Chapter 8 : Operation
8.1 Start-up
NOTE :
1. Before start-up, ensure that the batteries are fully charged. Before
using the UPS for the first time, please check the battery capacity and
the charging settings. Make sure that you charge the batteries until the
battery capacity percentage shown on the UPS’s LCD is 100% (
100 %
).
2. The configurable internal battery string quantity ranges from 16 to 22.
Please make sure that the actual quantity of battery strings are the same
DVWKDWFRQ¿JXUHGRQWKH/&'6HWXSWKHFRUUHVSRQGLQJFKDUJHFXUUHQW
based on the total battery amp-hour.
3. If the UPS connects to an inductive load, the inrush current (initial surge
current) may restart the inverter. To avoid this situation, please turn on the
inductive load in bypass mode before starting up the inverter.
z
Start-up with AC Input
1
9HULI\LIWKH836¶VLQSXWFRUGPHHWVZLWK1/ *RIWKHZDOOVRFNHWDQGWKH
utility AC power works normally.
2
Switch on the input protective device (see
)LJXUH
) installed between
the UPS and the utility AC power. After that, the UPS will enter into the
Initial Setting Screen
(please refer to
,QLWLDO6HWWLQJ6FUHHQ
for more
information).
3
Press and hold the
ON/ OFF
button (
) for 3 seconds to start up the
UPS. Release the button after you hear one beep and the UPS will start up.
After the UPS performs self-diagnosis, the UPS will run in
ON-LINE
mode.