Delta ASDA-A2 Series Скачать руководство пользователя страница 6

Item 

Content 

Inspection before 
operation 
(Control power is not 
applied) 

Inspect the servo drive and servo motor to insure they were not damaged. 
To avoid an electric shock, be sure to connect the ground terminal of servo drive to the 
ground terminal of control panel.   
Before making any connection, wait 10 minutes for capacitors to discharge after the 
power is disconnected, alternatively, use an appropriate discharge device to 
discharge. 
Ensure that all wiring terminals are correctly insulated. 
Ensure that all wiring is correct or damage and or malfunction may result. 
Visually check to ensure that there are not any unused screws, metal strips, or any 
conductive or inflammable materials inside the drive. 
Never put inflammable objects on servo drive or close to the external regenerative 
resistor. 
Make sure control switch is OFF. 
If the electromagnetic brake is being used, ensure that it is correctly wired. 
If required, use an appropriate electrical filter to eliminate noise to the servo drive. 
Ensure that the external applied voltage to the drive is correct and matched to the 
controller.   

Inspection during 
operation 
(Control power is 
applied) 

Ensure that the cables are not damaged, stressed excessively or loaded heavily. 
When the motor is running, pay close attention on the connection of the cables and 
notice that if they are damaged, frayed or over extended. 
Check for abnormal vibrations and sounds during operation. If the servo motor is 
vibrating or there are unusual noises while the motor is running, please contact the 
dealer or manufacturer for assistance. 
Ensure that all user-defined parameters are set correctly. Since the characteristics of 
various machines are different, in order to avoid accident or cause damage, do not 
adjust the parameter abnormally and ensure the parameter setting is not an excessive 
value. 
Ensure to reset some parameters when the servo drive is off (Please refer to Chapter 
8 of the user manual). Otherwise, it may result in malfunction. 
If there is no contact sound or there be any unusual noises when the relay of the servo 
drive is operating, please contact your distributor for assistance or contact with Delta. 
Check for abnormal conditions of the power indicators and LED display. If there is any 
abnormal condition of the power indicators and LED display, please contact your 
distributor for assistance or contact with Delta. 

 

 Wiring Methods 

Three-Phase Power Supply Connection (For all models) 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 Basic Wiring 

400W ~ 1.5kW models (with built-in regenerative resistor and fan) 

R

e

ct

if

ie

C

ir

cu

it

C

N

1

R

e

g

e

n

e

ra

tio

n

 C

ir

cu

it

C

o

n

tr

o

P

o

w

e

r

L

in

e

a

S

ca

le

P

h

a

se

 L

o

ss 

D

e

te

ct

io

n

 

 

2kW ~ 5.5kW models (without built-in regenerative resistor) 

 

 
 
 
 
 

 Servo Drive Dimensions 

400W ~ 1.5Kw models:   

 

 

Weight 

2.0

4.4

 

2kW ~ 5.5kW models: 

123.5(4.86)

107(4.21)

Ø6

(0.2

4)

70(2.76)

205.5(8.09)

2

4

5

(9

.6

4

)

2

3

0

(9

.0

6

)

SCREW: M4×0.7
MOUNTING SCREW TORQUE:14(kgf-cm)

 

Weight 

4.6

10.1

 

 

NOTE

 

1)    Dimensions are in millimeters and (inches). 
2)    Weights are in kilograms and (pounds). 
3)    For the actual appearance, please refer to the actual purchased product. 
4)    In this instruction sheet, actual measured values are in metric units. The units in   
        (imperial units) are for reference only. Please use metric for precise measurements. 

 
 
 
 
 
 
 
 
 
 

Содержание ASDA-A2 Series

Страница 1: ...6 2 1 AWG14 0 82 AWG18 2 1 AWG14 ASD A2 0743 E ECMA J10807 S 1 3 AWG16 2 1 AWG14 0 82 AWG18 2 1 AWG14 ASD A2 1043 E ECMA K11310 S 1 3 AWG16 2 1 AWG14 1 3 AWG16 2 1 AWG14 ASD A2 1543 E ECMA K11315 S 1...

Страница 2: ..._10 DC24V 10 _ DC24V Power Supply U V W CN6 CN5 CN2 DI CN3 EtherCAT CNSTO M 2kW 5 5kW DC24V DC0V PWM FPGA DSP Data Bus CN4 USB UART A D GATE DRIVE CN1 A B Z MODE SHIFT SET CHARGE 3 3V 15V 5V 24V C S T...

Страница 3: ...6 2 1 AWG14 0 82 AWG18 2 1 AWG14 ASD A2 0743 E ECMA J10807 S 1 3 AWG16 2 1 AWG14 0 82 AWG18 2 1 AWG14 ASD A2 1043 E ECMA K11310 S 1 3 AWG16 2 1 AWG14 1 3 AWG16 2 1 AWG14 ASD A2 1543 E ECMA K11315 S 1...

Страница 4: ...6 CN5 CN2 DI CN3 EtherCAT CNSTO M 2kW 5 5kW DC24V DC0V PWM FPGA DSP Data Bus CN4 USB UART A D GATE DRIVE CN1 A B Z MODE SHIFT SET CHARGE 3 3V 15V 5V 24V C S T D R P USB 12V 380 480V _10 DC24V 10 _ DC2...

Страница 5: ...cal knowledge should conduct maintenance and inspection Ensure that the Charge indicator ceases when performing any maintenance inspection or repairing Main Circuit Wiring Install the encoder cables i...

Страница 6: ...motor is running please contact the dealer or manufacturer for assistance Ensure that all user defined parameters are set correctly Since the characteristics of various machines are different in order...

Страница 7: ...otor besleme kablolar ayr kablo bloklar ndan ge irilmelidir Bloklar aras mesafe 30cm 11 8inch ve zeri olmal d r Enkoder PG geri besleme sinyali i in ok damarl sarmal ift kablo veya ok damarl ekranl if...

Страница 8: ...i ini kontrol ediniz al ma s ras nda anormal titre imleri ve sesleri kontrol ediniz E er motor al yor iken anormal bir ekilde titriyor veya ses kar yor ise teknik servisimizle ba lant ya ge iniz T m k...

Отзывы: