Amplon N Series
Chapter 6 : Turn-on, Cold Start & Turn-off Procedures
NOTE :
Please refer to
Chapter 3 : Operation Panel
to learn how to operate the
operation panel and understand the display meaning.
6.1 Turn-on Procedures
After the UPS is connected to the AC utility, the AC utility supplies power to the
UPS. The UPS is initially set in ‘STANDBY mode’. To turn on the UPS, press and
hold the
button for 3 seconds and release it after you hear one beep.
6.2 Cold Start Procedures
Even when there is no utility power, you can still turn on the UPS. Just press and
hold the
button for 3 seconds, release it after you hear one beep, and the UPS
will start up and run in battery mode.
6.3 Turn-off Procedures
1. In on-line mode, if you want to turn off the UPS, press and hold the
button
for 3 seconds and release it after you hear one beep. The inverter will turn off
and the UPS will transfer to standby mode.
The UPS will keep charging the batteries when the UPS is in standby mode
even though the
button has been pressed. To fully turn off the UPS, it is
advised to unplug the input power cord.
2. In battery mode, if you want to turn off the UPS, press and hold the
button
for 3 seconds and release it after you hear one beep. The UPS will turn off its
output.