Chapter 7 Alarm
23
Chapter 7 : Alarm
No.
Condition
Alarm
1
Battery Mode
The audible alarm beeps once every 2.1 seconds.
2
Low Battery
The audible alarm beeps once every 0.6 second.
3
Battery
Missing/ Weak
Battery/ Battery
Replacement/ *
The audible alarm beeps once every 2.1 seconds.
4
Overload
1. Overload_105%~125%: The audible alarm beeps
once every 2.1 seconds.
2. Overload_125%~150%: The audible alarm beeps
once every 0.6 seconds.
5
Fault
The audible alarm beeps continuously for 5 seconds
when the UPS detects an internal fault.
NOTE :
*
: After reconnecting or replacing the batteries, it might take a while for
the UPS to switch off the alarm automatically. If, after a period of time, the
audible alarm still exists, the user must manually initiate a battery test (press
and hold the button for 3 seconds and release it after you hear one beep)
to clear the alarm.