Chapter 12 : Maintenance
12.1 UPS
z
UPS Cleaning
Regularly clean the UPS, especially the slits and openings, to ensure that the
DLUIUHHO\ÀRZVLQWRWKH836WRDYRLGRYHUKHDWLQJ,IQHFHVVDU\XVHDQDLUJXQ
to clean the slits and openings to prevent any object from blocking or covering
these areas.
z
UPS Regular Inspection
Regularly check the UPS every half year and inspect:
1. Whether the UPS, LEDs, and alarm function are operating normally.
2. Whether battery voltage is normal. If battery voltage is too high or too low,
¿QGWKHURRWFDXVH
12.2 Batteries
The RT series UPS uses sealed lead-acid batteries. Though the typical battery
life cycle is 3~5 years, the battery life depends on the temperature, usage, and
charging/ discharging frequency. High temperature environments and high charging/
discharging frequency will quickly shorten the battery life. The UPS does not require
user maintenance; however, the batteries should be checked periodically. Please
follow the suggestions below to ensure a normal battery lifetime.
z
Keep the usage temperature at 20°C ~ 25°C.
z
Idle batteries must be fully recharged every three months if the UPS needs to be
stored for an extended period of time. Please fully charge the batteries (internal
and external) until the battery capacity percentage shown on the UPS’s LCD is
100% (
100 %
).
NOTE :
If the UPS’s internal batteries need to be replaced, please contact
qualified service personnel. During battery replacement, the loads
connected to the UPS will not be protected if input power fails.