 

In accordance to EN 60950 / UL 60950 and EN 62368 / UL 62368, flexible cables require ferrules.  

Use appropriate copper cables designed to sustain operating temperature of at least 75°C or more to fulfill UL requirements. 

 

For stranded wires, it is recommended to use suitable lug to crimp wires. 

Dismounting 

Fig. 2.1   Mounting 

 

Snap on the DIN rail as shown in Fig. 2.1: 

1.  Tilt the unit upwards and insert it onto the DIN rail. 

2.  Push downwards until stopped. 

3.  Press against the bottom front side for locking. 

4.  Shake the unit slightly to ensure that it is secured. 

 

Fig. 2.2   Dismounting 

 

To uninstall, pull or slide down the latch with screw driver as 

shown in Fig. 2.2. Then slide the power supply unit (PSU) in the 

opposite direction, release the latch and pull out the power 

supply unit (PSU) from the rail. 

 

 

No output power de-rating across the entire 

input voltage range 

Содержание CliQ DRP024V060W1AA

Страница 1: ...The rugged metal has a compact body at only 32mm which is both shock and vibration resistant according to IEC 60068 2 standard The product operates within a wide temperature range from 20 C to 80 C Th...

Страница 2: ...al Output Voltage 24Vdc Factory Set Point Tolerance 24Vdc 2 Output Voltage Adjustment Range 22 28Vdc Output Current 2 50A continuously operating at 24 3 75A Power Boost for 3 seconds at 24V refer to t...

Страница 3: ...power by 2 5 C Horizontal Mounting 0 C de rate power by 1 C 50 C de rate power by 2 5 C 70 C de rate power by 4 C Operating Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 2 000 Meters 6 56...

Страница 4: ...E191395 UL 62368 1 and CSA C22 2 No 62368 1 File No E191395 CSA CSA C22 2 No 60950 1 and UL 60950 1 File No 181564 CB Scheme IEC 60950 1 IEC 62368 1 Industrial Control Equipment UL cUL listed UL 508 a...

Страница 5: ...st IEC 61000 4 4 Level 3 Criteria A1 2kV Surge IEC 61000 4 5 Level 3 Criteria A1 Common Mode2 2kV Differential Mode3 2kV Conducted IEC 61000 4 6 Level 3 Criteria A1 150kHz 80MHz 10Vrms Power Frequency...

Страница 6: ...cified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com November 2020 Rev 08 6 Block Diagram Device Description 1 Input terminal block connector 2 Output terminal block connect...

Страница 7: ...mperature Protection When activated the output voltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep th...

Страница 8: ...les Use appropriate copper cables designed to sustain operating temperature of at least 75 C or more to fulfill UL requirements For stranded wires it is recommended to use suitable lug to crimp wires...

Страница 9: ...the device as well as a lateral distance of 50mm 1 97 inch to other units Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power...

Страница 10: ...0 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush current is the pea...

Страница 11: ...ed and approved on 20A UL and 16A IEC branch circuits without additional protection device An external protection device is only required if the supplying branch has an ampacity greater than above Thu...

Страница 12: ...rrent will operate in Hiccup mode as shown in the illustration in the OLP OCP section on this page The power supply will return to normal operation after the short circuit is removed Overvoltage Prote...

Страница 13: ...em load from Vout Please note that output voltage Vout from DRR module will be VO output voltage of power supply Vdrop in DRR module Vdrop will vary from 0 60V to 0 90V Typical 0 65V depending on the...

Страница 14: ...arth wire or to the machine ground Fig 7 2 of 3 Phase System Input Operation Connection Diagram 2 of 3 Phase System Input Operation Delta s CliQ can use on 2 of 3 phase system Please refer to the foll...

Страница 15: ...environment complying with EN 61000 3 2 is only necessary under special conditions Complying to this standard can have some technical drawbacks such as lower efficiency as well as some commercial aspe...

Отзывы: