Troubleshooting ASDA-B2-F
9-4
September, 2015
9
9.3 Alarm of Motion Control
Display
Alarm Name
Alarm Description
Corrective
Actions
Corresponding
DO
Servo
Status
AL201
An error occurs when
loading DMCNET data
An error occurs when
loading data from
EEPROM.
Re-power on
WARN
ON
AL235
PR command overflows
Feedback position
counter overflows and
executes the absolute
positioning command.
Controller
issues alarm
reset
command.
WARN ON
AL245
PR positioning is over
time
The execution of
positioning command
exceeds the time limit.
Same as
above
WARN ON
AL283
Forward software limit
The value of position
command is bigger than
forward software limit.
The fault will
be cleared
automatically
when the
motor
operates
backwards.
WARN ON
AL285
Reverse software limit
The value of position
command is smaller than
reverse software limit.
The fault will
be cleared
automatically
when the
motor
operates
backwards.
WARN ON
AL289
Feedback position
counter overflows
Feedback position
counter overflows.
Controller
issues alarm
reset
command.
WARN ON
AL301
DMCNET fails to
synchronize
DMCNET mode fails to
synchronize with the
controller.
Same as
above
WARN ON
AL302
The synchronized signal
of DMCNET is sent too
fast
The synchronized signal
of DMCNET is sent too
fast.
Same as
above
WARN ON
AL303
The synchronized signal
of DMCNET is sent too
slow
The synchronized signal
of DMCNET has not
been received in time.
Same as
above
WARN ON
AL304
DMCNET IP command
fails
Command cannot be
sent in DMCNET mode.
Same as
above
WARN ON
AL555
System failure
DSP processing error.
N/A
N/A
No
switching
Note:
If an alarm occurs and is different from the alarm showed in Alarm of Servo Drive,
Alarm of DMCNET
Communication
and
Alarm of Motion Control
, please contact local distributors or technical personnel.
Содержание ASD-B2-0121-F
Страница 3: ...September 2015 This page is intentionally left blank...
Страница 9: ...VI September 2015 This page is intentionally left blank...
Страница 17: ...Inspection and Model Explanation ASDA B2 F 1 8 September 2015 1 This page is intentionally left blank...
Страница 29: ...Installation ASDA B2 F 2 12 September 2015 2 This page is intentionally left blank...
Страница 117: ...Control Mode of Operation ASDA B2 F 6 28 September 2015 6 This page is intentionally left blank...
Страница 185: ...Parameters ASDA B2 F 7 68 September 2015 7 This page is intentionally left blank...
Страница 199: ...Communications ASDA B2 F 8 14 September 2015 8...
Страница 201: ...Communications ASDA B2 F 8 16 September 2015 8 This page is intentionally left blank...
Страница 217: ...Troubleshooting ASDA B2 F 9 16 September 2015 9 This page is intentionally left blank...
Страница 239: ...Absolute System ASDA B2 F 10 22 September 2015 10 This page is intentionally left blank...
Страница 265: ...Appendix A Specifications ASDA B2 F A 26 September 2015 A This page is intentionally left blank...
Страница 287: ...Appendix C Basic Inspection and Maintenance ASDA B2 F C 4 September 2015 C This page is intentionally left blank...